Control access display table, Local access display table, All module comp unload status fn5 – ClimaCool UGW Manual User Manual

Page 35: Module factory setup fn6, Service menu setup fn7

Advertising
background image

33

www.climacoolcorp.com

Control Access Display Table

Page 5 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET COMP VFD ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Compr VFD Alarms
M1 VFD in Alarm?

Module 1 Comp 1 VFD Fail

m1_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M1C1Reset Alm?

Mod 1 Reset VFD Fault

m1_reset_vfdfault_5

Off

No, Yes

TRUE

M2 VFD in Alarm?

Module 2 Comp 1 VFD Fail

m2_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M2C1Reset Alm?

Mod 2 Reset VFD Fault

m2_reset_vfdfault_5

Off

No, Yes

TRUE

M3 VFD in Alarm?

Module 3 Comp 1 VFD Fail

m3_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M3C1Reset Alm?

Mod 3 Reset VFD Fault

m3_reset_vfdfault_5

Off

No, Yes

TRUE

M4 VFD in Alarm?

Module 4 Comp 1 VFD Fail

m4_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M4C1Reset Alm?

Mod 4 Reset VFD Fault

m4_reset_vfdfault_5

Off

No, Yes

TRUE

M5 VFD in Alarm?

Module 5 Comp 1 VFD Fail

m5_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M5C1Reset Alm?

Mod 5 Reset VFD Fault

m5_reset_vfdfault_5

Off

No, Yes

TRUE

M6 VFD in Alarm?

Module 6 Comp 1 VFD Fail

m6_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M6C1Reset Alm?

Mod 6 Reset VFD Fault

m6_reset_vfdfault_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET MODULE FREEZ & HOT ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Mod Freez &Hot Alarms
M1 inFreezAlm?

Module 1 Freeze Alarm

m1_freeze_alrm_5

No

No, Yes

FALSE

/M1 Frz-CWReset?

Reset Mot1 Vlv Fail

m1_reset_freeze_5

Off

No, Yes

TRUE

M1 in CWR Alm? (/)

Module 1 Leaving Cond Water
Alarm

m1_cwr_alrm_5

No

No, Yes

FALSE

M2 inFreezAlm?

Module 2 Freeze Alarm

m2_freeze_alrm_5

No

No, Yes

FALSE

/M2 Frz-CWReset?

Reset Mot2 Vlv Fail

m2_reset_freeze_5

Off

No, Yes

TRUE

M2 in CWR Alm? (/)

Module 2 Leaving Cond Water
Alarm

m2_cwr_alrm_5

No

No, Yes

FALSE

M3 inFreezAlm?

Module 3 Freeze Alarm

m3_freeze_alrm_5

No

No, Yes

FALSE

/M3 Frz-CWReset?

Reset Mot3 Vlv Fail

m3_reset_freeze_5

Off

No, Yes

TRUE

M3 in CWR Alm? (/)

Module 3 Leaving Cond Water
Alarm

m3_cwr_alrm_5

No

No, Yes

FALSE

M4 inFreezAlm?

Module 4 Freeze Alarm

m4_freeze_alrm_5

No

No, Yes

FALSE

/M4 Frz-CWReset?

Reset Mot4 Vlv Fail

m4_reset_freeze_5

Off

No, Yes

TRUE

M4 in CWR Alm? (/)

Module 4 Leaving Cond Water
Alarm

m4_cwr_alrm_5

No

No, Yes

FALSE

M5 inFreezAlm?

Module 5 Freeze Alarm

m5_freeze_alrm_5

No

No, Yes

FALSE

/M5 Frz-CWReset?

Reset Mot5 Vlv Fail

m5_reset_freeze_5

Off

No, Yes

TRUE

M5 in CWR Alm? (/)

Module 5 Leaving Cond Water
Alarm

m5_cwr_alrm_5

No

No, Yes

FALSE

M6 inFreezAlm?

Module 6 Freeze Alarm

m6_freeze_alrm_5

No

No, Yes

FALSE

/M6 Frz-CWReset?

