Water piping – ClimaCool UGW Manual User Manual

Page 13

Advertising
background image

11

www.climacoolcorp.com

LOAD 1

FROM CHILLER BANK

TYPICAL LOAD BYPASS VALVE ARRANGEMENT

TO CHILLER BANK

LOAD 2

LOAD 3

LOAD X

TYPICAL CHILLED AND HOT WATER

LOAD SIDE BYPASS VALVES

SIZE EQUIVALENT TO ONE MODULE

WORTH OF FLOW

Figure 8 - Typical Load Bypass Valve Arrangement

Modules can be designated for fixed bypass for heating,

cooling and source flow, however, this limits the number of

modules remaining for that duty . Also, with a module acting

as a bypass increased wear of heat exchangers may be

caused by abrasion from bypass flow.

ClimaCool offers two types of water header bypass kits,

direct return (Figure 6) and reverse return (Figure 7) as

shown on page 10 . The bypass kits must be installed on

each water source loop and controls are integrated with the

CoolLogic software . Installation location can be found on

page 12 – Water Piping Configuration.

This bypass can also be created with field supplied piping.

The design piping must accommodate one module’s worth

of design flow, and be positioned so that the temperature

and differential flow sensors sense active flow in the

bypass mode . See Figures 9 and 10 on page 12 - Water

Piping Configuration. The field supplied piped chiller/

heater system bypass must be controlled by others. There

are system communication delays, polling and network

conflicts that strictly prohibit the use of ClimaCool sensors

and controls for control of field supplied bypasses or other

field supplied items. Recommended method is to control via

differential pressure or gpm flow meters across the chilled

water/evaporator, hot water/condenser water systems .

Load Side System Bypass (Air Handlers, Fan

Coils, etc.)

A load system bypass is required for preventing pump

deadheading, allowing active flow system sensing and

preventing starving flow from the chiller/heater system.

Examples of an acceptable load side system bypass are:

•Utilize a quantity of 3-way control valves on the largest

loads farthest from the chiller/heater system .

•Field piping with a control valve to provide a bypass across

the larger system loads when their 2-way valves go closed .

Please refer to Figure 8 for a typical load bypass

valve arrangement . The load side system bypass should

be sized for an absolute minimum of one module’s worth

of design flow. (Please refer to selection submittals for

design flow rates). A minimum of (6) six gallons per

nominal system ton are also required to maintain proper

system thermal inertia. This is to avoid short cycling of

compressors in the chiller/heater system as well as prevent

nuisance alarms.

Water Piping

Advertising