Table 4.2 – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 56

Advertising
background image

56

411UDAC Manual — P/N 51073:E 9/20/2013

Central Station Communications

Note that for Expanded Reporting, the digital communicator automatically adds the digit corre-
sponding to the Channel/Input number, and the second digit corresponding to any system trouble
condition. Only the first digit shown in Table 3.3 and Table 3.6 is programmable.

Where:
SSS or SSSS

= Subscriber ID

FA

= Fire Alarm (1st digit)

FA2

= Fire Alarm (2nd digit)

Z

= Channel/Input Number

RFA

= Fire Alarm Restore (1st digit)

RFA2

= Fire Alarm Restore (2nd digit)

TZ

= Zone Trouble (1st digit)

TZ2

= Zone Trouble (2nd digit)

RTZ

= Zone Trouble Restore (1st digit)

RTZ2

= Zone Trouble Restore (2nd digit)

TS

= System Trouble (1st digit)

TS2

= System Trouble (2nd digit)

RTS

= System Trouble Restore (1st digit)

RTS2

= System Trouble Restore (2nd digit)

P

= AC Loss (1st digit)

P2

= AC Loss (2nd digit)

RP

= AC Loss Restore (1st digit)

RP2

= AC Loss Restore (2nd digit)

V

= Fire Supervisory Condition (1st digit)

V2

= Fire Supervisory Condition (2nd digit)

RV

= Fire Supervisory Condition Restore (1st digit)

RV2

= Fire Supervisory Condition Restore (2nd digit)

X

= Test Report (1st digit)

X2

= Test Report (2nd digit)

Y

= Trouble corresponding to the following:

1

= Not Used

2

= Not Used

3

= Not Used

4

= Telco Primary Line Fault

5

= Telco Secondary Line Fault

6

= Not Used

7

= Not Used

8

= Not Used

9

= Not Used

A

= Communication Failure Primary Number

B

= Communication Failure Secondary Number

C

= Not Used

D

= Not Used

E

= Not Used

F

= Not Used

UD

= Upload/Download (1st digit)

UD2

= Upload/Download (2nd digit)

Table 4.2 Format Selection Address Explanation

Advertising