Program Mode

Input Channel 1 Function Selection (65)

1

Factory default for Channel 1 is '0' for activation on fire alarm (4-wire smoke). Enter '1' for pull
station; '2' for normally open contact device; '3' for host panel trouble; '4' for fire supervisory; '5' for
fire supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.

Input Channel 2 Function Selection (66)

1

Factory default for Channel 2 is '1' for pull station. Enter '2' for normally open contact device; '3'
for host panel trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for water-
flow silenceable; '7' for waterflow nonsilenceable.
Note that '0' is not a valid entry.

Input Channel 3 Function Selection (67)

1

Factory default for Channel 3 is '0' for activation on fire alarm (4-wire smoke). Enter '1' for pull
station; '2' for normally open contact device; '3' for host panel trouble; '4' for fire supervisory; '5' for
fire supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.

Input Channel 4 Function Selection (68)

1

Factory default for Channel 4 is '1' for pull station. Enter '2' for normally open contact device; '3'
for host panel trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for water-
flow silenceable; '7' for waterflow nonsilenceable.
Note that '0' is not a valid entry.

Input Channel 1 Delay Timer (69 - 71)

2

The Delay Timer is used to delay digital communicator transmission to a Central Station when the
Input Channel is activated. Input Channel 1 Delay Timer is factory set to '000' seconds for no
delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for
fire alarm, pull station, host control panel trouble and fire supervisory, must not be delayed. A
delay, therefore, cannot be selected for inputs programmed for these fire applications.
If the input
is set for a waterflow function, the delay timer will also delay activation of the relay, piezo sounder
and LEDs.

Input Channel 2 Delay Timer (72 - 74)

2

The Delay Timer is used to delay digital communicator transmission to a Central Station when the
Input Channel is activated. Input Channel 2 Delay Timer is factory set to '000' seconds for no
delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for
fire alarm, pull station, host control panel trouble and fire supervisory, must not be delayed. A
delay, therefore, cannot be selected for inputs programmed for these fire applications.
If the input
is set for a waterflow function, the delay timer will also delay activation of the relay, piezo sounder
and LEDs.

Address 64 Setting

411UDAC Operational Mode

411UDAC Function

0

Stand-alone/Communicator Disabled

latching inputs/onboard communicator disabled

1

Stand-alone/Communicator Enabled

latching inputs/onboard communicator enabled

2

Slave/Communicator Enabled

non-latching inputs/onboard communicator enabled

3

Slave/Communicator Disabled

non-latching inputs/onboard communicator disabled

Table 3.7 411UDAC Operational Modes

1. Changing the input function will automatically change the corresponding Primary and

Secondary event codes to reflect the new input function. The Communication Format
should be programmed first, followed by the Input Channel Function. See “Events and
Default Event Codes” on page 79.

2. This timer does not delay LED or Output Relay activation and is not used for channels

programmed as AC Loss circuits.