Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 24

Advertising
background image

24

411UDAC Manual — P/N 51073:E 9/20/2013

Installation

Input Channels

CAUTION!

HIGH VOLTAGE

COMM. FAIL

BATT FAULT

SYSTEM

TROUBLE

SUPV.

AC PWR

ACTIVE

GND FAULT

B+ A+ B- A- A B

Slc Slc Slc Slc Shield

NO NC C

NO NC C

NC NO C

411UDAC

Note: The addressable monitor module input, which is
being used to monitor the 411UDAC Relay Output
programmed for DACT Trouble must be programmed as
'DACT Trouble' at the FACP. The 411UDAC must be
programmed as a Slave Communicator (programming
address 64 set to ‘2’)

Addressable FACP (must be UL-listed for Central Station Service and Remote Signaling Service)

411UDAC Relay 2 Output (DACT Trouble)

Channel 2/Zone 2

Channel 1/Zone 1

Channel 3/Zone 3
2.2K ELR Channel 4

2.2K

ELR

Monitor Circuit Input

SLC Loop

Trouble Relay

Alarm Relay

Supervisory Relay

UL listed
2.2K ELRs
P/N 27070

Program the 411UDAC as follows:
Channel 1 - Normally Open Contact Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory

92

00

ud

ls

c4

11

a.

wm

f

Monitor
Module*

ELR
supplied
with
Monitor
Module

*If the SLC device does not
match the one in this figure,
refer to the SLC manual
wiring conversion charts for
legacy and newer versions of
the modules.

Figure 2.6 Typical Addressable FACP Connection to 411UDAC