Control Access Display Table

Page 3 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

LINK(S): PREV, STATUS, HOME, ALARM

ALL COMPR RUNTIME STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor Runtime Status
M1C1 Runtm: (h)

Module 1 Comp 1 Runtime

m1_c1_rtime_1

2.3116667

FALSE

/M4C1 Runtm: (h)

Module 4 Comp 1 Runtime

m4_c1_rtime_1

0.015833333

FALSE

M2C1 Runtm: (h)

Module 2 Comp 1 Runtime

m2_c1_rtime_1

3.02

FALSE

/M5C1 Runtm: (h)

Module 5 Comp 1 Runtime

m5_c1_rtime_1

0.0

FALSE

M3C1 Runtm: (h)

Module 3 Comp 1 Runtime

m3_c1_rtime_1

1.773889

FALSE

/M6C1 Runtm: (h)

Module 6 Comp 1 Runtime

m6_c1_rtime_1

0.0

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALL COMPR CYCLES STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor Cycles Status
M1C1 Cycles:

Module 1 Comp 1 Cycles

m1_c1_cycles_5

1.0

FALSE

/M4C1 Cycles:

Module 4 Comp 1 Cycles

m4_c1_cycles_5

0.0

FALSE

M2C1 Cycles:

Module 2 Comp 1 Cycles

m2_c1_cycles_5

1.0

FALSE

/M5C1 Cycles:

Module 5 Comp 1 Cycles

m5_c1_cycles_5

0.0

FALSE

M3C1 Cycles:

Module 3 Comp 1 Cycles

m3_c1_cycles_5

0.0

FALSE

/M6C1 Cycles:

Module 6 Comp 1 Cycles

m6_c1_cycles_5

0.0

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALL COMPR SS STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor ON/OFF Status
M1C1 Status:

Module 1 Comp 1 Status

m1_comp1_status_5

On

Off, On

FALSE

/ M4C1 Status:

Module 4 Comp 1 Status

m4_comp1_status_5

Off

Off, On

FALSE

M2C1 Status:

Module 2 Comp 1 Status

m2_comp1_status_5

On

Off, On

FALSE

/ M5C1 Status:

Module 5 Comp 1 Status

m5_comp1_status_5

Off

Off, On

FALSE

M3C1 Status:

Module 3 Comp 1 Status

m3_comp1_status_5

Off

Off, On

FALSE

/ M6C1 Status:

Module 6 Comp 1 Status

m6_comp1_status_5

Off

Off, On

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALL COMPR AMPERAGE STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor Amperage Status
M1C1 Compr Amps:

Module 1 Comp 1 Amps

m1c1_amps_stat_5

33.6

FALSE

/M4C1 Compr Amps:

Module 4 Comp 1 Amps

m4c1_amps_stat_5

0.4

FALSE

M2C1 Compr Amps:

Module 2 Comp 1 Amps

m2c1_amps_stat_5

25.4

FALSE

/M5C1 Compr Amps:

Module 5 Comp 1 Amps

m5c1_amps_stat_5

0.0

FALSE

M3C1 Compr Amps:

Module 3 Comp 1 Amps

m3c1_amps_stat_5

0.4

FALSE

/M6C1 Compr Amps:

Module 6 Comp 1 Amps

m6c1_amps_stat_5

0.0

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

SYSTEM SETUP FN2

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic System Setup FN2
LINK(S): GENERAL SYS SETTINGS,HEAT & COOL SETPOINT MENUS,EVAP PUMP SETUP,COND PUMP SETUP,LEAD COMPR ROTATION SETUP,ALARM LOCKOUT RESET,SCHEDULES,
PREV, STATUS, HOME, ALARM

GENERAL SYS SETTINGS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

CoolLogic General System Settings FN4
Chiller Control Type

Control Type

control_type_1

Cool Control

Cool Cntrl,
Heat Cntrl,
Heat Rcvry

TRUE

Chiller Control Source

Control Source

control_source_1

Digital Input

Dig Input,
Keypad, BAS

TRUE

Enable Chiller from Keypad?

Unit Enable (keypad)

enable_keypad_1

On

Off, On

TRUE

Mod Ref Type

Module Compr Ref Type

mod_comp_ref_type_5

134a

22, 407C,
410a, 134a

TRUE

Chiller Model Type:

Chiller Model Type

chiller_model_type_5

UGW

UGW, UGH,
UGR

TRUE

Cool Design Delta Temp

FULL LD COOL DES TD

cool_design_dt_1

-10.0

-50

50

TRUE

Heat Design Delta Temp

FULL LD HEAT DES TD

heat_design_dt_1

10.0

-50

50

TRUE

Use High Amb Tmp Limit?

HI AMBIENT TMP LIM

hi_amb_tmp_lim_1

No

No, Yes

TRUE

Software Version: UGW-H.08b.13
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

HEAT & COOL SETPOINT MENUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat and Cool Setpoints

Page 4 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

LINK(S): COOL MODE SETPOINT,HEAT MODE SETPOINT,MASTER INPUT CHNLS 6, &10 SETUP,MASTER INPUT 8 & 11 SETUP,LEAD COMPR ROTATION SETUP,PREV, SYSTEM SETUP,
HOME, ALARM

COOL MODE SETPOINT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Cool Mode Setpoint Menu
Local Evap Wat Out Setpt: (F)

COOL LVG TRG

chw_temp_stp_1

45.0 °F

0

75

TRUE

Min Evap Wat Out Setpt: (F)

MIN COOL TRG LIM

min_chw_temp_stp_1

40.0 °F

0

75

TRUE

Max Evap Wat Out Setpt: (F)

MAX COOL TRG LIM

max_chw_temp_stp_1

62.0 °F

0

75

TRUE

Remote Evap Wat Out Setpt: (F)

Remote CHW Setpoint

rem_chw_stp_stat_1

40.0 °F

10

75

FALSE

Rem Max Neg CHW Setpt Reset: (F)

MAX NEG DEM LIM COOL RESET max_neg_chw_stp_reset_1

0.0 °F

0

75

TRUE

Rem Max Pos CHW Setpt Reset: (F)

MAX POS DEM LIM COOL RESET max_pos_chw_stp_reset_1

10.0 °F

0

75

TRUE

Remote Evap Wat Out Reset: (F)

Remote CHW Setpoint Reset

rem_chw_stp_reset_1

0.0 °F

0

75

TRUE

Active Evap Wat Out Setpt: (F)

Active CHW Setpoint

chw_stp_stat_1

45.0 °F

10

75

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

HEAT MODE SETPOINT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

CoolLogic Heat Mode Setpoint Menu
Local Cond Wat Out Setpt: (F)

HEAT LVG TRG

cw_temp_stp_1

125.0 °F

10

165

TRUE

Min Cond Wat Out Setpt: (F)

MIN HEAT TRG LIM

min_cw_temp_stp_1

75.0 °F

10

165

TRUE

Max Cond Wat Out Setpt: (F)

MAX HEAT TRG LIM

max_cw_temp_stp_1

135.0 °F

10

165

TRUE

Remote Cond Wat Out Setpt: (F)

Remote CW Setpoint

rem_cw_stp_stat_1

75.0 °F

50

140

FALSE

Rem Max Neg CWR Setpt Reset: (F)

MAX NEG DEM LIM HEAT RESET max_neg_cw_stp_reset_1

0.0 °F

0

165

TRUE

Rem Max Pos CWR Setpt Reset: (F)

MAX POS DEM LIM HEAT RESET max_pos_cw_stp_reset_1

10.0 °F

0

165

TRUE

Auto Cond Wat Reset by OAT: (F)

Remote CW Setpoint

auto_oat_cw_stp_reset_1

135.0 °F

10

165

TRUE

Active Cond Wat Out Setpt: (F)

Active Htg Setpoint

cw_stp_stat_1

125.0 °F

10

165

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

LEAD COMPR ROTATION SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Lead Compr Rotation Setup
Manual Rotate LeadCompr:

Manually Refresh Lead Module man_refr_modlead_1

Do Not

Refresh Lead

Do Not Rotate,

Rotate

TRUE

Rotate Cmpr Lead on Runtime Hrs :

Lead Swap on Runtime

lead_swap_runtime_1

168.0 hr

1

9999

TRUE

Refresh Runtime Hours:

runtime_refresh_4

1

999

TRUE

Stage Down Safety Index: (sec)

safety_ind_delay2_4

1

999

TRUE

Stage Up Safety Index: (sec)

safety_ind_delay1_4

1

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALARM LOCKOUT RESET FN3

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Alarm Lockout Reset FN3
Master Pnl Out-of-Range Alm Reset:

Reset Sensor OOR Alarm

reset_oor_1

No

Off, On

TRUE

Master Pnl Temp Lockout Reset:

LOCK OUT RESET

reset_1

Off

Off, On

TRUE

LINK(S): RESET ALL MODULE ALARMS AT ONCE,RESET COMP ALARMS,RESET COMP VFD ALARMS,RESET MODULE FREEZ & HOT ALARMS,RESET COMP RUNTIME & CYCLES,
RESET MODULE SENSOR OOR ALARMS,PREV, SYSTEM SETUP, HOME, ALARM

RESET ALL MODULE ALARMS AT ONCE
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Module Alarms at Once
Reset ALL Module#1 Alarms at Once?

Reset M1 All Slave Alarms

m1_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#2 Alarms at Once?

Reset M2 All Slave Alarms

m2_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#3 Alarms at Once?

Reset M3 All Slave Alarms

m3_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#4 Alarms at Once?

Reset M4 All Slave Alarms

m4_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#5 Alarms at Once?

Reset M5 All Slave Alarms

m5_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#6 Alarms at Once?

Reset M6 All Slave Alarms

m6_reset_all_slave_alarms_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

RESET COMP ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Compr Alarms
M1C1 in Alarm?

Module 1 Comp 1 Fail

m1_comp1_fail_5

Off

No, Yes

FALSE

/M1C1Reset Alm?

M1C1 Alarm Reset

m1reset_c1_alrm_5

Off

No, Yes

TRUE

M2C1 in Alarm?

Module 2 Comp 1 Fail

m2_comp1_fail_5

Off

No, Yes

FALSE

/M2C1Reset Alm?

M2C1 Alarm Reset

m2reset_c1_alrm_5

Off

No, Yes

TRUE

M3C1 in Alarm?

Module 3 Comp 1 Fail

m3_comp1_fail_5

Off

No, Yes

FALSE

/M3C1Reset Alm?

M3C1 Alarm Reset

m3reset_c1_alrm_5

Off

No, Yes

TRUE

M4C1 in Alarm?

Module 4 Comp 1 Fail

m4_comp1_fail_5

Off

No, Yes

FALSE

/M4C1Reset Alm?

M4C1 Alarm Reset

m4reset_c1_alrm_5

Off

No, Yes

TRUE

M5C1 in Alarm?

Module 5 Comp 1 Fail

m5_comp1_fail_5

Off

No, Yes

FALSE

/M5C1Reset Alm?

M5C1 Alarm Reset

m5reset_c1_alrm_5

Off

No, Yes

TRUE

M6C1 in Alarm?

Module 6 Comp 1 Fail

m6_comp1_fail_5

Off

No, Yes

FALSE

/M6C1Reset Alm?

M6C1 Alarm Reset

m6reset_c1_alrm_5

Off

No, Yes

TRUE

Page 4 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

LINK(S): COOL MODE SETPOINT,HEAT MODE SETPOINT,MASTER INPUT CHNLS 6, &10 SETUP,MASTER INPUT 8 & 11 SETUP,LEAD COMPR ROTATION SETUP,PREV, SYSTEM SETUP,
HOME, ALARM

COOL MODE SETPOINT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Cool Mode Setpoint Menu
Local Evap Wat Out Setpt: (F)

COOL LVG TRG

chw_temp_stp_1

45.0 °F

0

75

TRUE

Min Evap Wat Out Setpt: (F)

MIN COOL TRG LIM

min_chw_temp_stp_1

40.0 °F

0

75

TRUE

Max Evap Wat Out Setpt: (F)

MAX COOL TRG LIM

max_chw_temp_stp_1

62.0 °F

0

75

TRUE

Remote Evap Wat Out Setpt: (F)

Remote CHW Setpoint

rem_chw_stp_stat_1

40.0 °F

10

75

FALSE

Rem Max Neg CHW Setpt Reset: (F)

MAX NEG DEM LIM COOL RESET max_neg_chw_stp_reset_1

0.0 °F

0

75

TRUE

Rem Max Pos CHW Setpt Reset: (F)

MAX POS DEM LIM COOL RESET max_pos_chw_stp_reset_1

10.0 °F

0

75

TRUE

Remote Evap Wat Out Reset: (F)

Remote CHW Setpoint Reset

rem_chw_stp_reset_1

0.0 °F

0

75

TRUE

Active Evap Wat Out Setpt: (F)

Active CHW Setpoint

chw_stp_stat_1

45.0 °F

10

75

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

HEAT MODE SETPOINT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

CoolLogic Heat Mode Setpoint Menu
Local Cond Wat Out Setpt: (F)

HEAT LVG TRG

cw_temp_stp_1

125.0 °F

10

165

TRUE

Min Cond Wat Out Setpt: (F)

MIN HEAT TRG LIM

min_cw_temp_stp_1

75.0 °F

10

165

TRUE

Max Cond Wat Out Setpt: (F)

MAX HEAT TRG LIM

max_cw_temp_stp_1

135.0 °F

10

165

TRUE

Remote Cond Wat Out Setpt: (F)

Remote CW Setpoint

rem_cw_stp_stat_1

75.0 °F

50

140

FALSE

Rem Max Neg CWR Setpt Reset: (F)

MAX NEG DEM LIM HEAT RESET max_neg_cw_stp_reset_1

0.0 °F

0

165

TRUE

Rem Max Pos CWR Setpt Reset: (F)

MAX POS DEM LIM HEAT RESET max_pos_cw_stp_reset_1

10.0 °F

0

165

TRUE

Auto Cond Wat Reset by OAT: (F)

Remote CW Setpoint

auto_oat_cw_stp_reset_1

135.0 °F

10

165

TRUE

Active Cond Wat Out Setpt: (F)

Active Htg Setpoint

cw_stp_stat_1

125.0 °F

10

165

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

LEAD COMPR ROTATION SETUP
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Lead Compr Rotation Setup
Manual Rotate LeadCompr:

Manually Refresh Lead Module man_refr_modlead_1

Do Not

Refresh Lead

Do Not Rotate,

Rotate

TRUE

Rotate Cmpr Lead on Runtime Hrs :

Lead Swap on Runtime

lead_swap_runtime_1

168.0 hr

1

9999

TRUE

Refresh Runtime Hours:

runtime_refresh_4

1

999

TRUE

Stage Down Safety Index: (sec)

safety_ind_delay2_4

1

999

TRUE

Stage Up Safety Index: (sec)

safety_ind_delay1_4

1

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALARM LOCKOUT RESET FN3

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Alarm Lockout Reset FN3
Master Pnl Out-of-Range Alm Reset:

Reset Sensor OOR Alarm

reset_oor_1

No

Off, On

TRUE

Master Pnl Temp Lockout Reset:

LOCK OUT RESET

reset_1

Off

Off, On

TRUE

LINK(S): RESET ALL MODULE ALARMS AT ONCE,RESET COMP ALARMS,RESET COMP VFD ALARMS,RESET MODULE FREEZ & HOT ALARMS,RESET COMP RUNTIME & CYCLES,
RESET MODULE SENSOR OOR ALARMS,PREV, SYSTEM SETUP, HOME, ALARM

RESET ALL MODULE ALARMS AT ONCE
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Module Alarms at Once
Reset ALL Module#1 Alarms at Once?

Reset M1 All Slave Alarms

m1_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#2 Alarms at Once?

Reset M2 All Slave Alarms

m2_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#3 Alarms at Once?

Reset M3 All Slave Alarms

m3_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#4 Alarms at Once?

Reset M4 All Slave Alarms

m4_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#5 Alarms at Once?

Reset M5 All Slave Alarms

m5_reset_all_slave_alarms_5

Off

No, Yes

TRUE

Reset ALL Module#6 Alarms at Once?

Reset M6 All Slave Alarms

m6_reset_all_slave_alarms_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

RESET COMP ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Compr Alarms
M1C1 in Alarm?

Module 1 Comp 1 Fail

m1_comp1_fail_5

Off

No, Yes

FALSE

/M1C1Reset Alm?

M1C1 Alarm Reset

m1reset_c1_alrm_5

Off

No, Yes

TRUE

M2C1 in Alarm?

Module 2 Comp 1 Fail

m2_comp1_fail_5

Off

No, Yes

FALSE

/M2C1Reset Alm?

M2C1 Alarm Reset

m2reset_c1_alrm_5

Off

No, Yes

TRUE

M3C1 in Alarm?

Module 3 Comp 1 Fail

m3_comp1_fail_5

Off

No, Yes

FALSE

/M3C1Reset Alm?

M3C1 Alarm Reset

m3reset_c1_alrm_5

Off

No, Yes

TRUE

M4C1 in Alarm?

Module 4 Comp 1 Fail

m4_comp1_fail_5

Off

No, Yes

FALSE

/M4C1Reset Alm?

M4C1 Alarm Reset

m4reset_c1_alrm_5

Off

No, Yes

TRUE

M5C1 in Alarm?

Module 5 Comp 1 Fail

m5_comp1_fail_5

Off

No, Yes

FALSE

/M5C1Reset Alm?

M5C1 Alarm Reset

m5reset_c1_alrm_5

Off

No, Yes

TRUE

M6C1 in Alarm?

Module 6 Comp 1 Fail

m6_comp1_fail_5

Off

No, Yes

FALSE

/M6C1Reset Alm?

M6C1 Alarm Reset

m6reset_c1_alrm_5

Off

No, Yes

TRUE