Water Treatment

Water quality is of the utmost importance for the proper

care and maintenance of the modular chiller system.

Proper water treatment is a specialized industry and it is

recommended to consult an expert in this field to analyze

the water for compliance with the water quality parameters

listed in Table 1 . The materials exposed to the water are

type 316 stainless steel, pure copper and carbon steel .

Other materials may exist external to the ClimaCool chiller .

It is the user’s responsibility to ensure these materials are

compatible with the treated water . Regular treatment

of the water will increase longevity of your system .

Failure to provide adequate filtration or treatment of

evaporator and condenser water will void the ClimaCool

module’s warranty.

Heavy-Contaminated Water

In such instances whereby the particulates in the water are

excessive, it is recommended to install an intermediate plate

and frame heat exchanger to isolate the ClimaCool chiller

from the building water system .

Cooling Tower

The cooling tower should be located away from sources of

external contaminates such as trees, dust or grass cuttings .

Insect infiltration can be reduced by eliminating lights near

the tower . A periodic visual inspection of the tower system

should be made and contaminates removed as required .

CAUTION

• Excessive Chlorine, Undissolved Solids and

other improper water quality conditions

WILL DAMAGE the internal heat exchanger and

WILL VOID YOUR WARRANTY!

• Please refer to the Installation and Operations

Manual for water quality parameters and

maintenance instructions.

For Warranty information, go to www.climacoolcorp.com

95B0051N01

Table 1 - Water Quality Parameters

WATER CONTAINING

CONCENTRATION

Ammonia

Less than 2.0 mg/l

CaCO

3

Alkalinity

30 - 500 mg/l

CaCO

3

Hardness

30 - 500 mg/l

Chlorides

Less than 200 mg/l

Dissolved Solids

Less than 1000 mg/l

Iron

Less than 5.0 mg/l

Manganese

Less than 0.4 mg/l

Nitrate

Less than 100 mg/l

pH

7.0 - 9.0

Sulphate

Less Than 200 mg/l