Startup – ClimaCool UGW Manual User Manual

Page 26

Advertising
background image

www.climacoolcorp.com

24

Startup

18 . Verify proper communications from each module back

to the master controller using the “STATUSmenu, then

indexing down to the desired compressor data screen .

• If the compressor data parameters all read “0,”

then communications are not yet established, and

communications cable troubleshooting is required .

• When all compressor data parameters read actual

values which agree with the refrigerant gauge set and

refrigerant line temperatures, then it is safe to assume

that communications are established .

19 . Set up the master controller parameters according to

the specific job submittal sheets.

• All parameters can be found in the FN 2 menu (setup),

FN 6 menu (module factory settings), FN 7 menu

(service), FN 8 menu (master factory settings).

•It is imperative to access EVERY MENU and EVERY

PARAMETER to ensure all settings are appropriate .

20 . Set up the Building Automation System (BAS) interface

parameters (as required) using the FN 0 menu (network

number selection, IP addressing), FN 4 menu (device

instances) .

Adjusting Unit Charge and Expansion Valves

Using Superheat and Subcooling Method

Due to varying installation conditions/applications and

to optimize performance, proper refrigerant charge and

expansion valve (TXV) adjustment must be confirmed.
After checking compressor rotation, choose a circuit to be

tested first. Connect test equipment to monitor the suction

line and liquid line temperatures simultaneously . Place a

manifold gauge set on the suction line and liquid line then

start the compressor . As long as the suction pressure is high

enough to prevent the low pressure switch from tripping,

run the compressor for five minutes.
Verify proper subcooling . This is accomplished by

subtracting the liquid line temperature from the saturated

condensing temperature . The saturated condensing

temperature is found by converting the liquid line pressure

reading on the manifold gauge to the related temperature .

The normal subcooling temperature range at the condenser

is 5-15°F BUT for total accuracy, please follow the charge

recommendations found in the selection program . If

subcooling is too low, then refrigerant must be added to the

system. Add charge and wait five minutes before checking

results . If subcooling is too high, then refrigerant must be

removed from the system .
Verify proper superheat by subtracting the saturated

evaporative temperature from the suction line temperature .

The saturated evaporative temperature is found by

converting the suction pressure reading on the manifold

gauge to the related temperature . The proper superheat

temperature range is 4-15°F at normal operating conditions

(typically 44

o

F leaving chilled water temperature) . If

superheat is low, this may indicate that the expansion valve is

overfeeding . To adjust the expansion valves, turn the adjustment

stem clockwise. This will cause the superheat to rise. Wait five

minutes before checking the results of this adjustment . Repeat

until the desired superheat is achieved .