Physical Data

Model UGW Module and Compressor

80

Capacity (Tons)

1

77

Refrigerant Type

R-134a

Compressor kWi

53.75

kW/Ton @ Full Load

0.698

Compressor Type

Optimized Quiet Screw

Compressor Quantity

1

Compressor Nominal HP

80

Refrigerant Charge (lbs)

119

Oil Circulation Rate

<0.5%

Module Operating Weight w/Water (lbs)

2

3,422

Module Shipping Weight (lbs)

3

2,995

Heat Exchanger (Type)

Brazed Plate

Refrigerant Circuits (quantity)

1

Water Storage Volume HX Only (gals.)

11.2

Water Storage Volume HX Plus 8" Main Headers (gals.)

26.4

Maximum Working Design Pressure-Water Side (PSI)

300

Header Water Connections - Inlet/Outlet (inches)

4

8

Heat Exchanger (Type)

Brazed Plate

Refrigerant Circuits (quantity)

1

Water Storage Volume HX Only (gals.)

14.9

Water Storage Volume HX Plus 8" Main Headers (gals)

30.1

Maximum Working Design Pressure - Water Side (PSI)

300

Header Water Connections - Inlet/Outlet (inches)

4

6

Notes:

4. Main header water/fluid connections are 8" grooved coupling.
5. Utilize Selection Program for performance based on glycol solution.

2. Module operational weight includes water, compressor oil, and refrigerant charge. Multiply times the number of modules for a total sytem operational weight.
3. Module shipping weight includes refrigerant charge, compressor oil and packaging.

Model UGW Evaporator

Model UGW Condenser

1. Tonnage ratings conditions: 44°F leaving chilled water temperature, 85°F entering condenser water temperature, flow rates are 3 GPM per ton through the condenser with a fouling
factor of .00025 and 2.4 GPM per ton through the evaporator with a .0001 fouling factor.

Notes:

a .0001 fouling factor.

a total system operational weight.

4. Main header water/fluid connections are 8" grooved coupling.
5. Utilize Selection Program for performance based on glycol solution.

2. Module operational weight includes water, compressor oil, and refrigerant charge. Multiply times the number of modules for

3. Module shipping weight includes refrigerant charge, compressor oil and packaging.

1. Tonnage ratings conditions: 44°F leaving chilled water temperature, 85°F entering condenser water temperature, flow rates are
3 GPM per ton through the condenser with a fouling factor of .00025 and 2.4 GPM per ton through the evaporator with