Control access display table, Local access display table, System setup fn2 – ClimaCool UGW Manual User Manual

Page 31

Advertising
background image

29

www.climacoolcorp.com

Control Access Display Table

Page 2 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

/Unit Mode:

Unit Mode

unit_mode_1

Normal Run

Schedule,

NoFlo/Phas,
CHWR High,

CWS Low, Sens

Error,

NoModAvail,

Module Dwn,

Compr Dwn,
NonCritAlm,

Normal Run

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

EVAP STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Evap Water Temp & Pump Status
Evp H2O In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

/Evp WaterOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

Evap Flow Status:

Evap Flow SW

evap_flow_1

On

Off, On

FALSE

Ev Pmp#1 Status:

CHW Pump 1 S/S

chw_pump_1_ss_1

Off

Off, On

FALSE

/Ev Pmp#2 Status:

CHW Pump 2 S/S

chw_pump_2_ss_1

Off

Off, On

FALSE

Chil Water Diff Press Sensor: (PSID)

Diff Press Cool Load

diff_press_cool_load_1

8.48872 °F

FALSE

LINK(S): PREV, SYSTEM SETUP, STATUS

COND STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Cond Water Temp & Pump Status
Cnd H2O In : (F)

CWS In Temp Status

cws_stat_1

67.3 °F

FALSE

/Cnd H2O Out: (F)

CWR Out Status

cwr_stat_1

83.3

FALSE

Cond Flow Status:

Cond Flow SW

cond_flow_1

On

Off, On

FALSE

Cnd Pump#1 Stat:

CW Pump 1 S/S

cw_pump_1_ss_1

Off

Off, On

FALSE

/Cnd Pump#2 Stat:

CW Pump 2 S/S

cw_pump_2_ss_1

Off

Off, On

FALSE

Cond Water Diff Press Sensor: (PSID)

Diff Press Heat Load

diff_press_heat_load_1

8.053761 °F

FALSE

LINK(S): PREV, SYSTEM SETUP, STATUS

MOT VLV OPEN/CLOSE STATUS MENU
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Mot Valve Open/Close Status
Mod1 Mot Valve Open Status:

Module 1 Open

m1_open_5

On

Closed, Open

FALSE

Mod2 Mot Valve Open Status:

Module 2 Open

m2_open_5

On

Closed, Open

FALSE

Mod3 Mot Valve Open Status:

Module 1 Open

m1_open_5

On

Closed, Open

FALSE

Mod4 Mot Valve Open S

Module 4 Open

m4_open_5

Off

Closed, Open

FALSE

Mod5 Mot Valve Open Status:

Module 5 Open

m5_open_5

Off

Closed, Open

FALSE

Mod6 Mot Valve Open Status:

Module 6 Open

m6_open_5

Off

Closed, Open

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MOD X COMP1 DATA
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

M1C1 Suc Pr: (psi)
/ MODULE 1 COMP 1

Module 1 Comp 1 Suction
Pressure

m1_c1_suc_pres_stat_5

40.6

FALSE

Suc SuperHt: (F)

Module 1 Comp 1 Suction
Superheat

m1_c1_suc_superheat_5

8.044445

FALSE

/CH Water In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

M1C1 Suc Tp: (F)

Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5

53.6

FALSE

/CH WaterOut: (F)

M1 Evap Leaving Temp

m1_chws_temp_stat_5

51.7

FALSE

M1 VFD VoltIn:

M1 VFD Screw Input

m1vfd_screw_input_1

7.53594 V

0

999

FALSE

/MainTX PIDOUT:

Module 1 Comp 1 Main TXV PID
Out

m1c1_mntx_pid_5

4.1325912

0

999

FALSE

M1C1 Dis Pr: (psi)

Module 1 Comp 1 Disch Press

m1_c1_disch_pres_stat_5

99.3

0

350

FALSE

/M1C1 Dis Tp: (F)

Module 1 Comp 1 Disch Temp

m1_c1_disch_temp_stat_5

110.3

FALSE

M1C1 Status:
/CD Water In : (F)

Module 1 Comp 1 Status

m1_comp1_status_5

On

Off, On

FALSE

M1C1 Fail :
/CD Water Out: (F)

Module 1 Comp 1 Fail

m1_c1_fail_1

Off

Off, On

FALSE

M1C1 Runtime: (h)

Module 1 Comp 1 Runtime

m1_c1_rtime_1

2.3116667

FALSE

/M1C1 Cycles:

Module 1 Comp 1 Cycles

m1_c1_cycles_5

1.0

FALSE

M1C1 Min Runtm:

Module 1 Compr 1 Min Run

m1_c1_min_runtime_5

On

Off, On

FALSE

/M1C1 Min OffTime:

Module 1 Comp 1 Min Off

m1_c1_minimum_off_5

Off

Off, On

FALSE

cdmvPIDOut:

Module 1 Cond Vlv PID Out

m1_cdmv_pidout_5

0.0

0

999

FALSE

%/cdmvVDCScaleOut:

Module 1 Cond Vlv Scaled PID
Out

m1_cdmv_scaled_pidout_5

2.0

0

10

FALSE

CR3 Sol Stat:

Module 1 CR3 valve status

m1_cr3_valve_status_5

Off

Off, On

FALSE

/ CR4 Sol Stat:

Module 1 CR4 valve status

m1_cr4_valve_status_5

On

Off, On

FALSE

NOTE: CR3 is Unload, CR4 is Full Load.
Compressor Amps:

Module 1 Comp 1 Amps

m1c1_amps_stat_5

33.6

0

999

FALSE

Page 2 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

/Unit Mode:

Unit Mode

unit_mode_1

Normal Run

Schedule,

NoFlo/Phas,
CHWR High,

CWS Low, Sens

Error,

NoModAvail,

Module Dwn,

Compr Dwn,
NonCritAlm,

Normal Run

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

EVAP STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Evap Water Temp & Pump Status
Evp H2O In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

/Evp WaterOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

Evap Flow Status:

Evap Flow SW

evap_flow_1

On

Off, On

FALSE

Ev Pmp#1 Status:

CHW Pump 1 S/S

chw_pump_1_ss_1

Off

Off, On

FALSE

/Ev Pmp#2 Status:

CHW Pump 2 S/S

chw_pump_2_ss_1

Off

Off, On

FALSE

Chil Water Diff Press Sensor: (PSID)

Diff Press Cool Load

diff_press_cool_load_1

8.48872 °F

FALSE

LINK(S): PREV, SYSTEM SETUP, STATUS

COND STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Cond Water Temp & Pump Status
Cnd H2O In : (F)

CWS In Temp Status

cws_stat_1

67.3 °F

FALSE

/Cnd H2O Out: (F)

CWR Out Status

cwr_stat_1

83.3

FALSE

Cond Flow Status:

Cond Flow SW

cond_flow_1

On

Off, On

FALSE

Cnd Pump#1 Stat:

CW Pump 1 S/S

cw_pump_1_ss_1

Off

Off, On

FALSE

/Cnd Pump#2 Stat:

CW Pump 2 S/S

cw_pump_2_ss_1

Off

Off, On

FALSE

Cond Water Diff Press Sensor: (PSID)

Diff Press Heat Load

diff_press_heat_load_1

8.053761 °F

FALSE

LINK(S): PREV, SYSTEM SETUP, STATUS

MOT VLV OPEN/CLOSE STATUS MENU
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Module Mot Valve Open/Close Status
Mod1 Mot Valve Open Status:

Module 1 Open

m1_open_5

On

Closed, Open

FALSE

Mod2 Mot Valve Open Status:

Module 2 Open

m2_open_5

On

Closed, Open

FALSE

Mod3 Mot Valve Open Status:

Module 1 Open

m1_open_5

On

Closed, Open

FALSE

Mod4 Mot Valve Open S

Module 4 Open

m4_open_5

Off

Closed, Open

FALSE

Mod5 Mot Valve Open Status:

Module 5 Open

m5_open_5

Off

Closed, Open

FALSE

Mod6 Mot Valve Open Status:

Module 6 Open

m6_open_5

Off

Closed, Open

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

MOD X COMP1 DATA
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

M1C1 Suc Pr: (psi)
/ MODULE 1 COMP 1

Module 1 Comp 1 Suction
Pressure

m1_c1_suc_pres_stat_5

40.6

FALSE

Suc SuperHt: (F)

Module 1 Comp 1 Suction
Superheat

m1_c1_suc_superheat_5

8.044445

FALSE

/CH Water In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

M1C1 Suc Tp: (F)

Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5

53.6

FALSE

/CH WaterOut: (F)

M1 Evap Leaving Temp

m1_chws_temp_stat_5

51.7

FALSE

M1 VFD VoltIn:

M1 VFD Screw Input

m1vfd_screw_input_1

7.53594 V

0

999

FALSE

/MainTX PIDOUT:

Module 1 Comp 1 Main TXV PID
Out

m1c1_mntx_pid_5

4.1325912

0

999

FALSE

M1C1 Dis Pr: (psi)

Module 1 Comp 1 Disch Press

m1_c1_disch_pres_stat_5

99.3

0

350

FALSE

/M1C1 Dis Tp: (F)

Module 1 Comp 1 Disch Temp

m1_c1_disch_temp_stat_5

110.3

FALSE

M1C1 Status:
/CD Water In : (F)

Module 1 Comp 1 Status

m1_comp1_status_5

On

Off, On

FALSE

M1C1 Fail :
/CD Water Out: (F)

Module 1 Comp 1 Fail

m1_c1_fail_1

Off

Off, On

FALSE

M1C1 Runtime: (h)

Module 1 Comp 1 Runtime

m1_c1_rtime_1

2.3116667

FALSE

/M1C1 Cycles:

Module 1 Comp 1 Cycles

m1_c1_cycles_5

1.0

FALSE

M1C1 Min Runtm:

Module 1 Compr 1 Min Run

m1_c1_min_runtime_5

On

Off, On

FALSE

/M1C1 Min OffTime:

Module 1 Comp 1 Min Off

m1_c1_minimum_off_5

Off

Off, On

FALSE

cdmvPIDOut:

Module 1 Cond Vlv PID Out

m1_cdmv_pidout_5

0.0

0

999

FALSE

%/cdmvVDCScaleOut:

Module 1 Cond Vlv Scaled PID
Out

m1_cdmv_scaled_pidout_5

2.0

0

10

FALSE

CR3 Sol Stat:

Module 1 CR3 valve status

m1_cr3_valve_status_5

Off

Off, On

FALSE

/ CR4 Sol Stat:

Module 1 CR4 valve status

m1_cr4_valve_status_5

On

Off, On

FALSE

NOTE: CR3 is Unload, CR4 is Full Load.
Compressor Amps:

Module 1 Comp 1 Amps

m1c1_amps_stat_5

33.6

0

999

FALSE

Page 1 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

STANDBY
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

ClimaCool Corp. CoolLogic
Date:
Time:
CHWS Temp:

EVAP OUT TMP

chws_temp_1

50.1 °F

FALSE

F CWR Temp: (F)

COND OUT TMP

cwr_temp_1

83.3 °F

FALSE

press any key to continue

HOME
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

Chill Water In: (F)

CHWR In Temp Status

chwr_stat_1

54.4

FALSE

/Cool Spt: (F)

Active CHW Setpoint

chw_stp_stat_1

45.0 °F

FALSE

Chill WaterOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

/ Tot Stg Want:

Num of Comp Requested

comp_req_1

2.0

FALSE

Cond Water In : (F)

CWS In Temp Status

cws_stat_1

67.3 °F

FALSE

/ Tot Stg On:

Num of Comp ON

comp_on_1

2.0

FALSE

Cond Water Out: (F)
/ Mode :

Mode

mode_1

CLG

Cooling,

Heating

FALSE

Chil Water Flow :
/Heat Spt: (F)

Evap Flow SW

evap_flow_1

On

No, Yes

FALSE

Cond Water Flo:

Cond Flow SW

cond_flow_1

On

No, Yes

FALSE

/UnitMode:

