Control Access Display Table

Page 9 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

/C1SucPr: (ps)

Module 1 Comp 1 Suction
Pressure

m1_c1_suc_pres_stat_5

40.6

FALSE

C1DisTmpCal: (F)

M1C1 DIS Temp Calib. Point

m1c1_disch_temp_cp_5

0.0

-250

250

TRUE

/C1DisTp: (F)

Module 1 Comp 1 Disch Temp

m1_c1_disch_temp_stat_5

110.3

FALSE

C1SucTempCal: (F)

M1C1 SUC Temp Calib. Point

m1c1_suc_tmp_cp_5

0.0

-250

250

TRUE

/C1SucTp: (F)

Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5

53.6

FALSE

C1CompAmpCal:

M1C1 Amps Calib. Point

m1c1_amps_cp_5

3.0

-250

250

TRUE

/C1 Amps:

Module 1 Comp 1 Amps

m1c1_amps_stat_5

33.6

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

LOCK WATER TEMPS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Lock Main Header Water & Air Temps
Evap Wat In Lock :

Lock CHWR Temp

lock_chwr_1

No

Off, On

TRUE

Evap Wat In Lock Value : (F)

CHWR Lock Value

chwr_lock_val_1

54.0

0

165

TRUE

Evap Wat Out Lock:

Lock EVAP LVG TMP

lock_chws_1

No

Off, On

TRUE

Evap Wat Out Lock Value: (F)

EVAP LVG TMP Lock Value

chws_lock_val_1

43.0

0

165

TRUE

Cond Wat In Lock :

Lock CWS Temp

lock_cws_1

No

Off, On

TRUE

Cond Wat In Lock Value : (F)

CWS Lock Value

cws_lock_val_1

85.0

0

165

TRUE

Cond Wat Out Lock:

Lock CWR Temp

lock_cwr_1

No

Off, On

TRUE

Cond Wat Out Lock Value: (F)

CWR Lock Value

cwr_lock_val_1

58.0

0

165

TRUE

Outdoor Air Lock:

Lock CHWS Temp

lock_oat_1

Yes

Off, On

TRUE

Outdoor Air Lock Value: (F)

OAT Lock Value

oat_lock_val_1

61.0

-20

140

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

SCREW PID SEQUENCING DATA
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic PID Sequencing Data
VFD Minimum VDC Input: 4.3