Reset Mot6 Vlv Fail

m6_reset_freeze_5

Off

No, Yes

TRUE

M6 in CWR Alm? (/)

Module 6 Leaving Cond Water
Alarm

m6_cwr_alrm_5

No

No, Yes

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET COMP RUNTIME & CYCLES
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Reset Compr Runtime & Cycles Menu
M1C1Reset Runtm

M1C1 Runtime Reset

m1reset_c1_rtim_5

Off

No, Yes

TRUE

/M1C1Reset Cyc

M1C1 Cycles Reset

m1c1_cycles_reset_5

Off

No, Yes

TRUE

M2C1Reset Runtm

M2C1 Runtime Reset

m2reset_c1_rtim_5

Off

No, Yes

TRUE

/M2C1Reset Cyc

M2C1 Cycles Reset

m2c1_cycles_reset_5

Off

No, Yes

TRUE

M3C1Reset Runtm

M3C1 Runtime Reset

m3reset_c1_rtim_5

Off

No, Yes

TRUE

/M3C1Reset Cyc

M3C1 Cycles Reset

m3c1_cycles_reset_5

Off

No, Yes

TRUE

M4C1Reset Runtm

M4C1 Runtime Reset

m4reset_c1_rtim_5

Off

No, Yes

TRUE

/M4C1Reset Cyc

M4C1 Cycles Reset

m4c1_cycles_reset_5

Off

No, Yes

TRUE

M5C1Reset Runtm

M5C1 Runtime Reset

m5reset_c1_rtim_5

Off

No, Yes

TRUE

/M5C1Reset Cyc

M5C1 Cycles Reset

m5c1_cycles_reset_5

Off

No, Yes

TRUE

M6C1Reset Runtm

M6C1 Runtime Reset

m6reset_c1_rtim_5

Off

No, Yes

TRUE

/M6C1Reset Cyc

M6C1 Cycles Reset

m6c1_cycles_reset_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET MODULE SENSOR OOR ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Module Sensor OOR Alms
M1C1 inOOR Alm?

Module 1 Comp 1 Sensor OOR

m1_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M1 OOR?

M1 Sensor OOR Reset

m1_oorsl_reset_5

Off

No, Yes

TRUE

M2C1 inOOR Alm?

Module 2 Comp 1 Sensor OOR

m2_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M2 OOR?

M2 Sensor OOR Reset

m2_oorsl_reset_5

Off

No, Yes

TRUE

M3C1 inOOR Alm?

Module 3 Comp 1 Sensor OOR

m3_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M3 OOR?

M3 Sensor OOR Reset

m3_oorsl_reset_5

Off

No, Yes

TRUE

M4C1 inOOR Alm?

Module 4 Comp 1 Sensor OOR

m4_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M4 OOR?

M4 Sensor OOR Reset

m4_oorsl_reset_5

Off

No, Yes

TRUE

Page 6 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

M5C1 inOOR Alm?

Module 5 Comp 1 Sensor OOR

m5_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M5 OOR?

M5 Sensor OOR Reset

m5_oorsl_reset_5

Off

No, Yes

TRUE

M6C1 inOOR Alm?

Module 6 Comp 1 Sensor OOR

m6_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M6 OOR?

M6 Sensor OOR Reset

m6_oorsl_reset_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

ALL MODULE COMP
UNLOAD STATUS FN5

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic All Module Compr Unloads FN5
LINK(S): MOD1 COMPR UNLOAD STATUS,MOD2 COMPR UNLOAD STATUS,MOD3 COMPR UNLOAD STATUS,MOD4 COMPR UNLOAD STATUS,MOD5 COMPR UNLOAD STATUS,
MOD6 COMPR UNLOAD STATUS,PREV, SYSTEM SETUP, HOME, ALARM

MODX COMPR UNLOAD STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Module 1 Compr Unload Status
M1C1 Low Suct Press Unload :

Module 1 Comp 1 Suct Pressure
Unload

m1_c1_lo_suc_psi_unld_5

Off

Off, On

FALSE

M1C1 XLow Suct Press Unload :

Module 1 Comp 1 XLow Suct
Pressure Unload

m1_c1_lolo_suc_psi_unld_5

Off

Off, On

FALSE

M1C1 Low Suct Temp Unload :

Module 1 Comp 1 Suct Temp
Unload

m1_c1_lo_suc_tmp_unld_5

Off

Off, On

FALSE

M1 Evap Freeze Temp Unload :

Module 1 Freeze trg Unload

m1_freeze_trg_unld_5

Off

Off, On

FALSE

M1 Cond WatOut Temp Unload :

Module 1 CWR trg Unload

m1_cwr_trg_unld_5

Off

Off, On

FALSE

M1C1 High Dis Press Unload :

Module 1 Comp 1 Dis Pressure
Unload

m1_c1_hi_dis_psi_unld_5

Off

Off, On

FALSE

M1C1 High Dis Temp Unload :

Module 1 Comp 1 Dis Temp
Unload

m1_c1_hi_dis_tmp_unld_5

Off

Off, On

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MODULE FACTORY SETUP FN6

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Module Factory Setup FN6
LINK(S): REFRIGERANT TYPE,REFRIG TMP & PRESS SENSORS AVAIL,REFRIG TMP & PSI ALARM SETPTS,PUMP DOWN SETUP,LO SUC SPRHT & LO DISCH SPRHT SETPTS,
FREEZE TARGET AND HOT WATER SETPOINT,COMPR MIN MAX RUN TIMES,COMPR ALARM DELAY,MODULE WATER TEMP LIMITS,SCREW COMP ALARM SETPOINTS,PREV,
SYSTEM SETUP, HOME, ALARM

REFRIGERANT TYPE
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Model & Refrig Setup Menu
Mod Ref Type

Module Compr Ref Type

mod_comp_ref_type_5

134a

22, 407C,

410a, 134a

TRUE

Chiller Model Type:

Chiller Model Type

chiller_model_type_5

UGW

UGW, UGH,

UGR

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

REFRIG TMP & PRESS SENSORS AVAIL
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Refr Temp & Press Avail Sensors
Dis Pres Avail

Module DISCH PSI AVAIL

mod_disch_psi_avail_5

On

Off, On

TRUE

/Suc Pres Avail

Module SUC PSI AVAIL

mod_suc_psi_avail_5

On

Off, On

TRUE

Dis Temp Avail

Module DISCH TMP AVAIL

mod_disch_tmp_avail_5

On

Off, On

TRUE

/Suc Temp Avail

Module SUC TMP AVAIL

mod_suc_tmp_avail_5

On

Off, On

TRUE

Avail. Sensor Menu Water Temp.
Leaving Cond Water Temp CWR Avail

Module CWR AVAIL

mod_cwr_avail_5

On

Off, On

TRUE

EnablCWR LoAlm

Module CWR Enable Low Limit

mod_cwr_lo_enable_5

On

Off, On

TRUE

/EnablCHS HiAlm

Module CWR Enable High Limit mod_chs_hi_enable_5

On

Off, On

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

REFRIG TMP & PSI ALARM SETPTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Refr Temp & Press. Alarm Setpts
DisPrAlm134UGW

High Head Press Sp 134a UCW

mod_hi_disch_press_sp_134_ucw_5

200.0

50

650

TRUE

/DisPrAlm134UGH

High Head Press Sp 134a UCH/R mod_hi_disch_press_sp_134_uchr_5

230.0

50

650

TRUE

DisPrAlm410UGW

High Head Press Sp 410a UCW

mod_hi_disch_press_sp_410_ucw_5

385.0

250

650

TRUE

/DisPrAlm410UGH

High Head Press Sp 410a UCH-
UCR

mod_hi_disch_press_sp_410_uchr_5

575.0

250

650

TRUE

DisPrAlm407UGW

High Head Press Sp 407C UCW

mod_hi_disch_press_sp_407_ucw_5

300.0

100

450

TRUE

/DisPrAlm407UGH

High Head Press Sp R-407C UCH-
UCR

mod_hi_disch_press_sp_407_uchr_5

385.0

100

450

TRUE

Page 6 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

M5C1 inOOR Alm?

Module 5 Comp 1 Sensor OOR

m5_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M5 OOR?

M5 Sensor OOR Reset

m5_oorsl_reset_5

Off

No, Yes

TRUE

M6C1 inOOR Alm?

Module 6 Comp 1 Sensor OOR

m6_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M6 OOR?

