Chilled Water Temperature

Modules are designed for a leaving water temperature

range from 40°F to 62°F . All cataloged modules can operate

safely in this range without the need of special controls or

glycol additives . Leaving water temperatures below 40°F

can result in evaporator suction temperatures below the

freezing point of water . Therefore, a glycol solution additive

is required that will protect the evaporator from freeze ups

at lower operating suction temperatures . The full range of

leaving chiller fluid using glycol is 20°F to 62°F.

Water Temperature Requirements

Condenser Water Temperature

The condensers are designed to operate most efficiently

at lower entering water temperatures for lower power

consumption . The expansion valve, however, relies on

the pressure difference across the valve to drive the liquid

refrigerant through . It is necessary to maintain a minimum

pressure differential across the thermal expansion valve

(equivalent to a 30°F difference between saturated

liquid temperature in the condenser and saturated vapor

temperature in the evaporator) to avoid loss of efficiency

and system performance. This pressure differential is most

commonly ensured by cycling the fans on the cooling tower

to maintain the entering condenser water temperature

above the minimum temperature of 60°F . An alternate

method to maintain the minimum entering condenser water

temperature above 60°F is to employ a bypass arrangement

as shown in Figure 13 below . This valve is an automatic

3-way bypass valve, which senses the temperature of the

mixed water entering the condenser . If this mixed water

temperature falls below 60°F the valve will re-circulate

the leaving condenser water and mix it into the entering

condenser water stream (bypassing the cooling tower).

The full range of entering condenser water is 60°F to 95°F

for standard applications and maximum leaving hot water

temperature of 135°F for high temperature applications .

For entering water less than 60°F refer to Options and

Accessories (page 52) - Motorized Water Isolation Valves.

Note: Contact factory for applications outside of the

standard temperature range.

Figure 13 – Condenser Water System

Pressure Taps

Thermometer

Wells

Isolation Valves

Condenser Water

Flow Sensor or

Switch

Pressure Relief Valve

Flow to Tower Load

Flow from Tower

Cooling Tower

Bypass Valve

Strainer Isolation

Valve

Pump

Backflow

Preventer

Strainer

Drain

Valve

Backflow

Preventer

Pressure

Relief Valve

Note: Only required for equipment without motorized condenser valves .