411UDAC Manual — P/N 51073:E 9/20/2013

Product Description

Controls and Indicators

1.4 Controls and Indicators

Front Panel Switch

Reset Switch - to reset 411UDAC circuits

Acknowledge/System Silence Switch
– press once to acknowledge alarm or trouble (silence local 411UDAC piezo sounder and

change all flashing LEDs to steady on)

– press a second time and hold for minimum of two seconds to perform a System Signal

Silence (silence Notification Appliance Circuit)

411UDAC Piezo Sounder

The 411UDAC piezo sounder is used to locally annunciate DACT alarms and troubles. DACT
troubles include input channel open circuit, NAC fault, phone line 1 or 2 voltage fault, phone
number 1 or 2 communication fault and total communication failure. Separate and distinct
sounds are provided for the following conditions:

alarm - steady On

trouble - 1 second On and 1 second Off

supervisory - ½ second On and ½ second Off

Front Panel Indicator

AC Power - green LED

Input Active - red LED

Communication Fail - yellow LED

System Trouble - yellow LED

Supervisory - yellow LED

Battery Trouble - yellow LED

Circuit Board Indicator

Earth Fault - yellow LED (indicates zero impedance between panel and earth ground)

Figure 1.2 411UDAC Controls and Indicators