411UDAC Manual — P/N 51073:E 9/20/2013

67

Digital Communicator Options Program Sheets

Programming Sheets

78

79

80

Input Channel 4 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.

Does not delay Input Channels programmed for fire functions.

81

Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.

82

Make/Break Ratio for Primary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.

83

Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.

84

Make/Break Ratio for Secondary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.

85

Output Relay #1 enable. Enter '1' to enable Relay #1; '0' to disable relay.

86

Output Relay #1 Function. Enter '0' for relay to activate on alarm; '1' host panel trouble; '2' DACT trouble; '3'

for latching fire supervisory; '4' for autoresettable fire supervisory; '7' (future use); '8' for total communication failure.

87

Output Relay #2 enable. Enter '1' to enable Relay #2; '0' to disable relay.

88

Output Relay #2 Function. Enter '0' for relay to activate on fire alarm; '1' host panel trouble; '2' for DACT

trouble; '3' for latching fire supervisory; '4' for autoresettable fire supervisory; '7' (future use); '8' total communication
failure.

89

Reserved for future use. Leave default setting of ‘0.’

90

Panel unlock. Enter ‘0’ for password unlock, ‘1’ for permanent unlock.

91

Alarm verification. Enter '0' for no verification; '1' for verification of all 4-wire smoke zones.

92

Silence inhibit. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC for one minute.

93

Autosilence. Enter '0' for no autosilence; '1' for 5 minute autosilence; '2' for 10 minutes; '3' for 15 minutes; '4'

for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.

94

Restoral method. Enter '0' for Typical restoral method; '1' for Conditional Restoral Method #1; '2' for Condi-

tional Restoral Method #2.

95

Coding, Notification Appliance Circuit. Enter ‘0’ for no coding (steady); ‘1’ for Temporal coding.

96

Trouble Call Limit - Dialer Runaway Prevention Feature. Enter a '0' to disable this feature; '1' to enable Trou-

ble Call Limit. Factory default is '0' for disabled.

97

98

99

100

Panel Identification Number.

101

102

103

104

105

106

107

108

109

110

111

112

113

114

115

116

117

118

119

120

Addresses 101 to 120 store the Service Terminal 1 Phone Number. Valid entries are 0 - 9 and A - E.

'F' designates the end of the phone number.

121

122

Ring Count on Primary Phone Line. Enter number of rings prior to panel answering call. Valid entries

are 00 to 25 (00 = no answer). Factory default is 03.

123

FAX/Answer Machine, Primary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.

124

125

126

127

128

129

130

131

132

133

134

135

136

137

138

139

140

141

142

143

Addresses 124 to 143 store the Service Terminal 2 Phone Number. Valid entries are 0-9 and A-E.

'F' designates the end of the phone number.

144

Upload/Download Backup Reporting. Enter '0' for Upload/Download reports to go to the Secondary Central

Station Phone Number on backup only; '1' for Upload/Download reports to always go to the Secondary; '2' for
Upload/Download reports to go to the first available Central Station phone number.