M6 Sensor OOR Reset

m6_oorsl_reset_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

ALL MODULE COMP
UNLOAD STATUS FN5

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic All Module Compr Unloads FN5
LINK(S): MOD1 COMPR UNLOAD STATUS,MOD2 COMPR UNLOAD STATUS,MOD3 COMPR UNLOAD STATUS,MOD4 COMPR UNLOAD STATUS,MOD5 COMPR UNLOAD STATUS,
MOD6 COMPR UNLOAD STATUS,PREV, SYSTEM SETUP, HOME, ALARM

MODX COMPR UNLOAD STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Module 1 Compr Unload Status
M1C1 Low Suct Press Unload :

Module 1 Comp 1 Suct Pressure
Unload

m1_c1_lo_suc_psi_unld_5

Off

Off, On

FALSE

M1C1 XLow Suct Press Unload :

Module 1 Comp 1 XLow Suct
Pressure Unload

m1_c1_lolo_suc_psi_unld_5

Off

Off, On

FALSE

M1C1 Low Suct Temp Unload :

Module 1 Comp 1 Suct Temp
Unload

m1_c1_lo_suc_tmp_unld_5

Off

Off, On

FALSE

M1 Evap Freeze Temp Unload :

Module 1 Freeze trg Unload

m1_freeze_trg_unld_5

Off

Off, On

FALSE

M1 Cond WatOut Temp Unload :

Module 1 CWR trg Unload

m1_cwr_trg_unld_5

Off

Off, On

FALSE

M1C1 High Dis Press Unload :

Module 1 Comp 1 Dis Pressure
Unload

m1_c1_hi_dis_psi_unld_5

Off

Off, On

FALSE

M1C1 High Dis Temp Unload :

Module 1 Comp 1 Dis Temp
Unload

m1_c1_hi_dis_tmp_unld_5

Off

Off, On

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MODULE FACTORY SETUP FN6

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Module Factory Setup FN6
LINK(S): REFRIGERANT TYPE,REFRIG TMP & PRESS SENSORS AVAIL,REFRIG TMP & PSI ALARM SETPTS,PUMP DOWN SETUP,LO SUC SPRHT & LO DISCH SPRHT SETPTS,
FREEZE TARGET AND HOT WATER SETPOINT,COMPR MIN MAX RUN TIMES,COMPR ALARM DELAY,MODULE WATER TEMP LIMITS,SCREW COMP ALARM SETPOINTS,PREV,
SYSTEM SETUP, HOME, ALARM

REFRIGERANT TYPE
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Model & Refrig Setup Menu
Mod Ref Type

Module Compr Ref Type

mod_comp_ref_type_5

134a

22, 407C,

410a, 134a

TRUE

Chiller Model Type:

Chiller Model Type

chiller_model_type_5

UGW

UGW, UGH,

UGR

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

REFRIG TMP & PRESS SENSORS AVAIL
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Refr Temp & Press Avail Sensors
Dis Pres Avail

Module DISCH PSI AVAIL

mod_disch_psi_avail_5

On

Off, On

TRUE

/Suc Pres Avail

Module SUC PSI AVAIL

mod_suc_psi_avail_5

On

Off, On

TRUE

Dis Temp Avail

Module DISCH TMP AVAIL

mod_disch_tmp_avail_5

On

Off, On

TRUE

/Suc Temp Avail

Module SUC TMP AVAIL

mod_suc_tmp_avail_5

On

Off, On

TRUE

Avail. Sensor Menu Water Temp.
Leaving Cond Water Temp CWR Avail

Module CWR AVAIL

mod_cwr_avail_5

On

Off, On

TRUE

EnablCWR LoAlm

Module CWR Enable Low Limit

mod_cwr_lo_enable_5

On

Off, On

TRUE

/EnablCHS HiAlm

Module CWR Enable High Limit mod_chs_hi_enable_5

On

Off, On

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

REFRIG TMP & PSI ALARM SETPTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Refr Temp & Press. Alarm Setpts
DisPrAlm134UGW

