IAI America PCON-CFA User Manual

Page 113

Advertising
background image

4. SCON-CA


107

(3) I/O signal assignments

(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”)

Signal type

Bit

Symbol

Description

Details

Target position

32-bit data

-

32-bit signed integer.
Specify the target position on the absolute coordinates.
The unit is 0.01 mm, while the specifiable range is -999999 to
999999.
(Example) To set +25.41 mm, specify “2541.”
If the entered value exceeds the range of soft limit parameters
(within 0.2 mm inside of the parameter values), the movement
will be limited to within the range of soft limits (within 0.2 mm
inside of the parameter values).
* If this data is entered using a hexadecimal, enter a negative

value as a 2’s complement.

4.6 (2)

Positioning band

32-bit data

-

32-bit integer.
The unit is 0.01 mm, while the specifiable range is 1 to 999999.
(Example) To set 25.40 mm, specify “2540.”
This register has one of two meanings depending on the
operation type:
[1] In the case of positioning operation, this register indicates

the allowable range from the target position within which
the positioning is deemed completed.

[2] In the case of push-motion operation, this register

indicates the push band. Use the control signal PUSH to
set whether to perform normal operation or push-motion
operation.

4.6 (2)

Speed 16-bit

data

-

16-bit integer.
Specify the speed at which to move the actuator.
The unit is 1.0 mm/sec or 0.1mm/sec, while the specifiable
range is 0 to 65535.
The change of unit is to be conducted in Parameter No. 159 FB
Half Direct Mode Speed Unit.
(Example) To set 254.0 mm/sec, specify “254.”
If a move command is issued by specifying a value exceeding
the maximum speed, an alarm will occur.

4.6 (2)

PLC output

Acceleration/

deceleration

16-bit data

-

16-bit integer.
Specify the acceleration/deceleration at which to move the
actuator. (The acceleration and deceleration become the same
value.)
The unit is 0.01 G, while the specifiable range is 1 to 300.
(Example) To set 0.30 G, specify “30.”
If a move command is issued by specifying “0” or a value
exceeding the maximum acceleration or maximum
deceleration, an alarm will occur.

4.6 (2)

Advertising
This manual is related to the following products: