411UDAC Manual — P/N 51073:E 9/20/2013

Installation

Output Circuits

Relay Programming

The relays are programmable for activation on fire alarm, host panel trouble, fire supervisory, total
communication failure and DACT. Refer to “DACT Programming” on page 36. Addresses ‘85 -
88’ are used for programming relay functions and enable.

RELAY 1 RELAY 2

TB1

NO

NO

NC

NC

C

C

Figure 2.8 Programmable Relay

Note: Relay connections may be power-limited or nonpower-limited. However, connecting one type next to the
other type is not allowed. Both circuits must be either power-limited or nonpower-limited.

Relays automatically change to energized

condition when programmed for Trouble.

4

11

a

rel

e.

w

mf

Relay 1 - Shown Programmed for Alarm,
Supervisory, or any other function except
DACT Trouble and Host Panel Trouble
(relay contacts shown in de-energized
condition with power applied to 411UDAC)

Relay 2 - Shown Programmed for
DACT Trouble or Host Panel
Trouble (relay contacts shown in
energized condition with power
applied to 411UDAC)