IAI America PCON-CFA User Manual

Page 22

Advertising
background image

3. SCON-CA/CF

A


16

(3) Bus terminal processing

If the connector is to be connected to the network terminal node, connect the terminal resistor to the
PROFIBUS-DP communication connector as shown below or use a connector with terminal resistor.

z Example of connector with terminal resistor: SUBCON-PLUS-PROFIB/AX/SC (Phoenix Contact)

z Connecting the terminal resistor












(4) Operation mode selection (setting)

Set a desired operation mode using a parameter.
Set the mode selector switch on the front side of the controller to the MANU position, and then set parameter No.
84, “FMOD: Fieldbus operation mode” using the RC PC software (V6.00.05.00 or later). (Refer to 3.7,
“PROFIBUS-DP.”)

Set value

Operation mode

Number of

occupied bytes

0 (factory setting)

Remote I/O mode

2

1

Position/simple direct mode

8

2

Half direct mode

16

3

Full direct mode

32

4

Remote I/O mode 2

12

* If a greater value is entered, an excessive input error will occur.



(5) Node address setting (Refer to 3.7.)

Set the node address using a parameter.
Set parameter No. 85, “NADR: Fieldbus node address” using the RC PC software.(Refer to 3.7, “PROFIBUS-DP
Parameters.”)

Settable range: 0 to 125 (The parameter has been set to 1 at the factory.)

(Note 1) Pay attention to duplicate node address settings.
(Note 2) PROFIBUS-DP node addresses are set with the master station always having address 0. Accordingly,

addresses of slave stations can be set between 1 and 125.

Board-end female

connector

Network-end male connector
(from counter-insertion side)

Network
wiring