Unit Mode

unit_mode_1

Normal Run

Schedule, No

Flo/Phas,

CHWR High,

CWS Low, Sens

Error, No

ModAvail,

Module Down,

Compr Down,

NonCrit Alm,

Normal Run

FALSE

LINK(S): STATUS, SYSTEM SETUP, SERVICE MENU SETUP, ALARM

STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Chiller Status Menu
LINK(S): ALL MODULE COMP UNLOAD STATUS,MODULE SIZE STATUS, CHILLER OPER STATUS,EVAP STATUS, COND STATUS,MOT VLV OPEN/CLOSE STATUS MENU,
MOD1 COMP1 DATA,MOD2 COMP1 DATA,MOD3 COMP1 DATA,MOD4 COMP1 DATA,MOD5 COMP1 DATA,MOD6 COMP1 DATA,ALL COMPR RUNTIME STATUS,
ALL COMPR CYCLES STATUS,ALL COMPR SS STATUS, ALL COMPR AMPERAGE STATUS,PREV, CLOCKSET, HOME, ALARM

MODULE SIZE STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

Module Size Status Only Legend
Mod1 Size:[
]/ 1= Not Used /4=80Ton Mod

Mod 1 Size

m1_size_st_1

4.0

1

4

FALSE

Mod2 Size:[
]/NOTE:DO NOT SELECT 2 OR 3

Mod 2 Size

m2_size_st_1

4.0

1

4

FALSE

Mod3 Size:[
]

Mod 3 Size

m3_size_st_1

4.0

1

4

FALSE

Mod4 Size:[
]

Mod 4 Size

m4_size_st_1

4.0

1

4

FALSE

Mod5 Size:[
]

Mod 5 Size

m5_size_st_1

1.0

1

4

FALSE

Mod6 Size:[
]

Mod 6 Size

m6_size_st_1

1.0

1

4

FALSE

LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET

CHILLER OPER STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Operating & Loading Status
PID1 Count:

Stage 1 Cooling PID

stg1_clg_pid_1

106.719604

FALSE

/Chil WaterOut: (F)

CHWS Out Temp Status

chws_stat_1

50.2

FALSE

Mod1 VFD Volt:

M1 VFD Screw Input

m1vfd_screw_input_1

7.53594 V

0

999

FALSE

/Mod2 VFD Volt:

M2 VFD Screw Input

m2vfd_screw_input_1

4.4 V

0

999

FALSE

Mod3 VFD Volt:

M3 VFD Screw Input

m3vfd_screw_input_1

0.0 °F

0

999

FALSE

/Mod4 VFD Volt:

M4 VFD Screw Input

m4vfd_screw_input_1

0.0 °F

0

999

FALSE

HPID1 Count:

Stage 1 Heating PID

stg1_htg_pid_1

0.0

FALSE

/Cond WaterOut: (F)

CWR Out Status

cwr_stat_1

83.3

FALSE

Cool Spt:

Active CHW Setpoint

chw_stp_stat_1

45.0 °F

FALSE

F / Heat Spt: (F)

Active Htg Setpoint

cw_stp_stat_1

125.0 °F

FALSE

Unit Stat:

Unit Status

unit_status_1

On

Unit OFF, Unit

ON

FALSE

LOCAL ACCESS DISPLAY TABLE

Page 3 of 15

10/9/2013

Product Line: UGW

Software Version: UGW-H.08B.13

Chiller Type: COOLING 4 PIPE

LOCAL ACCESS DISPLAY TABLE

LINK(S): PREV, STATUS, HOME, ALARM

ALL COMPR RUNTIME STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor Runtime Status
M1C1 Runtm: (h)

Module 1 Comp 1 Runtime

m1_c1_rtime_1

2.3116667

FALSE

/M4C1 Runtm: (h)

Module 4 Comp 1 Runtime

m4_c1_rtime_1

0.015833333

FALSE

M2C1 Runtm: (h)

Module 2 Comp 1 Runtime

m2_c1_rtime_1

3.02

FALSE

/M5C1 Runtm: (h)

Module 5 Comp 1 Runtime

m5_c1_rtime_1

0.0

FALSE

M3C1 Runtm: (h)

Module 3 Comp 1 Runtime

m3_c1_rtime_1

1.773889

FALSE

/M6C1 Runtm: (h)

Module 6 Comp 1 Runtime

m6_c1_rtime_1

0.0

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALL COMPR CYCLES STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor Cycles Status
M1C1 Cycles:

Module 1 Comp 1 Cycles

m1_c1_cycles_5

1.0

FALSE

/M4C1 Cycles:

Module 4 Comp 1 Cycles

m4_c1_cycles_5

0.0

FALSE

M2C1 Cycles:

Module 2 Comp 1 Cycles

m2_c1_cycles_5

1.0

FALSE

/M5C1 Cycles:

Module 5 Comp 1 Cycles

m5_c1_cycles_5

0.0

FALSE

M3C1 Cycles:

Module 3 Comp 1 Cycles

m3_c1_cycles_5

0.0

FALSE

/M6C1 Cycles:

Module 6 Comp 1 Cycles

m6_c1_cycles_5

0.0

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALL COMPR SS STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor ON/OFF Status
M1C1 Status:

Module 1 Comp 1 Status

m1_comp1_status_5

On

Off, On

FALSE

/ M4C1 Status:

Module 4 Comp 1 Status

m4_comp1_status_5

Off

Off, On

FALSE

M2C1 Status:

Module 2 Comp 1 Status

m2_comp1_status_5

On

Off, On

FALSE

/ M5C1 Status:

Module 5 Comp 1 Status

m5_comp1_status_5

Off

Off, On

FALSE

M3C1 Status:

Module 3 Comp 1 Status

m3_comp1_status_5

Off

Off, On

FALSE

/ M6C1 Status:

Module 6 Comp 1 Status

m6_comp1_status_5

Off

Off, On

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

ALL COMPR AMPERAGE STATUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Compressor Amperage Status
M1C1 Compr Amps:

Module 1 Comp 1 Amps

m1c1_amps_stat_5

33.6

FALSE

/M4C1 Compr Amps:

Module 4 Comp 1 Amps

m4c1_amps_stat_5

0.4

FALSE

M2C1 Compr Amps:

Module 2 Comp 1 Amps

m2c1_amps_stat_5

25.4

FALSE

/M5C1 Compr Amps:

Module 5 Comp 1 Amps

m5c1_amps_stat_5

0.0

FALSE

M3C1 Compr Amps:

Module 3 Comp 1 Amps

m3c1_amps_stat_5

0.4

FALSE

/M6C1 Compr Amps:

Module 6 Comp 1 Amps

m6c1_amps_stat_5

0.0

FALSE

LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

SYSTEM SETUP FN2

Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic System Setup FN2
LINK(S): GENERAL SYS SETTINGS,HEAT & COOL SETPOINT MENUS,EVAP PUMP SETUP,COND PUMP SETUP,LEAD COMPR ROTATION SETUP,ALARM LOCKOUT RESET,SCHEDULES,
PREV, STATUS, HOME, ALARM

GENERAL SYS SETTINGS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value

Editable

CoolLogic General System Settings FN4
Chiller Control Type

Control Type

control_type_1

Cool Control

Cool Cntrl,
Heat Cntrl,
Heat Rcvry

TRUE

Chiller Control Source

Control Source

control_source_1

Digital Input

Dig Input,
Keypad, BAS

TRUE

Enable Chiller from Keypad?

Unit Enable (keypad)

enable_keypad_1

On

Off, On

TRUE

Mod Ref Type

Module Compr Ref Type

mod_comp_ref_type_5

134a

22, 407C,
410a, 134a

TRUE

Chiller Model Type:

Chiller Model Type

chiller_model_type_5

UGW

UGW, UGH,
UGR

TRUE

Cool Design Delta Temp

FULL LD COOL DES TD

cool_design_dt_1

-10.0

-50

50

TRUE

Heat Design Delta Temp

FULL LD HEAT DES TD

heat_design_dt_1

10.0

-50

50

TRUE

Use High Amb Tmp Limit?

HI AMBIENT TMP LIM

hi_amb_tmp_lim_1

No

No, Yes

TRUE

Software Version: UGW-H.08b.13
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM

HEAT & COOL SETPOINT MENUS
Screen Display

Content

BACnet Object

Default

Min. Value

Max. Value Editable

CoolLogic Heat and Cool Setpoints

Advertising