High Head Press Sp 134a UCW

mod_hi_disch_press_sp_134_ucw_5

200.0

50

650

TRUE

/DisPrAlm134UGH

High Head Press Sp 134a UCH/R mod_hi_disch_press_sp_134_uchr_5

230.0

50

650

TRUE

DisPrAlm410UGW

High Head Press Sp 410a UCW

mod_hi_disch_press_sp_410_ucw_5

385.0

250

650

TRUE

/DisPrAlm410UGH

High Head Press Sp 410a UCH-
UCR

mod_hi_disch_press_sp_410_uchr_5

575.0

250

650

TRUE

DisPrAlm407UGW

High Head Press Sp 407C UCW

mod_hi_disch_press_sp_407_ucw_5

300.0

100

450

TRUE

/DisPrAlm407UGH

High Head Press Sp R-407C UCH-
UCR

mod_hi_disch_press_sp_407_uchr_5

385.0

100

450

TRUE

Page 7 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

Mod Active Status DisPr Alm SP:

Module Hi Disch Press Setpt

mod_hi_disch_press_sp_5

200.0

FALSE

Default Head Pressure Value:

Module Default Head Pressure

mod_default_hp_5

70.0

50

650

TRUE

Head Pressure Min Adj Value:

Module Head Pressure Positive
Adj

mod_hp_pos_adj_5

60.0

50

650

TRUE

SucPr Alm 134a

Low Suction Press Sp 134a

mod_lo_suc_press_sp_134_5

15.0

2

200

TRUE

SucPr Alm 410a

Low Suction Press Sp 410a

mod_lo_suc_press_sp_410_5

94.0

2

150

TRUE

/SucPr Alm 407C

Low Suction Press Sp 407C

mod_lo_suc_press_sp_407_5

50.0

2

120

TRUE

Mod Active Status SucPr Alm SP:

Module Low Suction Press Setpt mod_low_press_sp_5

15.0

FALSE

Mod SucPr Time Delay Before Alarm:

Module LO SUC PSI Delay

mod_lo_suc_psi_delay_5

30.0

0

999

TRUE

Mod Extra Low SucPr Alm SP:

Module LO-LO SUC PSI Setpoint mod_low_low_press_sp_5

0.0

-5

50

TRUE

Low Dis Pr Ctrl SP R134a

Low Head Press Sp 134a

mod_lo_disch_press_sp_134_5

100.0

20

350

TRUE

Low Dis Pr Ctrl SP R410a

Low Head Press Sp 410a

mod_lo_disch_press_sp_410_5

220.0

50

450

TRUE

Low Dis Pr Ctrl SP R407C

Low Head Press Sp 407

mod_lo_disch_press_sp_407_5

150.0

50

300

TRUE

Mod Active Status Low DisPr Alm SP:

Module Lo Disch Press Setpt

mod_lo_disch_press_sp_5

100.0

FALSE

M DisTp Alm SP

Module Hi Disch Temp

mod_hi_disch_tmp_5

225.0

100

325

TRUE

/M SucTp Alm SP

Module Low Suction Temp

mod_lo_suction_tmp_5

32.0

10

75

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

LO SUC SPRHT & LO DISCH SPRHT SETPTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Suc&Dis SuperHt Alrm Setpts
M Lo DisSuprHt

Module Low Disch SuperHt
Setpt

mod_lo_disc_supht_sp_5

15.0

TRUE

/M Lo SucSuprHt

Module Low Suct SuperHt Setpt mod_lo_suc_supht_sp_5

2.0

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

FREEZE TARGET SETPOINT
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Freeze Target Setpts Menu
Freeze TrgSp (F)

Module Freeze Target Setpoint mod_freeze_trg_sp_5

36.0

0

50

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

COMPR MIN MAX RUN TIMES
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Compressor Min & Max Run Times
Compr Minimum Run Time (sec)

Module Compr Min Run Time

mod_cmpr_min_run_5

120.0

1

999

TRUE

Compr Minimum Off Time (sec)

Module Compr Min Off Delay

mod_cmpr_off_delay_5

150.0

1

999

TRUE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

COMPR ALARM DELAY
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compr Alarm Delays
Mod Alm Delay

Module Compr Status Alarm
Delay

mod_comp_stat_alm_delay_5

9999.0

5

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MODULE WATER TEMP LIMITS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Module Water Out Temp Limits
Mod Evap Wat Out Lo Limit: (F)

Module Freeze Target Setpoint mod_freeze_trg_sp_5

36.0

0

165

TRUE

Mod Evap Wat Out Hi Limit: (F)

Module High Evaporator Leaving
Temp at Startup

mod_high_evap_lvg_tmp_5

90.0

0

165

TRUE

Mod Cond Wat Out Lo Limit: (F)

Module Low Condenser Leaving
Temp. Setpoint

mod_low_cond_lvg_sp_5

50.0

0

165

TRUE

Mod Cond Wat Out Hi Limit:
HI WTR OUT UGW

UCW Module High Cond Leaving
Temp at Startup

ugw_mod_cwr_trg_sp_5

118.0

10

165

TRUE

/HI WTR OUT UGH

UCH Module High Cond Leaving
Temp at Startup

ugh_mod_cwr_trg_sp_5

140.0

10

165

TRUE

Mod Cond Wat Out Hi Limit: (F)

Module Leaving Cond Water
Temp Setpoint

mod_cwr_trg_sp_5

118.0

10

165

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

SCREW COMP ALARM SETPOINTS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Screw Comp Alarm Setpoints
Screw Comp Max Amps Allowed 460:

Compressor Max Amps

mod_max_amps_sp_5

105.0

1

999

TRUE

Winding Temp Correlation to ohms:

Compr Max Winding Temp
Sensor Resis

mod_max_wind_sens_ohms_5

275.0

1

999

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

SERVICE MENU SETUP FN7

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Page 5 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET COMP VFD ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Compr VFD Alarms
M1 VFD in Alarm?

Module 1 Comp 1 VFD Fail

m1_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M1C1Reset Alm?

Mod 1 Reset VFD Fault

m1_reset_vfdfault_5

Off

No, Yes

TRUE

M2 VFD in Alarm?

Module 2 Comp 1 VFD Fail

m2_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M2C1Reset Alm?

Mod 2 Reset VFD Fault

m2_reset_vfdfault_5

Off

No, Yes

TRUE

M3 VFD in Alarm?

Module 3 Comp 1 VFD Fail

m3_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M3C1Reset Alm?

Mod 3 Reset VFD Fault

m3_reset_vfdfault_5

Off

No, Yes

TRUE

M4 VFD in Alarm?

Module 4 Comp 1 VFD Fail

m4_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M4C1Reset Alm?

Mod 4 Reset VFD Fault

m4_reset_vfdfault_5

Off

No, Yes

TRUE

M5 VFD in Alarm?

Module 5 Comp 1 VFD Fail

m5_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M5C1Reset Alm?

Mod 5 Reset VFD Fault

m5_reset_vfdfault_5

Off

No, Yes

TRUE

M6 VFD in Alarm?

Module 6 Comp 1 VFD Fail

m6_comp1_vfd_fail_5

Off

No, Yes

FALSE

/M6C1Reset Alm?

Mod 6 Reset VFD Fault

m6_reset_vfdfault_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET MODULE FREEZ & HOT ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Mod Freez &Hot Alarms
M1 inFreezAlm?

Module 1 Freeze Alarm

m1_freeze_alrm_5

No

No, Yes

FALSE

/M1 Frz-CWReset?

Reset Mot1 Vlv Fail

m1_reset_freeze_5

Off

No, Yes

TRUE

M1 in CWR Alm? (/)

Module 1 Leaving Cond Water
Alarm

m1_cwr_alrm_5

No

No, Yes

FALSE

M2 inFreezAlm?

Module 2 Freeze Alarm

m2_freeze_alrm_5

No

No, Yes

FALSE

/M2 Frz-CWReset?

Reset Mot2 Vlv Fail

m2_reset_freeze_5

Off

No, Yes

TRUE

M2 in CWR Alm? (/)

Module 2 Leaving Cond Water
Alarm

m2_cwr_alrm_5

No

No, Yes

FALSE

M3 inFreezAlm?

Module 3 Freeze Alarm

m3_freeze_alrm_5

No

No, Yes

FALSE

/M3 Frz-CWReset?

Reset Mot3 Vlv Fail

m3_reset_freeze_5

Off

No, Yes

TRUE

M3 in CWR Alm? (/)

Module 3 Leaving Cond Water
Alarm

m3_cwr_alrm_5

No

No, Yes

FALSE

M4 inFreezAlm?

Module 4 Freeze Alarm

m4_freeze_alrm_5

No

No, Yes

FALSE

/M4 Frz-CWReset?

Reset Mot4 Vlv Fail

m4_reset_freeze_5

Off

No, Yes

TRUE

M4 in CWR Alm? (/)

Module 4 Leaving Cond Water
Alarm

m4_cwr_alrm_5

No

No, Yes

FALSE

M5 inFreezAlm?

Module 5 Freeze Alarm

m5_freeze_alrm_5

No

No, Yes

FALSE

/M5 Frz-CWReset?

Reset Mot5 Vlv Fail

m5_reset_freeze_5

Off

No, Yes

TRUE

M5 in CWR Alm? (/)

Module 5 Leaving Cond Water
Alarm

m5_cwr_alrm_5

No

No, Yes

FALSE

M6 inFreezAlm?

Module 6 Freeze Alarm

m6_freeze_alrm_5

No

No, Yes

FALSE

/M6 Frz-CWReset?

Reset Mot6 Vlv Fail

m6_reset_freeze_5

Off

No, Yes

TRUE

M6 in CWR Alm? (/)

Module 6 Leaving Cond Water
Alarm

m6_cwr_alrm_5

No

No, Yes

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET COMP RUNTIME & CYCLES
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Reset Compr Runtime & Cycles Menu
M1C1Reset Runtm

M1C1 Runtime Reset

m1reset_c1_rtim_5

Off

No, Yes

TRUE

/M1C1Reset Cyc

M1C1 Cycles Reset

m1c1_cycles_reset_5

Off

No, Yes

TRUE

M2C1Reset Runtm

M2C1 Runtime Reset

m2reset_c1_rtim_5

Off

No, Yes

TRUE

/M2C1Reset Cyc

M2C1 Cycles Reset

m2c1_cycles_reset_5

Off

No, Yes

TRUE

M3C1Reset Runtm

M3C1 Runtime Reset

m3reset_c1_rtim_5

Off

No, Yes

TRUE

/M3C1Reset Cyc

M3C1 Cycles Reset

m3c1_cycles_reset_5

Off

No, Yes

TRUE

M4C1Reset Runtm

M4C1 Runtime Reset

m4reset_c1_rtim_5

Off

No, Yes

TRUE

/M4C1Reset Cyc

M4C1 Cycles Reset

m4c1_cycles_reset_5

Off

No, Yes

TRUE

M5C1Reset Runtm

M5C1 Runtime Reset

m5reset_c1_rtim_5

Off

No, Yes

TRUE

/M5C1Reset Cyc

M5C1 Cycles Reset

m5c1_cycles_reset_5

Off

No, Yes

TRUE

M6C1Reset Runtm

M6C1 Runtime Reset

m6reset_c1_rtim_5

Off

No, Yes

TRUE

/M6C1Reset Cyc

M6C1 Cycles Reset

m6c1_cycles_reset_5

Off

No, Yes

TRUE

LINK(S): PREV, SYSTEM SETUP, HOME

RESET MODULE SENSOR OOR ALARMS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Reset Module Sensor OOR Alms
M1C1 inOOR Alm?

Module 1 Comp 1 Sensor OOR

m1_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M1 OOR?

M1 Sensor OOR Reset

m1_oorsl_reset_5

Off

No, Yes

TRUE

M2C1 inOOR Alm?

Module 2 Comp 1 Sensor OOR

m2_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M2 OOR?

M2 Sensor OOR Reset

m2_oorsl_reset_5

Off

No, Yes

TRUE

M3C1 inOOR Alm?

Module 3 Comp 1 Sensor OOR

m3_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M3 OOR?

M3 Sensor OOR Reset

m3_oorsl_reset_5

Off

No, Yes

TRUE

M4C1 inOOR Alm?

Module 4 Comp 1 Sensor OOR

m4_comp1_oor_5

Off

No, Yes

FALSE

/ Reset M4 OOR?

M4 Sensor OOR Reset

m4_oorsl_reset_5

Off

No, Yes

TRUE

Advertising