VFD Minimum VDC Input

vfd_min_vdc_1

4.4

0

10

TRUE

VFD Minimum VDC In 3 Scr: 6.16

VFD Minimum for Three Screws vfd_min_vdc_three_scr_1

6.16

0

10

TRUE

VFD Minimum VDC In 4 Scr: 7.17

VFD Minimum for Four Screws

vfd_min_vdc_four_scr_1

7.17

0

10

TRUE

VFD Maximum VDC Input: 10.00

VFD Maximum VDC Input

vfd_max_vdc_1

10.0

0

10

TRUE

VFD Start PID for One Scr: 33

VFD Start PID for One Screw

vfd_start_pid_one_scr_1

33.0

0

500

TRUE

VFD Min PID for One Scr: 34

VFD Minimum PID for One
Screw

vfd_min_pid_one_scr_1

34.0

0

500

TRUE

VFD Max PID for One Scr: 75

VFD Maximum PID for One
Screw

vfd_max_pid_one_scr_1

75.0

0

500

TRUE

VFD Max One PID Min Two Scr: 85

VFD Max One PID Min Two
Screws

vfd_max_one_pid_min_two_scr_1

85.0

0

500

TRUE

VFD Min PID for Two Scr: 86

VFD Minimum PID for Two
Screws

vfd_min_pid_two_scr_1

86.0

0

500

TRUE

VFD Interim PID Two Scr: 123

VFDInterim PID for One Full One
Min Screws

vfd_interim_pid_two_scr_1

123.0

0

500

TRUE

VFD Max PID for Two Scr: 160

VFD Maximum PID for Two
Screws

vfd_max_pid_two_scr_1

160.0

0

500

TRUE

VFD Max Two PIDMinThree Scr:170

VFD Max Two PID Min Three
Screws

vfd_max_two_pid_min_three_scr_1

170.0

0

500

TRUE

VFD Min PID for Three Scr: 171

VFD Minimum PID for Three
Screws

vfd_min_pid_three_scr_1

171.0

0

500

TRUE

VFD IntPID One Full;Two Min:195

VFDInterim PID for One Full &
Two Min Screws

vfd_interim_pid_one_full_two_min_s
cr_1

195.0

0

500

TRUE

VFD IntPID Two Full;One Min:220

VFD Interim PID for Two Full &
One Min Screws

vfd_interim_pid_two_full_one_min_s
cr_1

220.0

0

500

TRUE

VFD Max PID for Three Scr: 245

VFD Maximum PID for Three
Screws

vfd_max_pid_three_scr_1

245.0

0

500

TRUE

VFD Max 3 PID Min Four Scr: 255

VFD Max Three PID Min Four
Screws

vfd_max_three_pid_min_four_scr_1

255.0

0

500

TRUE

VFD Min PID for Four Scr: 256

VFD Minimum PID for Four
Screws

vfd_min_pid_four_scr_1

256.0

0

500

TRUE

VFD IntPID One Full;3 Min: 274

VFDInterim PID for One Full &
Three Min Screws

vfd_interim_pid_one_full_three_min
_scr_1

274.0

0

500

TRUE

VFD IntPID Two Full;Two Min:292

VFD Interim PID for Two Half &
One Min Screws

vfd_interim_pid_two_full_two_min_s
cr_1

292.0

0

500

TRUE

VFD IntPID 3 Full; One Min: 311

VFD Interim PID for Three Full
One Min Screws

vfd_interim_pid_three_full_one_min
_scr_1

311.0

0

500

TRUE

VFD Max PID for Four Scr: 330

VFD Maximum PID for Four
Screws

vfd_max_pid_four_scr_1

330.0

0

500

TRUE

VFD Last PID: 340

VFD Last PID

vfd_last_pid_1

340.0

0

500

TRUE

Screw Runtime Before Flush 8.0h

Screw Runtime in Minutes

scr_runtime_before_flush_1

4.0

0

999

TRUE

Use Screw Flush Cycle

Use Screw Flush Cycle

use_scr_flush_1

Yes

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

Page 10 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

MASTER MICRO FACTORY
SETUP FN8

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Master Ctrlr Fact Setup FN8
FN5
LINK(S): MODULE SIZE SELECTOR,PID COOL STG1 SETUP,PID HEAT STG1 SETUP,FIXED OPEN MODULE MENU,MOTORIZED VALVE OPTION,MOT VLV SIGNAL TO CLOSE MENU,
MASTER INPUT CHNLS 6, &10 SETUP,MASTER INPUT CHNL 7 DEM LIMIT SETUP,MASTER INPUT 8 & 11 SETUP,WATER MAINS & AIR TEMP LIMITS,STARTUP & STAGE DELAYS,
ALL MODULE COMP UNLOAD STATUS,AUTO HEAT TRG RESET ON OAT,COMPR SEQUENCING METHOD,HEAT BIN LOAD CAP% STATUS,COOL BIN LOAD CAP% STATUS,
MAIN TXV PID SETTINGS,MAIN TXV PSI PID SETTINGS,M1 & M2 MAIN TXV SETTINGS,M3 & M4 MAIN TXV SETTINGS,MODULE ALARM CONDITION RETRIES,
MODULE NUMBER MENU,KEYPAD,PREV, SYSTEM SETUP, HOME, ALARM

MODULE SIZE SELECTOR
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Size Selector Screen Legend
Mod1 Size:
/ 1= Not Used/4=80Ton Mod

Module 1 Size

mod1_size_1

65 Ton

1

4

TRUE

Mod2 Size:
/NOTE:DO NOT SELECT 2 OR 3

Module 2 Size

mod2_size_1

65 Ton

1

4

TRUE

Mod3 Size:

Module 3 Size

mod3_size_1

65 Ton

1

4

TRUE

Mod4 Size:

Module 4 Size

mod4_size_1

65 Ton

1

4

TRUE

Mod5 Size:

Module 5 Size

mod5_size_1

Not Used

1

4

TRUE

Mod6 Size:

Module 6 Size

mod6_size_1

Not Used

1

4

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

PID COOL STG1 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Cool PID Stage #1 Setup
Stage One Cool PID Output : (%)

Stage 1 Cooling PID

stg1_clg_pid_1

106.719604

FALSE

Stage One Cool PID Interval:

Clg PID Interval

clg_interval_1

8.0 sec

1

100

TRUE

Stage One Cool PID P-Gain :

Clg PID P-gain

clg_p_gain_1

18.0

0

999

TRUE

Stage One Cool PID I-Gain#1:

Clg PID I-gain

clg_i_gain_1

0.35

0

99

TRUE

Max Cool Ramp Rate: - (F) (/min)

MAX COOL RAMP RATE

max_cool_ramp_rate_1

10.0 °F/min

1

20

TRUE

Clg PID Rise Fast: (%/min)

Clg PID Rise Fast

clg_rise_fast_1

12.0 sec

1

300

TRUE

Clg PID Rise Slow: (%/min)

Clg PID Rise Slow

clg_rise_slow_1

5.0 sec

1

300

TRUE

Clg PID Fall: (%/min)

Clg PID Fall

clg_fall_1

22.0

2

300

TRUE

Cool Deadbd1:

Clg PID DB1

clg_db1_1

0.3

0

99

TRUE

/CoolDeadbd2:

Clg PID DB2

clg_db2_1

0.0

0

99

TRUE

Stage One Cool PID I-Gain#2:

Clg PID IG2

clg_ig2_1

0.01

0

99

TRUE

PID Switching Differential: (%)

PID Differential Factor

pid_diff_fact_1

5.0

-100

100

TRUE

Cool Cntrl Setpt Offset: (F)

Cool Control Setpoint Offset

cl_cntrl_spt_offset_1

0.0

-250

250

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

PID HEAT STG1 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat PID Stage #1 Setup
Stage One Heat PID Output : (%)

Stage 1 Heating PID

stg1_htg_pid_1

0.0

FALSE

Stage One Heat PID Interval:

Htg PID Interval

htg_interval_1

2.0 sec

1

100

TRUE

Stage One Heat PID P-Gain :

Htg PID P-gain

htg_p_gain_1

20.0

0

999

TRUE

Stage One Heat PID I-Gain#1:

Htg PID I-gain

htg_i_gain_1

0.25

0

99

TRUE

Max Heat Ramp Rate: (F) (/min)

MAX HEAT RAMP RATE

max_heat_ramp_rate_1

10.0 °F/min

1

99

TRUE

Htg PID Rise Fast: (%/min)

Htg PID Rise Fast

htg_rise_fast_1

12.0 sec

1

300

TRUE

Htg PID Rise Slow: (%/min)

Htg PID Rise Slow

htg_rise_slow_1

4.0 sec

1

300

TRUE

Htg PID Fall: (%/min)

Htg PID Fall

htg_fall_1

25.0

2

300

TRUE

HeatDeadbd1:

Htg PID DB1

htg_db1_1

0.1

0

99

TRUE

/Heat Deadbd2:

Htg PID DB2

htg_db2_1

0.0

0

99

TRUE

Stage One Heat PID I-Gain#2:

Htg PID IG2

htg_ig2_1

0.0

0

99

TRUE

PID Switching Differential: (%)

PID Differential Factor

pid_diff_fact_1

5.0

-100

100

TRUE

Heat Cntrl Setpt Offset: (F)

Heat Control Setpoint Offset

ht_cntrl_spt_offset_1

1.0

-250

250

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

FIXED OPEN MODULE MENU
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

FIX Mod Mot Vlv Open for Header Bypass
Open Ext Bypass if NO Comps ON?

Open Bypass Valves by NO
Comps ON

open_byp_vlv_on_no_cmps_1

Off

No, Yes

TRUE

Delay Before Closing Mot Valves:

Delay Before Closing Mot Vlv

close_vlv_delay_5

25.0

1

999

TRUE

Fix Module #1 as Open Module?:

Fix Mod1 as Open

fix_module1_open_1

Yes

No, Yes

TRUE

Never Close Module #1?:

Never Close Module #1

never_close_mod1_1

No

No, Yes

TRUE

Fix Module #2 as Open Module?:

Fix Mod2 as Open

fix_module2_open_1

No

No, Yes

TRUE

Never Close Module #2?:

Never Close Module #2

never_close_mod2_1

No

No, Yes

TRUE

Fix Module #3 as Open Module?:

Fix Mod3 as Open

fix_module3_open_1

No

No, Yes

TRUE

Never Close Module #3?:

Never Close Module #3

never_close_mod3_1

No

No, Yes

TRUE

Fix Module #4 as Open Module?:

Fix Mod4 as Open

fix_module4_open_1

No

No, Yes

TRUE

Never Close Module #4?:

Never Close Module #4

never_close_mod4_1

No

No, Yes

TRUE

Page 10 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

MASTER MICRO FACTORY
SETUP FN8

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Master Ctrlr Fact Setup FN8
FN5
LINK(S): MODULE SIZE SELECTOR,PID COOL STG1 SETUP,PID HEAT STG1 SETUP,FIXED OPEN MODULE MENU,MOTORIZED VALVE OPTION,MOT VLV SIGNAL TO CLOSE MENU,
MASTER INPUT CHNLS 6, &10 SETUP,MASTER INPUT CHNL 7 DEM LIMIT SETUP,MASTER INPUT 8 & 11 SETUP,WATER MAINS & AIR TEMP LIMITS,STARTUP & STAGE DELAYS,
ALL MODULE COMP UNLOAD STATUS,AUTO HEAT TRG RESET ON OAT,COMPR SEQUENCING METHOD,HEAT BIN LOAD CAP% STATUS,COOL BIN LOAD CAP% STATUS,
MAIN TXV PID SETTINGS,MAIN TXV PSI PID SETTINGS,M1 & M2 MAIN TXV SETTINGS,M3 & M4 MAIN TXV SETTINGS,MODULE ALARM CONDITION RETRIES,
MODULE NUMBER MENU,KEYPAD,PREV, SYSTEM SETUP, HOME, ALARM

MODULE SIZE SELECTOR
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Size Selector Screen Legend
Mod1 Size:
/ 1= Not Used/4=80Ton Mod

Module 1 Size

mod1_size_1

65 Ton

1

4

TRUE

Mod2 Size:
/NOTE:DO NOT SELECT 2 OR 3

Module 2 Size

mod2_size_1

65 Ton

1

4

TRUE

Mod3 Size:

Module 3 Size

mod3_size_1

65 Ton

1

4

TRUE

Mod4 Size:

Module 4 Size

mod4_size_1

65 Ton

1

4

TRUE

Mod5 Size:

Module 5 Size

mod5_size_1

Not Used

1

4

TRUE

Mod6 Size:

Module 6 Size

mod6_size_1

Not Used

1

4

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

PID COOL STG1 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Cool PID Stage #1 Setup
Stage One Cool PID Output : (%)

Stage 1 Cooling PID

stg1_clg_pid_1

106.719604

FALSE

Stage One Cool PID Interval:

Clg PID Interval

clg_interval_1

8.0 sec

1

100

TRUE

Stage One Cool PID P-Gain :

Clg PID P-gain

clg_p_gain_1

18.0

0

999

TRUE

Stage One Cool PID I-Gain#1:

Clg PID I-gain

clg_i_gain_1

0.35

0

99

TRUE

Max Cool Ramp Rate: - (F) (/min)

MAX COOL RAMP RATE

max_cool_ramp_rate_1

10.0 °F/min

1

20

TRUE

Clg PID Rise Fast: (%/min)

Clg PID Rise Fast

clg_rise_fast_1

12.0 sec

1

300

TRUE

Clg PID Rise Slow: (%/min)

Clg PID Rise Slow

clg_rise_slow_1

5.0 sec

1

300

TRUE

Clg PID Fall: (%/min)

Clg PID Fall

clg_fall_1

22.0

2

300

TRUE

Cool Deadbd1:

Clg PID DB1

clg_db1_1

0.3

0

99

TRUE

/CoolDeadbd2:

Clg PID DB2

clg_db2_1

0.0

0

99

TRUE

Stage One Cool PID I-Gain#2:

Clg PID IG2

clg_ig2_1

0.01

0

99

TRUE

PID Switching Differential: (%)

PID Differential Factor

pid_diff_fact_1

5.0

-100

100

TRUE

Cool Cntrl Setpt Offset: (F)

Cool Control Setpoint Offset

cl_cntrl_spt_offset_1

0.0

-250

250

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

PID HEAT STG1 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat PID Stage #1 Setup
Stage One Heat PID Output : (%)

Stage 1 Heating PID

stg1_htg_pid_1

0.0

FALSE

Stage One Heat PID Interval:

Htg PID Interval

htg_interval_1

2.0 sec

1

100

TRUE

Stage One Heat PID P-Gain :

Htg PID P-gain

htg_p_gain_1

20.0

0

999

TRUE

Stage One Heat PID I-Gain#1:

Htg PID I-gain

htg_i_gain_1

0.25

0

99

TRUE

Max Heat Ramp Rate: (F) (/min)

MAX HEAT RAMP RATE

max_heat_ramp_rate_1

10.0 °F/min

1

99

TRUE

Htg PID Rise Fast: (%/min)

Htg PID Rise Fast

htg_rise_fast_1

12.0 sec

1

300

TRUE

Htg PID Rise Slow: (%/min)

Htg PID Rise Slow

htg_rise_slow_1

4.0 sec

1

300

TRUE

Htg PID Fall: (%/min)

Htg PID Fall

htg_fall_1

25.0

2

300

TRUE

HeatDeadbd1:

Htg PID DB1

htg_db1_1

0.1

0

99

TRUE

/Heat Deadbd2:

Htg PID DB2

htg_db2_1

0.0

0

99

TRUE

Stage One Heat PID I-Gain#2:

Htg PID IG2

htg_ig2_1

0.0

0

99

TRUE

PID Switching Differential: (%)

PID Differential Factor

pid_diff_fact_1

5.0

-100

100

TRUE

Heat Cntrl Setpt Offset: (F)

Heat Control Setpoint Offset

ht_cntrl_spt_offset_1

1.0

-250

250

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

FIXED OPEN MODULE MENU
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

FIX Mod Mot Vlv Open for Header Bypass
Open Ext Bypass if NO Comps ON?

Open Bypass Valves by NO
Comps ON

open_byp_vlv_on_no_cmps_1

Off

No, Yes

TRUE

Delay Before Closing Mot Valves:

Delay Before Closing Mot Vlv

close_vlv_delay_5

25.0

1

999

TRUE

Fix Module #1 as Open Module?:

Fix Mod1 as Open

fix_module1_open_1

Yes

No, Yes

TRUE

Never Close Module #1?:

Never Close Module #1

never_close_mod1_1

No

No, Yes

TRUE

Fix Module #2 as Open Module?:

Fix Mod2 as Open

fix_module2_open_1

No

No, Yes

TRUE

Never Close Module #2?:

Never Close Module #2

never_close_mod2_1

No

No, Yes

TRUE

Fix Module #3 as Open Module?:

Fix Mod3 as Open

fix_module3_open_1

No

No, Yes

TRUE

Never Close Module #3?:

Never Close Module #3

never_close_mod3_1

No

No, Yes

TRUE

Fix Module #4 as Open Module?:

Fix Mod4 as Open

fix_module4_open_1

No

No, Yes

TRUE

Never Close Module #4?:

Never Close Module #4

never_close_mod4_1

No

No, Yes

TRUE

Page 11 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Fix Module #5 as Open Module?:

Fix Mod5 as Open

fix_module5_open_1

No

No, Yes

TRUE

Never Close Module #5?:

Never Close Module #5

never_close_mod5_1

No

No, Yes

TRUE

Fix Module #6 as Open Module?:

Fix Mod6 as Open

fix_module6_open_1

No

No, Yes

TRUE

Never Close Module #6?:

Never Close Module #6

never_close_mod6_1

No

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MOTORIZED VALVE OPTION
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Motorized Valve Option
Motorized Valves:

Motorized Valve Options

mot_vlv_opt_5

MVCONDEVA

P

No Mot Vlvs,

Evap Mot Vlvs

Only,

Cond&Evap

Mot Vlvs

TRUE

Cond Mot Vlv Delay Before Alarm:

Module COND VLV ALM DELAY mod_cond_vlv_alm_delay_5

600.0

1

999

TRUE

Evap Mot Vlv Delay Before Alarm:

Module EVAP VLV ALM DELAY

mod_evap_vlv_alm_delay_5

600.0

1

999

TRUE

Low Head Press Setpoint Status:

Module Lo Disch Press Setpt

mod_lo_disch_press_sp_5

100.0

1

585

FALSE

Low Head Press Setpoint R410A :

Low Head Press Sp 410a

mod_lo_disch_press_sp_410_5

220.0

1

650

TRUE

Low Head Press Setpoint R134a :

Low Head Press Sp 134a

mod_lo_disch_press_sp_134_5

100.0

1

450

TRUE

Low Head Press Setpoint R407C :

Low Head Press Sp 407

mod_lo_disch_press_sp_407_5

150.0

1

450

TRUE

Cond Mot Vlv PID Settings
Cond MV PID Interval:

CDMV PID Interval

cdmv_interval_5

2.0 sec

1

180

TRUE

Cond MV PID P-Gain :

CDMV PID P-gain

cdmv_p_gain_5

8.0

1

999

TRUE

Cond MV PID I-Gain :

CDMV PID I-gain

cdmv_i_gain_5

0.02

0

99

TRUE

Cond MV PID Deadband:

CDMV PID Deadband

cdmv_pid_db_5

0.0

0

99

TRUE

Cond MV PID Ramp sec:

CDMV PID RAMP

cdmv_pid_ramp_5

2.0

1

999

TRUE

Cond MV PID Min % :

CDMV PID Minimum Percent

cdmv_pid_mnpct_5

20.0

0

100

TRUE

Module Min CDMV ADJ :

Mod CDMV PID Minimum VDC

mod_min_cdmv_adj_5

3.4

0

100

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MOT VLV SIGNAL TO CLOSE MENU
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Mot Valve Signal to Close
Mod1 Mot Valve Signal to Close:

Module 1 Closed

m1_closed_5

Off

No, Yes

FALSE

Mod2 Mot Valve Signal to Close:

Module 2 Closed

m2_closed_5

Off

No, Yes

FALSE

Mod3 Mot Valve Signal to Close:

Module 3 Closed

m3_closed_5

On

No, Yes

FALSE

Mod4 Mot Valve Signal to Close:

Module 4 Closed

m4_closed_5

On

No, Yes

FALSE

Mod5 Mot Valve Signal to Close:

Module 5 Closed

m5_closed_5

Off

No, Yes

FALSE

Mod6 Mot Valve Signal to Close:

Module 6 Closed

m6_closed_5

Off

No, Yes

FALSE

Delay Before Closing Mot Valves:

Delay Before Closing Mot Vlv

close_vlv_delay_5

25.0

1

999

TRUE

Open Ext Bypass if NO Comps ON?

Open Bypass Valves by NO
Comps ON

open_byp_vlv_on_no_cmps_1

Off

No, Yes

TRUE

Cool Header Bypass Vlv Status:

Cool Header Ext Bypass Valve

cl_hdr_ext_byp_vlv_1

Off

Closed, Open

FALSE

Heat Header Bypass Vlv Status:

Heat Header Ext Bypass Valve

ht_hdr_ext_byp_vlv_1

Off

Closed, Open

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MASTER INPUT CHNLS 6, &10 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Master Controller Inputs 6 & 10 Setup
Input Chn#10Type:

Input Chnl 10 Type

inp_10_point_type_1

NONE

None, Remote

Heat Trg

TRUE

Min Cond Wat Out Setpt: (F)

MIN HEAT TRG LIM

min_cw_temp_stp_1

75.0 °F

60

165

TRUE

Max Cond Wat Out Setpt: (F)

MAX HEAT TRG LIM

max_cw_temp_stp_1

135.0 °F

60

165

TRUE

Input Chn#10Scaling:

AI10 Type Rem Ht Trg

an_inp10_typ_1

NONE

NONE, 4-20

ma, 2-10VDC

TRUE

Input Chn#6 Type:

Input Chnl 6 Type

inp_6_point_type_1

NONE

None, Remote

Cool Trg

TRUE

Min Evap Wat Out Setpt: (F)

MIN COOL TRG LIM

min_chw_temp_stp_1

40.0 °F

0

75

TRUE

Max Evap Wat Out Setpt: (F)

MAX COOL TRG LIM

max_chw_temp_stp_1

62.0 °F

0

75

TRUE

Input Chn#6 Scaling:

AI6 Type Off is 0-10

an_inp6_typ_1

NONE

NONE, 4-20

ma, 2-10VDC

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

MASTER INPUT CHNL 7 DEM LIMIT SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Master Control Demand Limiting Chnl#7
COOL & HEAT MODE DEMAND LIMITING
Input Chn#7 Type:

Input Chnl 7 Type

inp_7_point_type_1

None

None, Demand

Lim TrgRst,

Demand Lim

Max #Cmp

TRUE

Max Neg Cool Out Trg Reset: (F)

MAX NEG DEM LIM COOL RESET max_neg_chw_stp_reset_1

0.0 °F

0

100

TRUE

Max Pos Cool Out Trg Reset: (F)

MAX POS DEM LIM COOL RESET max_pos_chw_stp_reset_1

10.0 °F

0

100

TRUE

Max Neg Heat Out Trg Reset: (F)

MAX NEG DEM LIM HEAT RESET max_neg_cw_stp_reset_1

0.0 °F

0

100

TRUE

Max Pos Heat Out Trg Reset: (F)

MAX POS DEM LIM HEAT RESET max_pos_cw_stp_reset_1

10.0 °F

0

100

TRUE

Page 9 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

/C1SucPr: (ps)

Module 1 Comp 1 Suction
Pressure

m1_c1_suc_pres_stat_5

40.6

FALSE

C1DisTmpCal: (F)

M1C1 DIS Temp Calib. Point

m1c1_disch_temp_cp_5

0.0

-250

250

TRUE

/C1DisTp: (F)

Module 1 Comp 1 Disch Temp

m1_c1_disch_temp_stat_5

110.3

FALSE

C1SucTempCal: (F)

M1C1 SUC Temp Calib. Point

m1c1_suc_tmp_cp_5

0.0

-250

250

TRUE

/C1SucTp: (F)

Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5

53.6

FALSE

C1CompAmpCal:

M1C1 Amps Calib. Point

m1c1_amps_cp_5

3.0

-250

250

TRUE

/C1 Amps:

Module 1 Comp 1 Amps

m1c1_amps_stat_5

33.6

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

LOCK WATER TEMPS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Lock Main Header Water & Air Temps
Evap Wat In Lock :

Lock CHWR Temp

lock_chwr_1

No

Off, On

TRUE

Evap Wat In Lock Value : (F)

CHWR Lock Value

chwr_lock_val_1

54.0

0

165

TRUE

Evap Wat Out Lock:

Lock EVAP LVG TMP

lock_chws_1

No

Off, On

TRUE

Evap Wat Out Lock Value: (F)

EVAP LVG TMP Lock Value

chws_lock_val_1

43.0

0

165

TRUE

Cond Wat In Lock :

Lock CWS Temp

lock_cws_1

No

Off, On

TRUE

Cond Wat In Lock Value : (F)

CWS Lock Value

cws_lock_val_1

85.0

0

165

TRUE

Cond Wat Out Lock:

Lock CWR Temp

lock_cwr_1

No

Off, On

TRUE

Cond Wat Out Lock Value: (F)

CWR Lock Value

cwr_lock_val_1

58.0

0

165

TRUE

Outdoor Air Lock:

Lock CHWS Temp

lock_oat_1

Yes

Off, On

TRUE

Outdoor Air Lock Value: (F)

OAT Lock Value

oat_lock_val_1

61.0

-20

140

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

SCREW PID SEQUENCING DATA
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic PID Sequencing Data
VFD Minimum VDC Input: 4.3

VFD Minimum VDC Input

vfd_min_vdc_1

4.4

0

10

TRUE

VFD Minimum VDC In 3 Scr: 6.16

VFD Minimum for Three Screws vfd_min_vdc_three_scr_1

6.16

0

10

TRUE

VFD Minimum VDC In 4 Scr: 7.17

VFD Minimum for Four Screws

vfd_min_vdc_four_scr_1

7.17

0

10

TRUE

VFD Maximum VDC Input: 10.00

VFD Maximum VDC Input

vfd_max_vdc_1

10.0

0

10

TRUE

VFD Start PID for One Scr: 33

VFD Start PID for One Screw

vfd_start_pid_one_scr_1

33.0

0

500

TRUE

VFD Min PID for One Scr: 34

VFD Minimum PID for One
Screw

vfd_min_pid_one_scr_1

34.0

0

500

TRUE

VFD Max PID for One Scr: 75

VFD Maximum PID for One
Screw

vfd_max_pid_one_scr_1

75.0

0

500

TRUE

VFD Max One PID Min Two Scr: 85

VFD Max One PID Min Two
Screws

vfd_max_one_pid_min_two_scr_1

85.0

0

500

TRUE

VFD Min PID for Two Scr: 86

VFD Minimum PID for Two
Screws

vfd_min_pid_two_scr_1

86.0

0

500

TRUE

VFD Interim PID Two Scr: 123

VFDInterim PID for One Full One
Min Screws

vfd_interim_pid_two_scr_1

123.0

0

500

TRUE

VFD Max PID for Two Scr: 160

VFD Maximum PID for Two
Screws

vfd_max_pid_two_scr_1

160.0

0

500

TRUE

VFD Max Two PIDMinThree Scr:170

VFD Max Two PID Min Three
Screws

vfd_max_two_pid_min_three_scr_1

170.0

0

500

TRUE

VFD Min PID for Three Scr: 171

VFD Minimum PID for Three
Screws

vfd_min_pid_three_scr_1

171.0

0

500

TRUE

VFD IntPID One Full;Two Min:195

VFDInterim PID for One Full &
Two Min Screws

vfd_interim_pid_one_full_two_min_s
cr_1

195.0

0

500

TRUE

VFD IntPID Two Full;One Min:220

VFD Interim PID for Two Full &
One Min Screws

vfd_interim_pid_two_full_one_min_s
cr_1

220.0

0

500

TRUE

VFD Max PID for Three Scr: 245

VFD Maximum PID for Three
Screws

vfd_max_pid_three_scr_1

245.0

0

500

TRUE

VFD Max 3 PID Min Four Scr: 255

VFD Max Three PID Min Four
Screws

vfd_max_three_pid_min_four_scr_1

255.0

0

500

TRUE

VFD Min PID for Four Scr: 256

VFD Minimum PID for Four
Screws

vfd_min_pid_four_scr_1

256.0

0

500

TRUE

VFD IntPID One Full;3 Min: 274

VFDInterim PID for One Full &
Three Min Screws

vfd_interim_pid_one_full_three_min
_scr_1

274.0

0

500

TRUE

VFD IntPID Two Full;Two Min:292

VFD Interim PID for Two Half &
One Min Screws

vfd_interim_pid_two_full_two_min_s
cr_1

292.0

0

500

TRUE

VFD IntPID 3 Full; One Min: 311

VFD Interim PID for Three Full
One Min Screws

vfd_interim_pid_three_full_one_min
_scr_1

311.0

0

500

TRUE

VFD Max PID for Four Scr: 330

VFD Maximum PID for Four
Screws

vfd_max_pid_four_scr_1

330.0

0

500

TRUE

VFD Last PID: 340

VFD Last PID

vfd_last_pid_1

340.0

0

500

TRUE

Screw Runtime Before Flush 8.0h

Screw Runtime in Minutes

scr_runtime_before_flush_1

4.0

0

999

TRUE

Use Screw Flush Cycle

Use Screw Flush Cycle

use_scr_flush_1

Yes

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME