Appendix a: programming sheets, A.1 digital communicator options program sheets, A.1: digital communicator options program sheets – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 66

Advertising
background image

66

411UDAC Manual — P/N 51073:E 9/20/2013

Appendix A: Programming Sheets

A.1 Digital Communicator Options Program Sheets

To enter Programming Mode, press the MODE key, 7764, and then the [ENTER/STORE] key.

00

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.

20

Primary Central Station Communication Format: Valid entries are 0 to 9 and A to F.

21

22

23

24

Primary Central Station Account Code: Valid entries are 0 to 9 and A to F.

25

26

27

28

Primary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).

29

Primary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.

50

Secondary Central Station Communication Format: Valid entries are 0 to 9 and A to F.

51

52

53

54

Secondary Central Station Account Code: Valid entries are 0 - 9 and A - F.

55

56

57

58

Secondary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).

59

Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.

60

AC Loss Reporting Delay. Enter '0' for no delay; '1' for 1 hours; '2' for 2 hours; '3' for 6 hours; '4' for 7 hours;

'5' for 8 hours; '6' for 9 hours; '7' for 10 hours; '8' for 11 hours; '9' for 12 hours; 'A' for 13 hours; 'B' for 14 hours; 'C' for
15 hours; 'D' for 16 hours; 'E' for 17 hours; 'F' for 18 hours.

61

Backup Reporting. Enter '0' to report to Secondary phone number as backup only; '1' to report to both Primary

and Secondary phone number for all reports/messages; '2' reports go to first available receiver.

62

Reserved for Future Use.

63

DACT Trouble Reminder. Enter '0' to disable; '1' to enable.

64

Operational Mode Selection. Enter '0' for stand-alone/communicator disabled; '1' for stand-alone/communi-

cator enabled; '2' for slave/communicator enabled; '3' for slave/communicator disabled. Default setting is '0'.

65

Input Channel 1 Function Selection. Enter '0' for fire alarm; '1' for pull station; '2' for normally open contact;

'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.

66

Input Channel 2 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel

trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi-
lenceable.

67

Input Channel 3 Function Selection. Enter '0' for fire alarm; '1' for pull station; '2' for normally open contact;

'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.

68

Input Channel 4 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel

trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi-
lenceable.

69

70

71

Input Channel 1 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.

Does not delay Input Channels programmed for fire functions.

72

73

74

Input Channel 2 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.

Does not delay Input Channels programmed for fire functions.

75

76

77

Input Channel 3 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.

Does not delay Input Channels programmed for fire functions.