Control Access Display Table

Page 7 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Mod Active Status DisPr Alm SP:

Module Hi Disch Press Setpt

mod_hi_disch_press_sp_5

200.0

FALSE

Default Head Pressure Value:

Module Default Head Pressure

mod_default_hp_5

70.0

50

650

TRUE

Head Pressure Min Adj Value:

Module Head Pressure Positive
Adj

mod_hp_pos_adj_5

60.0

50

650

TRUE

SucPr Alm 134a

Low Suction Press Sp 134a

mod_lo_suc_press_sp_134_5

15.0

2

200

TRUE

SucPr Alm 410a

Low Suction Press Sp 410a

mod_lo_suc_press_sp_410_5

94.0

2

150

TRUE

/SucPr Alm 407C

Low Suction Press Sp 407C

mod_lo_suc_press_sp_407_5

50.0

2

120

TRUE

Mod Active Status SucPr Alm SP:

Module Low Suction Press Setpt mod_low_press_sp_5

15.0

FALSE

Mod SucPr Time Delay Before Alarm:

Module LO SUC PSI Delay

mod_lo_suc_psi_delay_5

30.0

0

999

TRUE

Mod Extra Low SucPr Alm SP:

Module LO-LO SUC PSI Setpoint mod_low_low_press_sp_5

0.0

-5

50

TRUE

Low Dis Pr Ctrl SP R134a

Low Head Press Sp 134a

mod_lo_disch_press_sp_134_5

100.0

20

350

TRUE

Low Dis Pr Ctrl SP R410a

Low Head Press Sp 410a

mod_lo_disch_press_sp_410_5

220.0

50

450

TRUE

Low Dis Pr Ctrl SP R407C

Low Head Press Sp 407

mod_lo_disch_press_sp_407_5

150.0

50

300

TRUE

Mod Active Status Low DisPr Alm SP:

Module Lo Disch Press Setpt

mod_lo_disch_press_sp_5

100.0

FALSE

M DisTp Alm SP

Module Hi Disch Temp

mod_hi_disch_tmp_5

225.0

100

325

TRUE

/M SucTp Alm SP

Module Low Suction Temp

mod_lo_suction_tmp_5

32.0

10

75

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

LO SUC SPRHT & LO DISCH SPRHT SETPTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Suc&Dis SuperHt Alrm Setpts
M Lo DisSuprHt

Module Low Disch SuperHt
Setpt

mod_lo_disc_supht_sp_5

15.0

TRUE

/M Lo SucSuprHt

Module Low Suct SuperHt Setpt mod_lo_suc_supht_sp_5

2.0

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

FREEZE TARGET SETPOINT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Freeze Target Setpts Menu
Freeze TrgSp (F)

Module Freeze Target Setpoint mod_freeze_trg_sp_5

36.0

0

50

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

COMPR MIN MAX RUN TIMES
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Compressor Min & Max Run Times
Compr Minimum Run Time (sec)

Module Compr Min Run Time

mod_cmpr_min_run_5

120.0

1

999

TRUE

Compr Minimum Off Time (sec)

Module Compr Min Off Delay

mod_cmpr_off_delay_5

150.0

1

999

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

COMPR ALARM DELAY
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compr Alarm Delays
Mod Alm Delay

Module Compr Status Alarm
Delay

mod_comp_stat_alm_delay_5

9999.0

5

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MODULE WATER TEMP LIMITS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Module Water Out Temp Limits
Mod Evap Wat Out Lo Limit: (F)

Module Freeze Target Setpoint mod_freeze_trg_sp_5

36.0

0

165

TRUE

Mod Evap Wat Out Hi Limit: (F)

Module High Evaporator Leaving
Temp at Startup

mod_high_evap_lvg_tmp_5

90.0

0

165

TRUE

Mod Cond Wat Out Lo Limit: (F)

Module Low Condenser Leaving
Temp. Setpoint

mod_low_cond_lvg_sp_5

50.0

0

165

TRUE

Mod Cond Wat Out Hi Limit:
HI WTR OUT UGW

UCW Module High Cond Leaving
Temp at Startup

ugw_mod_cwr_trg_sp_5

118.0

10

165

TRUE

/HI WTR OUT UGH

UCH Module High Cond Leaving
Temp at Startup

ugh_mod_cwr_trg_sp_5

140.0

10

165

TRUE

Mod Cond Wat Out Hi Limit: (F)

Module Leaving Cond Water
Temp Setpoint

mod_cwr_trg_sp_5

118.0

10

165

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

SCREW COMP ALARM SETPOINTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Screw Comp Alarm Setpoints
Screw Comp Max Amps Allowed 460:

Compressor Max Amps

mod_max_amps_sp_5

105.0

1

999

TRUE

Winding Temp Correlation to ohms:

Compr Max Winding Temp
Sensor Resis

mod_max_wind_sens_ohms_5

275.0

1

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

SERVICE MENU SETUP FN7

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Page 8 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

CoolLogic Service Menu Setup FN7
LINK(S): DIAGNOSTICS MANUAL MODE,CALIB WATER DIFF PRESS SENSORS,CALIB WATER MAINS & AIR TEMPS,ALL MODULE SENSOR CALIBRATION MENUS,
ALL MODULE COMP UNLOAD STATUS,RESET MODULE SENSOR OOR ALARMS,RESET COMP ALARMS,MODULE WATER TEMP LIMITS,WATER MAINS & AIR TEMP LIMITS,
PUMP DOWN SETUP,LOCK WATER TEMPS,RESET COMP RUNTIME & CYCLES,TIME MSTR,SCREW PID SEQUENCING DATA,PREV, SYSTEM SETUP, HOME, ALARM

DIAGNOSTICS MANUAL MODE
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

(/)
Link (/)

Manual Mode M1, Manual Mode M2

Link (/)

Manual Mode M3, Manual Mode M4

/
SWAP LEAD COMPR:

Manually Refresh Lead Module man_refr_modlead_1

Do Not

Refresh Lead

Do Not Refresh

Lead, Refresh

Lead

TRUE

LINK(S): MANUAL MODE M5, MANUAL MODE M6,LOCK WATER TEMPS,PREV, SYSTEM SETUP, HOME, ALARM

MANUAL MODE Mx
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

M1 Manual Mode

M1 Manual Mode Enable

m1_man_mode_5

Off

Off, On

TRUE

M1C1 Manual ON

M1C1 Manual Run

m1c1_man_run_5

Off

Off, On

TRUE

M1C1 Status:

Module 1 Comp 1 Status

m1_comp1_status_5

On

Off, On

FALSE

LINK(S): PREV, SERVICE MENU SETUP, HOME

CALIB WATER DIFF PRESS SENSORS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Calibrate Water Diff Press Sensors
Cool Water Dif Psi Stat: (PSID)

Diff Press Cool Load

diff_press_cool_load_1

8.48872 °F

FALSE

Cool PsiCalib Offset: (PSID)

Chilled Diff Press Calibration
Point

chwpsi_cali_point_1

0.0

-199

199

TRUE

Heat Water Dif Psi Stat: (PSID)

Diff Press Heat Load

diff_press_heat_load_1

8.053761 °F

FALSE

Heat Psi Calib Offset: (PSID)

Cond Diff Press Calibration Point cwpsi_cali_point_1

0.0

-199

199

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

CALIB WATER MAINS & AIR TEMPS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Calibrate Main Header Water &Air Temps
Evap InSens: (F)

EVAP IN TMP

chwr_temp_1

54.4 °F

FALSE

/Evap Wat In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

Evap In Calib Offset: (F)

CHWR Temp Calibration Point

chwr_cali_point_1

0.0

-250

250

TRUE

Evp OutSens: (F)

EVAP OUT TMP

chws_temp_1

50.1 °F

FALSE

/Evap WatOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

Evap Out Calib Offset: (F)

CHWS Temp Calibration Point

chws_cali_point_1

0.0

-250

250

TRUE

Cnd Out Sens: (F)

COND OUT TMP

cwr_temp_1

83.3 °F

FALSE

/CndWat Out: (F)

CWR Out Status

cwr_stat_1

83.3

FALSE

Cond Out Calib Offset: (F)

CWR Calibration Point

cwr_cali_point_1

0.0

-250

250

TRUE

Cond In Sens: (F)

COND IN TMP

cws_temp_1

67.3 °F

FALSE

/Cnd Wat In: (F)

CWS In Temp Status

cws_stat_1

67.3 °F

FALSE

Cond In Calib Offset: (F)

CWS Temp Calibration Point

cws_cali_point_1

0.0

-250

250

TRUE

Outdoor Sens: (F)

OA Temp

oat_1

-60.2 °F

FALSE

/Outdr Air : (F)

OAT Status

oat_stat_1

61.0

FALSE

Outdoor Air Calib Offset: (F)

OAT Calibration Point

oat_cali_point_1

0.0

-250

250

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

ALL MODULE SENSOR CALIBRATION MENUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic All Module Calibration Menus
LINK(S): MODULE 1 SENSOR CALIBRATIONS,MODULE 2 SENSOR CALIBRATIONS,MODULE 3 SENSOR CALIBRATIONS,MODULE 4 SENSOR CALIBRATIONS,
MODULE 5 SENSOR CALIBRATIONS,MODULE 6 SENSOR CALIBRATIONS,PREV, SYSTEM SETUP, HOME, ALARM

MODULE X SENSOR CALIBRATIONS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

ClimaCool Module 1 Water Calibrations
EvpOutCalib: (F)

M1 CHWS Temp Calib. Point

m1_chws_temp_cp_5

0.0

-250

250

TRUE

/EvpOutSta: (F)

M1 Evap Leaving Temp

m1_chws_temp_stat_5

51.7

FALSE

CndOutCal: (F)

M1 CWR Temp Calib. Point

m1_cwr_temp_cp_5

0.0

-250

250

TRUE

/CondOutStat: (F)

M1 Cond Leaving Temp

m1_cwr_temp_stat_5

84.6

FALSE

ClimaCool Module 1 Refrig Calibrations
C1DisPresCal: (psi)

M1C1 DIS Pressure Calib. Point

m1c1_disch_pres_cp_5

0.0

-250

250

TRUE

/C1DisPr: (psi)

Module 1 Comp 1 Disch Press

m1_c1_disch_pres_stat_5

99.3

0

350

FALSE

C1SucPresCal: (psi)

M1C1 SUC Pressure Calib. Point m1c1_suc_pres_cp_5

0.0

-250

250

TRUE

Page 7 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Mod Active Status DisPr Alm SP:

Module Hi Disch Press Setpt

mod_hi_disch_press_sp_5

200.0

FALSE

Default Head Pressure Value:

Module Default Head Pressure

mod_default_hp_5

70.0

50

650

TRUE

Head Pressure Min Adj Value:

Module Head Pressure Positive
Adj

mod_hp_pos_adj_5

60.0

50

650

TRUE

SucPr Alm 134a

Low Suction Press Sp 134a

mod_lo_suc_press_sp_134_5

15.0

2

200

TRUE

SucPr Alm 410a

Low Suction Press Sp 410a

mod_lo_suc_press_sp_410_5

94.0

2

150

TRUE

/SucPr Alm 407C

Low Suction Press Sp 407C

mod_lo_suc_press_sp_407_5

50.0

2

120

TRUE

Mod Active Status SucPr Alm SP:

Module Low Suction Press Setpt mod_low_press_sp_5

15.0

FALSE

Mod SucPr Time Delay Before Alarm:

Module LO SUC PSI Delay

mod_lo_suc_psi_delay_5

30.0

0

999

TRUE

Mod Extra Low SucPr Alm SP:

Module LO-LO SUC PSI Setpoint mod_low_low_press_sp_5

0.0

-5

50

TRUE

Low Dis Pr Ctrl SP R134a

Low Head Press Sp 134a

mod_lo_disch_press_sp_134_5

100.0

20

350

TRUE

Low Dis Pr Ctrl SP R410a

Low Head Press Sp 410a

mod_lo_disch_press_sp_410_5

220.0

50

450

TRUE

Low Dis Pr Ctrl SP R407C

Low Head Press Sp 407

mod_lo_disch_press_sp_407_5

150.0

50

300

TRUE

Mod Active Status Low DisPr Alm SP:

Module Lo Disch Press Setpt

mod_lo_disch_press_sp_5

100.0

FALSE

M DisTp Alm SP

Module Hi Disch Temp

mod_hi_disch_tmp_5

225.0

100

325

TRUE

/M SucTp Alm SP

Module Low Suction Temp

mod_lo_suction_tmp_5

32.0

10

75

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

LO SUC SPRHT & LO DISCH SPRHT SETPTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Suc&Dis SuperHt Alrm Setpts
M Lo DisSuprHt

Module Low Disch SuperHt
Setpt

mod_lo_disc_supht_sp_5

15.0

TRUE

/M Lo SucSuprHt

Module Low Suct SuperHt Setpt mod_lo_suc_supht_sp_5

2.0

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

FREEZE TARGET SETPOINT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Freeze Target Setpts Menu
Freeze TrgSp (F)

Module Freeze Target Setpoint mod_freeze_trg_sp_5

36.0

0

50

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

COMPR MIN MAX RUN TIMES
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Compressor Min & Max Run Times
Compr Minimum Run Time (sec)

Module Compr Min Run Time

mod_cmpr_min_run_5

120.0

1

999

TRUE

Compr Minimum Off Time (sec)

Module Compr Min Off Delay

mod_cmpr_off_delay_5

150.0

1

999

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

COMPR ALARM DELAY
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compr Alarm Delays
Mod Alm Delay

Module Compr Status Alarm
Delay

mod_comp_stat_alm_delay_5

9999.0

5

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MODULE WATER TEMP LIMITS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Module Water Out Temp Limits
Mod Evap Wat Out Lo Limit: (F)

Module Freeze Target Setpoint mod_freeze_trg_sp_5

36.0

0

165

TRUE

Mod Evap Wat Out Hi Limit: (F)

Module High Evaporator Leaving
Temp at Startup

mod_high_evap_lvg_tmp_5

90.0

0

165

TRUE

Mod Cond Wat Out Lo Limit: (F)

Module Low Condenser Leaving
Temp. Setpoint

mod_low_cond_lvg_sp_5

50.0

0

165

TRUE

Mod Cond Wat Out Hi Limit:
HI WTR OUT UGW

UCW Module High Cond Leaving
Temp at Startup

ugw_mod_cwr_trg_sp_5

118.0

10

165

TRUE

/HI WTR OUT UGH

UCH Module High Cond Leaving
Temp at Startup

ugh_mod_cwr_trg_sp_5

140.0

10

165

TRUE

Mod Cond Wat Out Hi Limit: (F)

Module Leaving Cond Water
Temp Setpoint

mod_cwr_trg_sp_5

118.0

10

165

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

SCREW COMP ALARM SETPOINTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Screw Comp Alarm Setpoints
Screw Comp Max Amps Allowed 460:

Compressor Max Amps

mod_max_amps_sp_5

105.0

1

999

TRUE

Winding Temp Correlation to ohms:

Compr Max Winding Temp
Sensor Resis

mod_max_wind_sens_ohms_5

275.0

1

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

SERVICE MENU SETUP FN7

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Page 8 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

CoolLogic Service Menu Setup FN7
LINK(S): DIAGNOSTICS MANUAL MODE,CALIB WATER DIFF PRESS SENSORS,CALIB WATER MAINS & AIR TEMPS,ALL MODULE SENSOR CALIBRATION MENUS,
ALL MODULE COMP UNLOAD STATUS,RESET MODULE SENSOR OOR ALARMS,RESET COMP ALARMS,MODULE WATER TEMP LIMITS,WATER MAINS & AIR TEMP LIMITS,
PUMP DOWN SETUP,LOCK WATER TEMPS,RESET COMP RUNTIME & CYCLES,TIME MSTR,SCREW PID SEQUENCING DATA,PREV, SYSTEM SETUP, HOME, ALARM

DIAGNOSTICS MANUAL MODE
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

(/)
Link (/)

Manual Mode M1, Manual Mode M2

Link (/)

Manual Mode M3, Manual Mode M4

/
SWAP LEAD COMPR:

Manually Refresh Lead Module man_refr_modlead_1

Do Not

Refresh Lead

Do Not Refresh

Lead, Refresh

Lead

TRUE

LINK(S): MANUAL MODE M5, MANUAL MODE M6,LOCK WATER TEMPS,PREV, SYSTEM SETUP, HOME, ALARM

MANUAL MODE Mx
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

M1 Manual Mode

M1 Manual Mode Enable

m1_man_mode_5

Off

Off, On

TRUE

M1C1 Manual ON

M1C1 Manual Run

m1c1_man_run_5

Off

Off, On

TRUE

M1C1 Status:

Module 1 Comp 1 Status

m1_comp1_status_5

On

Off, On

FALSE

LINK(S): PREV, SERVICE MENU SETUP, HOME

CALIB WATER DIFF PRESS SENSORS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Calibrate Water Diff Press Sensors
Cool Water Dif Psi Stat: (PSID)

Diff Press Cool Load

diff_press_cool_load_1

8.48872 °F

FALSE

Cool PsiCalib Offset: (PSID)

Chilled Diff Press Calibration
Point

chwpsi_cali_point_1

0.0

-199

199

TRUE

Heat Water Dif Psi Stat: (PSID)

Diff Press Heat Load

diff_press_heat_load_1

8.053761 °F

FALSE

Heat Psi Calib Offset: (PSID)

Cond Diff Press Calibration Point cwpsi_cali_point_1

0.0

-199

199

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

CALIB WATER MAINS & AIR TEMPS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Calibrate Main Header Water &Air Temps
Evap InSens: (F)

EVAP IN TMP

chwr_temp_1

54.4 °F

FALSE

/Evap Wat In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

Evap In Calib Offset: (F)

CHWR Temp Calibration Point

chwr_cali_point_1

0.0

-250

250

TRUE

Evp OutSens: (F)

EVAP OUT TMP

chws_temp_1

50.1 °F

FALSE

/Evap WatOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

Evap Out Calib Offset: (F)

CHWS Temp Calibration Point

chws_cali_point_1

0.0

-250

250

TRUE

Cnd Out Sens: (F)

COND OUT TMP

cwr_temp_1

83.3 °F

FALSE

/CndWat Out: (F)

CWR Out Status

cwr_stat_1

83.3

FALSE

Cond Out Calib Offset: (F)

CWR Calibration Point

cwr_cali_point_1

0.0

-250

250

TRUE

Cond In Sens: (F)

COND IN TMP

cws_temp_1

67.3 °F

FALSE

/Cnd Wat In: (F)

CWS In Temp Status

cws_stat_1

67.3 °F

FALSE

Cond In Calib Offset: (F)

CWS Temp Calibration Point

cws_cali_point_1

0.0

-250

250

TRUE

Outdoor Sens: (F)

OA Temp

oat_1

-60.2 °F

FALSE

/Outdr Air : (F)

OAT Status

oat_stat_1

61.0

FALSE

Outdoor Air Calib Offset: (F)

OAT Calibration Point

oat_cali_point_1

0.0

-250

250

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

ALL MODULE SENSOR CALIBRATION MENUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic All Module Calibration Menus
LINK(S): MODULE 1 SENSOR CALIBRATIONS,MODULE 2 SENSOR CALIBRATIONS,MODULE 3 SENSOR CALIBRATIONS,MODULE 4 SENSOR CALIBRATIONS,
MODULE 5 SENSOR CALIBRATIONS,MODULE 6 SENSOR CALIBRATIONS,PREV, SYSTEM SETUP, HOME, ALARM

MODULE X SENSOR CALIBRATIONS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

ClimaCool Module 1 Water Calibrations
EvpOutCalib: (F)

M1 CHWS Temp Calib. Point

m1_chws_temp_cp_5

0.0

-250

250

TRUE

/EvpOutSta: (F)

M1 Evap Leaving Temp

m1_chws_temp_stat_5

51.7

FALSE

CndOutCal: (F)

M1 CWR Temp Calib. Point

m1_cwr_temp_cp_5

0.0

-250

250

TRUE

/CondOutStat: (F)

M1 Cond Leaving Temp

m1_cwr_temp_stat_5

84.6

FALSE

ClimaCool Module 1 Refrig Calibrations
C1DisPresCal: (psi)

M1C1 DIS Pressure Calib. Point

m1c1_disch_pres_cp_5

0.0

-250

250

TRUE

/C1DisPr: (psi)

Module 1 Comp 1 Disch Press

m1_c1_disch_pres_stat_5

99.3

0

350

FALSE

C1SucPresCal: (psi)

M1C1 SUC Pressure Calib. Point m1c1_suc_pres_cp_5

0.0

-250

250

TRUE

Page 9 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

/C1SucPr: (ps)

Module 1 Comp 1 Suction
Pressure

m1_c1_suc_pres_stat_5

40.6

FALSE

C1DisTmpCal: (F)

M1C1 DIS Temp Calib. Point

m1c1_disch_temp_cp_5

0.0

-250

250

TRUE

/C1DisTp: (F)

Module 1 Comp 1 Disch Temp

m1_c1_disch_temp_stat_5

110.3

FALSE

C1SucTempCal: (F)

M1C1 SUC Temp Calib. Point

m1c1_suc_tmp_cp_5

0.0

-250

250

TRUE

/C1SucTp: (F)

Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5

53.6

FALSE

C1CompAmpCal:

M1C1 Amps Calib. Point

m1c1_amps_cp_5

3.0

-250

250

TRUE

/C1 Amps:

Module 1 Comp 1 Amps

m1c1_amps_stat_5

33.6

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

LOCK WATER TEMPS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Lock Main Header Water & Air Temps
Evap Wat In Lock :

Lock CHWR Temp

lock_chwr_1

No

Off, On

TRUE

Evap Wat In Lock Value : (F)

CHWR Lock Value

chwr_lock_val_1

54.0

0

165

TRUE

Evap Wat Out Lock:

Lock EVAP LVG TMP

lock_chws_1

No

Off, On

TRUE

Evap Wat Out Lock Value: (F)

EVAP LVG TMP Lock Value

chws_lock_val_1

43.0

0

165

TRUE

Cond Wat In Lock :

Lock CWS Temp

lock_cws_1

No

Off, On

TRUE

Cond Wat In Lock Value : (F)

CWS Lock Value

cws_lock_val_1

85.0

0

165

TRUE

Cond Wat Out Lock:

Lock CWR Temp

lock_cwr_1

No

Off, On

TRUE

Cond Wat Out Lock Value: (F)

CWR Lock Value

cwr_lock_val_1

58.0

0

165

TRUE

Outdoor Air Lock:

Lock CHWS Temp

lock_oat_1

Yes

Off, On

TRUE

Outdoor Air Lock Value: (F)

OAT Lock Value

oat_lock_val_1

61.0

-20

140

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

SCREW PID SEQUENCING DATA
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic PID Sequencing Data
VFD Minimum VDC Input: 4.3

VFD Minimum VDC Input

vfd_min_vdc_1

4.4

0

10

TRUE

VFD Minimum VDC In 3 Scr: 6.16

VFD Minimum for Three Screws vfd_min_vdc_three_scr_1

6.16

0

10

TRUE

VFD Minimum VDC In 4 Scr: 7.17

VFD Minimum for Four Screws

vfd_min_vdc_four_scr_1

7.17

0

10

TRUE

VFD Maximum VDC Input: 10.00

VFD Maximum VDC Input

vfd_max_vdc_1

10.0

0

10

TRUE

VFD Start PID for One Scr: 33

VFD Start PID for One Screw

vfd_start_pid_one_scr_1

33.0

0

500

TRUE

VFD Min PID for One Scr: 34

VFD Minimum PID for One
Screw

vfd_min_pid_one_scr_1

34.0

0

500

TRUE

VFD Max PID for One Scr: 75

VFD Maximum PID for One
Screw

vfd_max_pid_one_scr_1

75.0

0

500

TRUE

VFD Max One PID Min Two Scr: 85

VFD Max One PID Min Two
Screws

vfd_max_one_pid_min_two_scr_1

85.0

0

500

TRUE

VFD Min PID for Two Scr: 86

VFD Minimum PID for Two
Screws

vfd_min_pid_two_scr_1

86.0

0

500

TRUE

VFD Interim PID Two Scr: 123

VFDInterim PID for One Full One
Min Screws

vfd_interim_pid_two_scr_1

123.0

0

500

TRUE

VFD Max PID for Two Scr: 160

VFD Maximum PID for Two
Screws

vfd_max_pid_two_scr_1

160.0

0

500

TRUE

VFD Max Two PIDMinThree Scr:170

VFD Max Two PID Min Three
Screws

vfd_max_two_pid_min_three_scr_1

170.0

0

500

TRUE

VFD Min PID for Three Scr: 171

VFD Minimum PID for Three
Screws

vfd_min_pid_three_scr_1

171.0

0

500

TRUE

VFD IntPID One Full;Two Min:195

VFDInterim PID for One Full &
Two Min Screws

vfd_interim_pid_one_full_two_min_s
cr_1

195.0

0

500

TRUE

VFD IntPID Two Full;One Min:220

VFD Interim PID for Two Full &
One Min Screws

vfd_interim_pid_two_full_one_min_s
cr_1

220.0

0

500

TRUE

VFD Max PID for Three Scr: 245

VFD Maximum PID for Three
Screws

vfd_max_pid_three_scr_1

245.0

0

500

TRUE

VFD Max 3 PID Min Four Scr: 255

VFD Max Three PID Min Four
Screws

vfd_max_three_pid_min_four_scr_1

255.0

0

500

TRUE

VFD Min PID for Four Scr: 256

VFD Minimum PID for Four
Screws

vfd_min_pid_four_scr_1

256.0

0

500

TRUE

VFD IntPID One Full;3 Min: 274

VFDInterim PID for One Full &
Three Min Screws

vfd_interim_pid_one_full_three_min
_scr_1

274.0

0

500

TRUE

VFD IntPID Two Full;Two Min:292

VFD Interim PID for Two Half &
One Min Screws

vfd_interim_pid_two_full_two_min_s
cr_1

292.0

0

500

TRUE

VFD IntPID 3 Full; One Min: 311

VFD Interim PID for Three Full
One Min Screws

vfd_interim_pid_three_full_one_min
_scr_1

311.0

0

500

TRUE

VFD Max PID for Four Scr: 330

VFD Maximum PID for Four
Screws

vfd_max_pid_four_scr_1

330.0

0

500

TRUE

VFD Last PID: 340

VFD Last PID

vfd_last_pid_1

340.0

0

500

TRUE

Screw Runtime Before Flush 8.0h

Screw Runtime in Minutes

scr_runtime_before_flush_1

4.0

0

999

TRUE

Use Screw Flush Cycle

Use Screw Flush Cycle

use_scr_flush_1

Yes

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME