IAI America PCON-CFA User Manual

Page 133

Advertising
background image

4. SCON-CA


127

(6) Home return

(HOME) PLC output signal

Home return complete

(HEND) PLC input signal

Home return in progress (GHMS) PLC input signal

When the HOME signal is turned ON, the command will be processed at the leading (ON) edge of the signal and
home return operation will be performed automatically. The GHMS signal turns ON while the home return is in
progress.
When the home return is completed, the HEND signal turns ON while the GHMS signal turns OFF.
Turn the HOME signal OFF when the HEND signal turns ON. Once the HEND signal turns ON, it will not turn OFF
until the power is turned OFF or the HOME signal is input again.
Even after home return has been completed once, another home return can be performed by turning the HOME
signal ON.






















Caution: In the remote I/O mode, remote I/O mode 2 or position/simple direct mode, issuing a positioning

command to a given position immediately after the power has been turned on, before home
return is performed, will cause the actuator to automatically return home and then perform
positioning, provided that this is the first positioning command after the power on.
In the half direct mode or full direct mode, issuing a positioning command to a given position
immediately after the power has been turned on, before home return is performed, will generate
an alarm (error code 83: ALARM HOME ABS (absolute position move command when home
return is not yet completed) (operation-cancellation alarm)). Exercise caution.

Actuator operation

Mechanical end

Stopped at the home position

HOME

(PLC

oPCON)

GHMS

(PCON

oPLC)

HEND

(PCON

oPLC)

PEND

(PCON

oPLC)

MOVE

(PCON

oPLC)

Advertising