4 program mode, Program mode – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 34

Advertising
background image

34

411UDAC Manual — P/N 51073:E 9/20/2013

Modes of Operation

Program Mode

Enter the second hour digit (4 in this example) and press the [ENTER/STORE] key. The number
'4' will appear as the digit second from the left and the decimal point will move one position to the
right indicating that the third digit from the left is now ready for programming.

Enter the first minute digit (0 in this example) and press the [ENTER/STORE] key. The number
'0' will appear as the digit third from the left and the decimal point will move one position to the
right indicating that the fourth digit from the left is now ready for programming.

Enter the second minute digit (0 in this example) and press the [ENTER/STORE] key. The num-
ber '0' will appear as the digit fourth from the left. Following the entry of the fourth and final digit,
the operating mode will immediately switch to Normal Mode, indicating that programming of the
time is now completed.

To exit Real Time Clock Mode before completing clock programming, press the MODE key, fol-
lowed by the 4-digit code for an alternate mode and then the [ENTER/STORE] key. During Real
Time Clock Mode, if no key is pressed within 10 minutes, the 411UDAC will revert to Normal
Mode.

Note that upon power-up, the internal clock starts running at 00:01 midnight. It must be changed so
that the 411UDAC can accurately call in test signals to the Central Station. Upon power loss or on
entering Default Mode, the clock reverts to 00:01 midnight and must be reset.

3.4 Program Mode

All programming selections made during Program Mode are stored in nonvolatile memory. This
ensures that the 411UDAC will retain all entries made in Programming Mode even if power is
removed.

140.1

Digit to be programmed

1400.

Digit to be programmed

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION

AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to
specific values or not used at all as indicated below:

Program feature

or option

Permitted in

UL 864? (Y/N)

Possible settings

Settings permitted in

UL 864

AC Loss Delay

Y

AC Loss Delay = 0, 1, 2 (factory default), 6, 7, 8, 10, 11, 12, 13, 14,
15, 16, 17, or 18 hours
Refer to “AC Loss Reporting Delay (60)” on page 45.

AC Loss Delay =

1 or 2 hours

Input Channel 1-4

Delay Timer

Y

0 – 179 seconds
Refer to “Input Channel 1 Delay Timer (69 - 71)” on page 46

Delay timer =

0 - 90 seconds

Trouble Call Limit

N

Program Address 96 = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Program Address 96 = 1: limits call for each unique trouble to 10
within a 24 hour period
Refer to “Trouble Call Limit - Dialer Runaway Prevention (96)” on
page 50

Program Address

96 = 0 for unlimited

Central Station

trouble calls