Control Access Display Table

Page 11 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Fix Module #5 as Open Module?:

Fix Mod5 as Open

fix_module5_open_1

No

No, Yes

TRUE

Never Close Module #5?:

Never Close Module #5

never_close_mod5_1

No

No, Yes

TRUE

Fix Module #6 as Open Module?:

Fix Mod6 as Open

fix_module6_open_1

No

No, Yes

TRUE

Never Close Module #6?:

Never Close Module #6

never_close_mod6_1

No

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MOTORIZED VALVE OPTION
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Motorized Valve Option
Motorized Valves:

Motorized Valve Options

mot_vlv_opt_5

MVCONDEVA

P

No Mot Vlvs,

Evap Mot Vlvs

Only,

Cond&Evap

Mot Vlvs

TRUE

Cond Mot Vlv Delay Before Alarm:

Module COND VLV ALM DELAY mod_cond_vlv_alm_delay_5

600.0

1

999

TRUE

Evap Mot Vlv Delay Before Alarm:

Module EVAP VLV ALM DELAY

mod_evap_vlv_alm_delay_5

600.0

1

999

TRUE

Low Head Press Setpoint Status:

Module Lo Disch Press Setpt

mod_lo_disch_press_sp_5

100.0

1

585

FALSE

Low Head Press Setpoint R410A :

Low Head Press Sp 410a

mod_lo_disch_press_sp_410_5

220.0

1

650

TRUE

Low Head Press Setpoint R134a :

Low Head Press Sp 134a

mod_lo_disch_press_sp_134_5

100.0

1

450

TRUE

Low Head Press Setpoint R407C :

Low Head Press Sp 407

mod_lo_disch_press_sp_407_5

150.0

1

450

TRUE

Cond Mot Vlv PID Settings
Cond MV PID Interval:

CDMV PID Interval

cdmv_interval_5

2.0 sec

1

180

TRUE

Cond MV PID P-Gain :

CDMV PID P-gain

cdmv_p_gain_5

8.0

1

999

TRUE

Cond MV PID I-Gain :

CDMV PID I-gain

cdmv_i_gain_5

0.02

0

99

TRUE

Cond MV PID Deadband:

CDMV PID Deadband

cdmv_pid_db_5

0.0

0

99

TRUE

Cond MV PID Ramp sec:

CDMV PID RAMP

cdmv_pid_ramp_5

2.0

1

999

TRUE

Cond MV PID Min % :

CDMV PID Minimum Percent

cdmv_pid_mnpct_5

20.0

0

100

TRUE

Module Min CDMV ADJ :

Mod CDMV PID Minimum VDC

mod_min_cdmv_adj_5

3.4

0

100

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MOT VLV SIGNAL TO CLOSE MENU
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Mot Valve Signal to Close
Mod1 Mot Valve Signal to Close:

Module 1 Closed

m1_closed_5

Off

No, Yes

FALSE

Mod2 Mot Valve Signal to Close:

Module 2 Closed

m2_closed_5

Off

No, Yes

FALSE

Mod3 Mot Valve Signal to Close:

Module 3 Closed

m3_closed_5

On

No, Yes

FALSE

Mod4 Mot Valve Signal to Close:

Module 4 Closed

m4_closed_5

On

No, Yes

FALSE

Mod5 Mot Valve Signal to Close:

Module 5 Closed

m5_closed_5

Off

No, Yes

FALSE

Mod6 Mot Valve Signal to Close:

Module 6 Closed

m6_closed_5

Off

No, Yes

FALSE

Delay Before Closing Mot Valves:

Delay Before Closing Mot Vlv

close_vlv_delay_5

25.0

1

999

TRUE

Open Ext Bypass if NO Comps ON?

Open Bypass Valves by NO
Comps ON

open_byp_vlv_on_no_cmps_1

Off

No, Yes

TRUE

Cool Header Bypass Vlv Status:

Cool Header Ext Bypass Valve

cl_hdr_ext_byp_vlv_1

Off

Closed, Open

FALSE

Heat Header Bypass Vlv Status:

Heat Header Ext Bypass Valve

ht_hdr_ext_byp_vlv_1

Off

Closed, Open

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MASTER INPUT CHNLS 6, &10 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Master Controller Inputs 6 & 10 Setup
Input Chn#10Type:

Input Chnl 10 Type

inp_10_point_type_1

NONE

None, Remote

Heat Trg

TRUE

Min Cond Wat Out Setpt: (F)

MIN HEAT TRG LIM

min_cw_temp_stp_1

75.0 °F

60

165

TRUE

Max Cond Wat Out Setpt: (F)

MAX HEAT TRG LIM

max_cw_temp_stp_1

135.0 °F

60

165

TRUE

Input Chn#10Scaling:

AI10 Type Rem Ht Trg

an_inp10_typ_1

NONE

NONE, 4-20

ma, 2-10VDC

TRUE

Input Chn#6 Type:

Input Chnl 6 Type

inp_6_point_type_1

NONE

None, Remote

Cool Trg

TRUE

Min Evap Wat Out Setpt: (F)

MIN COOL TRG LIM

min_chw_temp_stp_1

40.0 °F

0

75

TRUE

Max Evap Wat Out Setpt: (F)

MAX COOL TRG LIM

max_chw_temp_stp_1

62.0 °F

0

75

TRUE

Input Chn#6 Scaling:

AI6 Type Off is 0-10

an_inp6_typ_1

NONE

NONE, 4-20

ma, 2-10VDC

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

MASTER INPUT CHNL 7 DEM LIMIT SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Master Control Demand Limiting Chnl#7
COOL & HEAT MODE DEMAND LIMITING
Input Chn#7 Type:

Input Chnl 7 Type

inp_7_point_type_1

None

None, Demand

Lim TrgRst,

Demand Lim

Max #Cmp

TRUE

Max Neg Cool Out Trg Reset: (F)

MAX NEG DEM LIM COOL RESET max_neg_chw_stp_reset_1

0.0 °F

0

100

TRUE

Max Pos Cool Out Trg Reset: (F)

MAX POS DEM LIM COOL RESET max_pos_chw_stp_reset_1

10.0 °F

0

100

TRUE

Max Neg Heat Out Trg Reset: (F)

MAX NEG DEM LIM HEAT RESET max_neg_cw_stp_reset_1

0.0 °F

0

100

TRUE

Max Pos Heat Out Trg Reset: (F)

MAX POS DEM LIM HEAT RESET max_pos_cw_stp_reset_1

10.0 °F

0

100

TRUE

Page 12 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Input Chn#7 Scaling:

AI7 Type Rem Cl Trg or Dem Lim an_inp7_typ_1

NONE

NONE, 4-20

ma, 2-10VDC

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

MASTER INPUT 8 & 11 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Channels 8,11&1-13 Setup(Wtr Diff Pres)
Use Dif Pr. Sens for Chn8,11&1-13?

Use Diff Press Flow Sensors

use_diff_pr_flow_sens_1

Yes

No, Yes

TRUE

*Std CC Dif Pres Sensor Range=0-43 psid
Min&Max Scale Range-Cold Wtr Dif Pr.:
Cold Wtr Chn#08 Scaling Type:

AI8 Type

an_inp8_typ_1

0-5VDC

4-20 ma, 0-
10VDC, 0-5

VDC

TRUE

Cold Wtr Min Scale @ 0V or 0mA :

Min Cool Diff Press Scale @ 0

min_scale_cool_diff_pr_1

-5.43

-99.9

999.9

TRUE

Cold Wtr Max Scale@5V,10Vor20mA:

Max Cool Diff Press Scale

max_scale_cool_diff_pr_1

48.94

-99.9

999.9

TRUE

Min&Max Scale Range-Hot Wtr Dif Pr.:
Hot Wtr Chn #11 Scaling Type:

AI11 Type

an_inp11_typ_1

0-5VDC

4-20 ma, 0-
10VDC, 0-5

VDC

TRUE

Hot Wtr Min Scale @ 0V or 0mA :

Min Source Diff Press Scale @ 0 min_scale_heat_diff_pr_1

-5.43

-99.9

999.9

TRUE

Hot Wtr Max Scale@5V,10Vor20mA:

Max Source Diff Press Scale

max_scale_heat_diff_pr_1

48.94

-99.9

999.9

TRUE

Cond Wat Min Dif Pr Flo Setpt: (PSI)

LO CW Diff Press

lo_cw_diff_pr_1

2.0

0

46

TRUE

Chil Wat Min Dif Pr Flo Setpt: (PSI)

Lo CHW Diff Pressure

lo_chw_diff_pr_1

2.0

0

46

TRUE

Differential Pressure Sensure Readings:
Cond Water Diff Press Sensor: (PSID)

Diff Press Heat Load

diff_press_heat_load_1

8.053761 °F

FALSE

Chil Water Diff Press Sensor: (PSID)

Diff Press Cool Load

diff_press_cool_load_1

8.48872 °F

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

WATER MAINS & AIR TEMP LIMITS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Main Hdr Water & Air Temp Alarm Limits
Evap Wat In Lo Limit: (F)

CHWR Enable Lo Limit

chwr_lo_lim_1

38.0

0

165 TRUE

Evap Wat In Hi Limit: (F)

CHWR Enable Hi Limit

chwr_hi_lim_1

90.0

0

165 TRUE

Evap Wat Out Lo Limit: (F)

LO EVAP LVG TMP

chws_low_lim_1

38.0

0

165 TRUE

Evap Wat Out Hi Limit: (F)

HI EVAP LVG TMP

chws_hi_lim_1

90.0

0

165 TRUE

Cond Wat In Lo Limit: (F)

LO CND LVG TMP

cws_low_lim_1

55.0

10

165 TRUE

Cond Wat Out Lo Limit: (F)

CWR Enable Lo Limit

cwr_lo_lim_1

55.0

10

165 TRUE

Main Header Cond Water Hi Limit:
CWR Cond Wtr Out UGW Hi Limit: (F)

HI COND LVG TMP UCW

ucw_cwr_hi_lim_1

118.0

10

165

TRUE

CWS Cond Wtr In UGW Hi Limit: (F)

HI COND ENT TMP UCW

ucw_cws_hi_lim_1

114.0

10

165

TRUE

CWR Cond Wtr Out UGH Hi Limit: (F)

HI COND LVG TMP UCH

uch_cwr_hi_lim_1

135.0

10

165

TRUE

CWS Cond Wtr In UGH Hi Limit: (F)

HI COND ENT TMP UCH

uch_cws_hi_lim_1

135.0

10

165

TRUE

Cond Wat In Hi Limit: (F)

Module Entering Cond Water
Temp Setpoint

cws_hi_lim_1

114.0

10

165

FALSE

Cond Wat Out Hi Limit: (F)

Module Leaving Cond Water
Temp Setpoint

cwr_hi_lim_1

118.0

10

165

FALSE

Use Hi Amb Temp Limit?

HI AMBIENT TMP LIM

hi_amb_tmp_lim_1

No

No, Yes

TRUE

Outdoor Air Lo Limit: (F)

LO AMBIENT TMP

lo_ambient_tmp_1

45.0 °F

-20

140

TRUE

Outdoor Air Hi Limit: (F)

HI AMBIENT TMP

hi_ambient_tmp_1

110.0 °F

-20

140

TRUE

Allow Evap Wtr Pump Menu Access?:

Use CHW Pump Menu

use_chw_pump_menu_1

No

No, Yes

TRUE

Allow Cond Wtr Pump Menu Access?:

Use CW Pump Menu

use_cw_pump_menu_1

No

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

STARTUP & STAGE DELAYS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Start-Up,Stage-Up & Stage-Dn Delays
Start-Up Time Delay (sec)

Start-Up Delay

o562_1

45.0 sec

1

999

TRUE

Stage-Up Delay (sec)

Stage Up Delay

n003_1

45.0 sec

1

999

TRUE

Stage-Down Delay (sec)

Stage Down Delay

n006_1

45.0 sec

1

999

TRUE

Mode Change Delay (sec)

Mode Change Delay

mode_change_delay_1

30.0 sec

1

3000

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

AUTO HEAT TRG RESET ON OAT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat Tgr Reset on OAT
Auto Heat Trg Reset :

OA AUTO HT TRG ON/OFF

auto_ht_trg_onof_1

0.0

Off, On

TRUE

Max OAT for Scaling Cond Trg: (F)

MAX OAT FOR HTG TRG RES

max_oat_htg_trg_reset_1

60.0 °F

0

140

TRUE

Min OAT for Scaling Cond Trg: (F)

MIN OAT FOR HTG TRG RESET

min_oat_htg_trg_reset_1

0.0 °F

-20

140

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

COMPR SEQUENCING METHOD
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compr Sequencing Method
Compr Equal Runtime:

Equal Runtime

equal_rtim_1

On

Off, On

TRUE

Page 12 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Input Chn#7 Scaling:

AI7 Type Rem Cl Trg or Dem Lim an_inp7_typ_1

NONE

NONE, 4-20

ma, 2-10VDC

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

MASTER INPUT 8 & 11 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Channels 8,11&1-13 Setup(Wtr Diff Pres)
Use Dif Pr. Sens for Chn8,11&1-13?

Use Diff Press Flow Sensors

use_diff_pr_flow_sens_1

Yes

No, Yes

TRUE

*Std CC Dif Pres Sensor Range=0-43 psid
Min&Max Scale Range-Cold Wtr Dif Pr.:
Cold Wtr Chn#08 Scaling Type:

AI8 Type

an_inp8_typ_1

0-5VDC

4-20 ma, 0-
10VDC, 0-5

VDC

TRUE

Cold Wtr Min Scale @ 0V or 0mA :

Min Cool Diff Press Scale @ 0

min_scale_cool_diff_pr_1

-5.43

-99.9

999.9

TRUE

Cold Wtr Max Scale@5V,10Vor20mA:

Max Cool Diff Press Scale

max_scale_cool_diff_pr_1

48.94

-99.9

999.9

TRUE

Min&Max Scale Range-Hot Wtr Dif Pr.:
Hot Wtr Chn #11 Scaling Type:

AI11 Type

an_inp11_typ_1

0-5VDC

4-20 ma, 0-
10VDC, 0-5

VDC

TRUE

Hot Wtr Min Scale @ 0V or 0mA :

Min Source Diff Press Scale @ 0 min_scale_heat_diff_pr_1

-5.43

-99.9

999.9

TRUE

Hot Wtr Max Scale@5V,10Vor20mA:

Max Source Diff Press Scale

max_scale_heat_diff_pr_1

48.94

-99.9

999.9

TRUE

Cond Wat Min Dif Pr Flo Setpt: (PSI)

LO CW Diff Press

lo_cw_diff_pr_1

2.0

0

46

TRUE

Chil Wat Min Dif Pr Flo Setpt: (PSI)

Lo CHW Diff Pressure

lo_chw_diff_pr_1

2.0

0

46

TRUE

Differential Pressure Sensure Readings:
Cond Water Diff Press Sensor: (PSID)

Diff Press Heat Load

diff_press_heat_load_1

8.053761 °F

FALSE

Chil Water Diff Press Sensor: (PSID)

Diff Press Cool Load

diff_press_cool_load_1

8.48872 °F

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

WATER MAINS & AIR TEMP LIMITS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Main Hdr Water & Air Temp Alarm Limits
Evap Wat In Lo Limit: (F)

CHWR Enable Lo Limit

chwr_lo_lim_1

38.0

0

165 TRUE

Evap Wat In Hi Limit: (F)

CHWR Enable Hi Limit

chwr_hi_lim_1

90.0

0

165 TRUE

Evap Wat Out Lo Limit: (F)

LO EVAP LVG TMP

chws_low_lim_1

38.0

0

165 TRUE

Evap Wat Out Hi Limit: (F)

HI EVAP LVG TMP

chws_hi_lim_1

90.0

0

165 TRUE

Cond Wat In Lo Limit: (F)

LO CND LVG TMP

cws_low_lim_1

55.0

10

165 TRUE

Cond Wat Out Lo Limit: (F)

CWR Enable Lo Limit

cwr_lo_lim_1

55.0

10

165 TRUE

Main Header Cond Water Hi Limit:
CWR Cond Wtr Out UGW Hi Limit: (F)

HI COND LVG TMP UCW

ucw_cwr_hi_lim_1

118.0

10

165

TRUE

CWS Cond Wtr In UGW Hi Limit: (F)

HI COND ENT TMP UCW

ucw_cws_hi_lim_1

114.0

10

165

TRUE

CWR Cond Wtr Out UGH Hi Limit: (F)

HI COND LVG TMP UCH

uch_cwr_hi_lim_1

135.0

10

165

TRUE

CWS Cond Wtr In UGH Hi Limit: (F)

HI COND ENT TMP UCH

uch_cws_hi_lim_1

135.0

10

165

TRUE

Cond Wat In Hi Limit: (F)

Module Entering Cond Water
Temp Setpoint

cws_hi_lim_1

114.0

10

165

FALSE

Cond Wat Out Hi Limit: (F)

Module Leaving Cond Water
Temp Setpoint

cwr_hi_lim_1

118.0

10

165

FALSE

Use Hi Amb Temp Limit?

HI AMBIENT TMP LIM

hi_amb_tmp_lim_1

No

No, Yes

TRUE

Outdoor Air Lo Limit: (F)

LO AMBIENT TMP

lo_ambient_tmp_1

45.0 °F

-20

140

TRUE

Outdoor Air Hi Limit: (F)

HI AMBIENT TMP

hi_ambient_tmp_1

110.0 °F

-20

140

TRUE

Allow Evap Wtr Pump Menu Access?:

Use CHW Pump Menu

use_chw_pump_menu_1

No

No, Yes

TRUE

Allow Cond Wtr Pump Menu Access?:

Use CW Pump Menu

use_cw_pump_menu_1

No

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

STARTUP & STAGE DELAYS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Start-Up,Stage-Up & Stage-Dn Delays
Start-Up Time Delay (sec)

Start-Up Delay

o562_1

45.0 sec

1

999

TRUE

Stage-Up Delay (sec)

Stage Up Delay

n003_1

45.0 sec

1

999

TRUE

Stage-Down Delay (sec)

Stage Down Delay

n006_1

45.0 sec

1

999

TRUE

Mode Change Delay (sec)

Mode Change Delay

mode_change_delay_1

30.0 sec

1

3000

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

AUTO HEAT TRG RESET ON OAT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat Tgr Reset on OAT
Auto Heat Trg Reset :

OA AUTO HT TRG ON/OFF

auto_ht_trg_onof_1

0.0

Off, On

TRUE

Max OAT for Scaling Cond Trg: (F)

MAX OAT FOR HTG TRG RES

max_oat_htg_trg_reset_1

60.0 °F

0

140

TRUE

Min OAT for Scaling Cond Trg: (F)

MIN OAT FOR HTG TRG RESET

min_oat_htg_trg_reset_1

0.0 °F

-20

140

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

COMPR SEQUENCING METHOD
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compr Sequencing Method
Compr Equal Runtime:

Equal Runtime

equal_rtim_1

On

Off, On

TRUE

Page 12 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Input Chn#7 Scaling:

AI7 Type Rem Cl Trg or Dem Lim an_inp7_typ_1

NONE

NONE, 4-20

ma, 2-10VDC

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

MASTER INPUT 8 & 11 SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Channels 8,11&1-13 Setup(Wtr Diff Pres)
Use Dif Pr. Sens for Chn8,11&1-13?

Use Diff Press Flow Sensors

use_diff_pr_flow_sens_1

Yes

No, Yes

TRUE

*Std CC Dif Pres Sensor Range=0-43 psid
Min&Max Scale Range-Cold Wtr Dif Pr.:
Cold Wtr Chn#08 Scaling Type:

AI8 Type

an_inp8_typ_1

0-5VDC

4-20 ma, 0-
10VDC, 0-5

VDC

TRUE

Cold Wtr Min Scale @ 0V or 0mA :

Min Cool Diff Press Scale @ 0

min_scale_cool_diff_pr_1

-5.43

-99.9

999.9

TRUE

Cold Wtr Max Scale@5V,10Vor20mA:

Max Cool Diff Press Scale

max_scale_cool_diff_pr_1

48.94

-99.9

999.9

TRUE

Min&Max Scale Range-Hot Wtr Dif Pr.:
Hot Wtr Chn #11 Scaling Type:

AI11 Type

an_inp11_typ_1

0-5VDC

4-20 ma, 0-
10VDC, 0-5

VDC

TRUE

Hot Wtr Min Scale @ 0V or 0mA :

Min Source Diff Press Scale @ 0 min_scale_heat_diff_pr_1

-5.43

-99.9

999.9

TRUE

Hot Wtr Max Scale@5V,10Vor20mA:

Max Source Diff Press Scale

max_scale_heat_diff_pr_1

48.94

-99.9

999.9

TRUE

Cond Wat Min Dif Pr Flo Setpt: (PSI)

LO CW Diff Press

lo_cw_diff_pr_1

2.0

0

46

TRUE

Chil Wat Min Dif Pr Flo Setpt: (PSI)

Lo CHW Diff Pressure

lo_chw_diff_pr_1

2.0

0

46

TRUE

Differential Pressure Sensure Readings:
Cond Water Diff Press Sensor: (PSID)

Diff Press Heat Load

diff_press_heat_load_1

8.053761 °F

FALSE

Chil Water Diff Press Sensor: (PSID)

Diff Press Cool Load

diff_press_cool_load_1

8.48872 °F

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

WATER MAINS & AIR TEMP LIMITS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Main Hdr Water & Air Temp Alarm Limits
Evap Wat In Lo Limit: (F)

CHWR Enable Lo Limit

chwr_lo_lim_1

38.0

0

165 TRUE

Evap Wat In Hi Limit: (F)

CHWR Enable Hi Limit

chwr_hi_lim_1

90.0

0

165 TRUE

Evap Wat Out Lo Limit: (F)

LO EVAP LVG TMP

chws_low_lim_1

38.0

0

165 TRUE

Evap Wat Out Hi Limit: (F)

HI EVAP LVG TMP

chws_hi_lim_1

90.0

0

165 TRUE

Cond Wat In Lo Limit: (F)

LO CND LVG TMP

cws_low_lim_1

55.0

10

165 TRUE

Cond Wat Out Lo Limit: (F)

CWR Enable Lo Limit

cwr_lo_lim_1

55.0

10

165 TRUE

Main Header Cond Water Hi Limit:
CWR Cond Wtr Out UGW Hi Limit: (F)

HI COND LVG TMP UCW

ucw_cwr_hi_lim_1

118.0

10

165

TRUE

CWS Cond Wtr In UGW Hi Limit: (F)

HI COND ENT TMP UCW

ucw_cws_hi_lim_1

114.0

10

165

TRUE

CWR Cond Wtr Out UGH Hi Limit: (F)

HI COND LVG TMP UCH

uch_cwr_hi_lim_1

135.0

10

165

TRUE

CWS Cond Wtr In UGH Hi Limit: (F)

HI COND ENT TMP UCH

uch_cws_hi_lim_1

135.0

10

165

TRUE

Cond Wat In Hi Limit: (F)

Module Entering Cond Water
Temp Setpoint

cws_hi_lim_1

114.0

10

165

FALSE

Cond Wat Out Hi Limit: (F)

Module Leaving Cond Water
Temp Setpoint

cwr_hi_lim_1

118.0

10

165

FALSE

Use Hi Amb Temp Limit?

HI AMBIENT TMP LIM

hi_amb_tmp_lim_1

No

No, Yes

TRUE

Outdoor Air Lo Limit: (F)

LO AMBIENT TMP

lo_ambient_tmp_1

45.0 °F

-20

140

TRUE

Outdoor Air Hi Limit: (F)

HI AMBIENT TMP

hi_ambient_tmp_1

110.0 °F

-20

140

TRUE

Allow Evap Wtr Pump Menu Access?:

Use CHW Pump Menu

use_chw_pump_menu_1

No

No, Yes

TRUE

Allow Cond Wtr Pump Menu Access?:

Use CW Pump Menu

use_cw_pump_menu_1

No

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

STARTUP & STAGE DELAYS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Start-Up,Stage-Up & Stage-Dn Delays
Start-Up Time Delay (sec)

Start-Up Delay

o562_1

45.0 sec

1

999

TRUE

Stage-Up Delay (sec)

Stage Up Delay

n003_1

45.0 sec

1

999

TRUE

Stage-Down Delay (sec)

Stage Down Delay

n006_1

45.0 sec

1

999

TRUE

Mode Change Delay (sec)

Mode Change Delay

mode_change_delay_1

30.0 sec

1

3000

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

AUTO HEAT TRG RESET ON OAT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat Tgr Reset on OAT
Auto Heat Trg Reset :

OA AUTO HT TRG ON/OFF

auto_ht_trg_onof_1

0.0

Off, On

TRUE

Max OAT for Scaling Cond Trg: (F)

MAX OAT FOR HTG TRG RES

max_oat_htg_trg_reset_1

60.0 °F

0

140

TRUE

Min OAT for Scaling Cond Trg: (F)

MIN OAT FOR HTG TRG RESET

min_oat_htg_trg_reset_1

0.0 °F

-20

140

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

COMPR SEQUENCING METHOD
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compr Sequencing Method
Compr Equal Runtime:

Equal Runtime

equal_rtim_1

On

Off, On

TRUE

Page 13 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

SWAP COMP LEAD :

Manually Refresh Lead Module man_refr_modlead_1

Do Not

Refresh Lead

Do Not Refresh

Lead, Refresh

Lead

TRUE

LINK(S): LEAD COMPR ROTATION SETUP,PREV, SYSTEM SETUP, HOME, ALARM

HEAT BIN LOAD CAP% STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat BinLoad Cap% Status
HeatBin 10% (h)

HEAT BIN 0-10 % HRS

heat_bin_0010_1

0.0

FALSE

/ HeatBin 60% (h)

HEAT BIN 50-60 % HRS

heat_bin_5060_1

0.0

FALSE

HeatBin 20% (h)

HEAT BIN 10-20 % HRS

heat_bin_1020_1

0.0

FALSE

/ HeatBin 70% (h)

HEAT BIN 60-70 % HRS

heat_bin_6070_1

0.0

FALSE

HeatBin 30% (h)

HEAT BIN 20-30 % HRS

heat_bin_2030_1

0.0

FALSE

/ HeatBin 80% (h)

HEAT BIN 70-80 % HRS

heat_bin_7080_1

0.0

FALSE

HeatBin 40% (h)

HEAT BIN 30-40 % HRS

heat_bin_3040_1

0.0

FALSE

/ HeatBin 90% (h)

HEAT BIN 80-90 % HRS

heat_bin_8090_1

0.0

FALSE

HeatBin 50% (h)

HEAT BIN 40-50 % HRS

heat_bin_4050_1

0.0

FALSE

/HeatBin 100% (h)

HEAT BIN 90-100 % HRS

heat_bin_90100_1

0.0

FALSE

Reset Hours in ALL Heat Bins:

HEAT BIN RESET

heat_bin_reset_1

Off

Off, On

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

COOL BIN LOAD CAP% STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

CoolLogic Cool BinLoad Cap% Status
CoolBin 10% (h)

COOL BIN 0-10 % HRS

cool_bin_0010_1

0.044166666

FALSE

/ CoolBin 60% (h)

COOL BIN 50-60 % HRS

cool_bin_5060_1

0.0

FALSE

CoolBin 20% (h)

COOL BIN 10-20 % HRS

cool_bin_1020_1

0.11083333

FALSE

/ CoolBin 70% (h)

COOL BIN 60-70 % HRS

cool_bin_6070_1

0.0

FALSE

CoolBin 30% (h)

COOL BIN 20-30 % HRS

cool_bin_2030_1

0.11305556

FALSE

/ CoolBin 80% (h)

COOL BIN 70-80 % HRS

cool_bin_7080_1

0.0

FALSE

CoolBin 40% (h)

COOL BIN 30-40 % HRS

cool_bin_3040_1

0.03

FALSE

/ CoolBin 90% (h)

COOL BIN 80-90 % HRS

cool_bin_8090_1

0.0

FALSE

CoolBin 50% (h)

COOL BIN 40-50 % HRS

cool_bin_4050_1

0.0

FALSE

/CoolBin 100% (h)

COOL BIN 90-100 % HRS

cool_bin_90100_1

0.0

FALSE

Reset Hours in ALL Cool Bins:

COOL BIN RESET

cool_bin_reset_1

Off

Off, On

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MAIN TXV PID SETTINGS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

MAIN TXV PID Settings
M1C1 MainTXV PID Output: (%)

Module 1 Comp 1 Main TXV PID
Out

m1c1_mntx_pid_5

4.1325912

FALSE

M2C1 MainTXV PID Output: (%)

Module 2 Comp 1 Main TXV PID
Out

m2c1_mntx_pid_5

3.0173447

FALSE

M3C1 MainTXV PID Output: (%)

Module 3 Comp 1 Main TXV PID
Out

m3c1_mntx_pid_5

0.0

FALSE

M4C1 MainTXV PID Output: (%)

Module 4 Comp 1 Main TXV PID
Out

m4c1_mntx_pid_5

0.0

FALSE

Main TXV Superheat Setpoint:

Main TX SPRHT Setpoint

mntx_sprht_stpt_5

8.0

0

99

TRUE

Main TXV PID Interval:

MNTX PID Interval

mntx_interval_5

3.0 sec

1

999

TRUE

Main TXV PID Gain :

MNTX PID gain

mntx_gain_5

1.0

0

999

TRUE

Main TXV PID P-Gain :

MNTX PID P-gain

mntx_p_gain_5

11.0

0

999

TRUE

Main TXV PID I-Gain#1:

MNTX PID I-gain

mntx_i_gain_5

0.8

0

99

TRUE

Main TXV PID I-Gain#2:

MNTX PID IG2

mntx_i_gain2_5

0.0

0

99

TRUE

Main TXV PID D-Gain#1:

MNTX PID D-gain

mntx_d_gain_5

0.0

0

99

TRUE

Main TXV PID Rise : (%/min)

MNTX PID Rise

mntx_pid_rise_5

30.0 sec

1

999

TRUE

Main TXV PID Fall : (%/min)

MNTX PID Fall

mntx_pid_fall_5

30.0

1

999

TRUE

Main TXV PID Limit : (%)

Main TX Maximum PID

mntx_max_pid_5

65.0

55

999

FALSE

Main TXV PID Deadbd1 :

mntx_db1_5

0

99

TRUE

Main TXV PID Deadbd2 :

MNTX PID DB2

mntx_pid_db2_5

0.0

0

99

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MAIN TXV PSI PID SETTINGS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

MAIN TXV PID Settings FOR PSI
M1C1 MainTXV PID Output : (%)

Module 1 Comp 1 Main TXV PID
Out

m1c1_mntx_pid_5

4.1325912

FALSE

M2C1 MainTXV PID Output : (%)

Module 2 Comp 1 Main TXV PID
Out

m2c1_mntx_pid_5

3.0173447

FALSE

M3C1 MainTXV PID Output : (%)

Module 3 Comp 1 Main TXV PID
Out

m3c1_mntx_pid_5

0.0

FALSE

M4C1 MainTXV PID Output : (%)

Module 4 Comp 1 Main TXV PID
Out

m4c1_mntx_pid_5

0.0

FALSE

MainTXV for PSI PID Interval:

MNTX PID PSI Interval

mntx_psi_interval_5

3.0 sec

1

999

TRUE