3. SCON-CA/CF

A


49

(1) PLC address configuration (* n indicates the initial input/output address for each axis.)

Parameter

No. 84

ACON/PCON DI and

input register

PLC output address

ACON/PCON DO and

output register

PLC input address

Port number 0 to 15

n+0

Port number 0 to 15

n+0

n+1

Occupied area

n+1

n+2 n+2
n+3

Current position

n+3

n+4 n+4

4

Occupied area

n+5

Command current

n+5

(Note) The [occupied area] cannot be used for any other purpose.

Also pay attention to use of duplicate addresses.


(2) I/O signal assignments for each axis

An I/O signal of each axis consists of 6 words (12 bytes) of I/O addresses.

z Addresses controlled by port numbers are controlled by bit ON/OFF signals.

z The current position is a 2-word (32-bit) binary data (unit: 0.01 mm).

z The command current is a 2-word (32-bit) binary data (unit: 1 mA).












PLC output
address

(* n indicates the initial output address for each axis.)

1 word = 2 bytes = 16 bits

Controller
input port
number