Control access display table, Multiple accesses to menu tables, Use of this table during startup – ClimaCool UGW Manual User Manual

Page 29: Local access display table

Advertising
background image

27

www.climacoolcorp.com

Control Access Display Table

Editable- True = Value is adjustable . False = Value is

‘read only’ .
Many of the Menus in the Control Access Display Table are

typical of each module, Menus for subsequent modules

are not listed . To preserve space in this document, these

single Menus are represented with a title of MOD X, and can

be viewed, Module by Module, in the BACview Interface

Device .

Multiple Accesses to Menu Tables

While navigating the BACview Interface Device, there are

multiple ways to access many Menus . The intent of the

Control Access Display Table is to provide concise direction

to access each Menu and Object in the BACview Interface

Device using a single method for each . While Menus are

included in multiple locations in the BACview Interface

Device, they will not be included in all the Menus herein .

However, every Menu is accessible using the Control Access

Display Table as a reference . This document locates these

Menus in an appropriate location based on the nature of

the object .

Use of this Table during Startup

It is of the utmost importance to review all the settings

in the FN2, FN6, FN7 and FN8 Menus while performing

start up to confirm proper configuration for the intended

application. This review must also confirm that all alarm

set points meet the required values for the system . Please

consider the type of equipment installed, heat transfer

medium used for each individual fluid loop, and safe

minimum flow rates for each fluid loop in the chiller system.
Please contact ClimaCool Corp Technical Service for any

questions related to the Control Access Display Table and

any content contained within .

Page 1 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

STANDBY
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

ClimaCool Corp. CoolLogic
Date:
Time:
CHWS Temp:

EVAP OUT TMP

chws_temp_1

50.1 °F

FALSE

F CWR Temp: (F)

COND OUT TMP

cwr_temp_1

83.3 °F

FALSE

press any key to continue

HOME
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Chill Water In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

/Cool Spt: (F)

Active CHW Setpoint

chw_stp_stat_1

45.0 °F

FALSE

Chill WaterOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

/ Tot Stg Want:

Num of Comp Requested

comp_req_1

2.0

FALSE

Cond Water In : (F)

CWS In Temp Status

cws_stat_1

67.3 °F

FALSE

/ Tot Stg On:

Num of Comp ON

comp_on_1

2.0

FALSE

Cond Water Out: (F)
/ Mode :

Mode

mode_1

CLG

Cooling,

Heating

FALSE

Chil Water Flow :
/Heat Spt: (F)

Evap Flow SW

evap_flow_1

On

No, Yes

FALSE

Cond Water Flo:

Cond Flow SW

cond_flow_1

On

No, Yes

FALSE

/UnitMode:

Unit Mode

unit_mode_1

Normal Run

Schedule, No

Flo/Phas,

CHWR High,

CWS Low, Sens

Error, No

ModAvail,

Module Down,

Compr Down,

NonCrit Alm,

Normal Run

FALSE

LINK(S): STATUS, SYSTEM SETUP, SERVICE MENU SETUP, ALARM

STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Chiller Status Menu
LINK(S): ALL MODULE COMP UNLOAD STATUS,MODULE SIZE STATUS, CHILLER OPER STATUS,EVAP STATUS, COND STATUS,MOT VLV OPEN/CLOSE STATUS MENU,
MOD1 COMP1 DATA,MOD2 COMP1 DATA,MOD3 COMP1 DATA,MOD4 COMP1 DATA,MOD5 COMP1 DATA,MOD6 COMP1 DATA,ALL COMPR RUNTIME STATUS,
ALL COMPR CYCLES STATUS,ALL COMPR SS STATUS, ALL COMPR AMPERAGE STATUS,PREV, CLOCKSET, HOME, ALARM

MODULE SIZE STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Module Size Status Only Legend
Mod1 Size:[
]/ 1= Not Used /4=80Ton Mod

Mod 1 Size

m1_size_st_1

4.0

1

4

FALSE

Mod2 Size:[
]/NOTE:DO NOT SELECT 2 OR 3

Mod 2 Size

m2_size_st_1

4.0

1

4

FALSE

Mod3 Size:[
]

Mod 3 Size

m3_size_st_1

4.0

1

4

FALSE

Mod4 Size:[
]

Mod 4 Size

m4_size_st_1

4.0

1

4

FALSE

Mod5 Size:[
]

Mod 5 Size

m5_size_st_1

1.0

1

4

FALSE

Mod6 Size:[
]

Mod 6 Size

m6_size_st_1

1.0

1

4

FALSE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

CHILLER OPER STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Operating & Loading Status
PID1 Count:

Stage 1 Cooling PID

stg1_clg_pid_1

106.719604

FALSE

/Chil WaterOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

Mod1 VFD Volt:

M1 VFD Screw Input

m1vfd_screw_input_1

7.53594 V

0

999

FALSE

/Mod2 VFD Volt:

M2 VFD Screw Input

m2vfd_screw_input_1

4.4 V

0

999

FALSE

Mod3 VFD Volt:

M3 VFD Screw Input

m3vfd_screw_input_1

0.0 °F

0

999

FALSE

/Mod4 VFD Volt:

M4 VFD Screw Input

m4vfd_screw_input_1

0.0 °F

0

999

FALSE

HPID1 Count:

Stage 1 Heating PID

stg1_htg_pid_1

0.0

FALSE

/Cond WaterOut: (F)

CWR Out Status

cwr_stat_1

83.3

FALSE

Cool Spt:

Active CHW Setpoint

chw_stp_stat_1

45.0 °F

FALSE

F / Heat Spt: (F)

Active Htg Setpoint

cw_stp_stat_1

125.0 °F

FALSE

Unit Stat:

Unit Status

unit_status_1

On

Unit OFF, Unit

ON

FALSE

LOCAL ACCESS DISPLAY TABLE