Unit installation – ClimaCool UGW Manual User Manual

Page 5

Advertising
background image

3

www.climacoolcorp.com

Unit Installation

Unit Placement

ClimaCool modular chillers must be installed in a conditioned

and dehumidified space. The minimum foundation

requirement for the chiller is a level surface capable of

bearing the combined operating weight of the modules

(See Physical Data on page 5).

Service Access

The recommended service clearances for modules with

standard brazed plate heat exchangers are 36” for front

service access, 36” height clearance for service and 30”

for rear service access as identified in the Recommended

Service Clearances on page 9 . For the optional shell and

tube condenser design, allow 60” for front clearance . Local

building or electrical codes may require additional clearance –

please consult applicable codes .

Draining

When performing standard maintenance procedures such

as flushing a heat exchanger, it will be necessary to isolate

either heat exchanger. ClimaCool modular chillers offer

optional water isolation valves for this purpose . Access

to a floor drain is helpful when performing standard

maintenance procedures . Warning: Water valves must be

reopened after flushing is complete.

Assembling Modules

ClimaCool recommends locking down the chiller to a

concrete base or to three (3) 4” base mounting rails using

the six (6) bolt holes provided in each base pan. Although

the compressors are installed on anti-vibration mountings,

further isolation of the chiller from the structure is

recommended by installing vibration-eliminating springs

or pads under the base rails on which the chiller will rest

(See page 8 – Mounting Rail and Vibration Isolation). One

module should be chosen as the reference module and

carefully located .

Field installed mounting accessories are provided for

adjoining each module .

Header grooved coupling kits containing four (4)

grooved couplings with gaskets

Mounting hardware kit containing necessary bolts,

spacers, nuts and washers

Header bank end cap kit containing four (4) grooved

couplings with gaskets and four (4) end caps

Field installing the mounting hardware kit will assist with

alignment of the modules in a bank and eliminate offset

inconsistencies . The 1/2” mounting holes are provided on

sides of the unit base pan . First module should be set, set

adjacent unit on mounting surface roughly aligned

1 ½” away from the first unit. While holding spacer

in place, work through the first modules front base

cutout to place a washer and insert bolt through the front

mounting hole and spacer . Repeat the process for the rear

mounting hole . Line up mounting hole of adjacent module

with bolt from previous module and working through

adjacent modules front base cutout, place a washer, split

lock washer and nut . Using the appropriate tools tighten

hardware assembly until seated .

Inspect the pipe ends to ensure they are free from any

indentations, projections, roll marks or other harmful

surface defects such as loose paint, scale, dirt, chips,

grease and rust . Inspect the grooved coupling gasket for

any defects . Apply a thin layer of silicone or other

non-petroleum lubricant to the sealing lips of the gasket

as well as to the exterior of the gasket . Install gaskets on

the pipe ends of one of the two modules to be mated .

Be sure the gasket is completely on the pipe to avoid

damage in the next step. Move the second module into

position and line up the piping . Ensure you are maintaining

alignment for any additional modules to be added . When

pipe ends are aligned, slide the gasket over the ends and

center it between the grooves . No part of the gasket

should protrude into the groove of either pipe end . Place

the coupling halves over the gasket and make sure that

the coupling keys (the part that goes into the groove) are

engaged into the grooves . Insert the bolts and install nuts

to hand tight . Ensure the oval neck of the bolt engages into

the bolt hole of the housing . Tighten nuts alternately and

equally until the bolt pads meet and make metal to metal

contact. Tighten nuts by another ¼ to ½ turn to make sure

the nuts and bolts are snug and secure . The use of a torque

wrench is usually not required . Uneven tightening of bolts

may cause the gasket to be pinched resulting in immediate

or delayed leaks.

Header Insulation

Chilled water piping is pre-insulated on each module at

the factory with ¾” closed cell insulation . After bolting

all modules together and leak testing, the entire coupling

connection will need to be insulated by the installing

contractor .

Sound Attenuation Panels and Gasket

Attenuation panels are enclosures made of 18 gauge

galvanized steel with powder coat paint finish and fiberglass

insulation. Panel package includes one (1) upper panel and

one (1) lower panel for each side of bank (field installed),

four (4) panels for each module in the bank (factory

installed) and gasket sealant tape for installation between

modules . Install panels by setting in place and locking down

with the half turn latches or self tapping screws . Note: Panel

package includes a compressed 1” x 1” gasket sealant tape

for installation between modules . Install the tape on the

outer frame on the side of one module prior to installing

the adjacent modules.

Advertising