Appendix d: events and default event codes – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 79

Advertising
background image

411UDAC Manual — P/N 51073:E 9/20/2013

79

Appendix D: Events and Default Event Codes

Note: The character ‘x’ in the following table refers to the input circuit number (1 - 4).

Group Definitions:

Format Group 1

4+2 Ademco Express Standard, DTMF

1400/2300 Hz ACK

4+1 Expanded 1800 Hz Carrier

2300 Hz ACK

4+1 Expanded 1900 Hz Carrier

1400 Hz ACK

4+2 Standard 1800 Hz Carrier

2300 Hz ACK

4+2 Expanded 1800 Hz Carrier

2300 Hz ACK

4+2 Standard 1900 Hz Carrier

1400 Hz ACK

4+2 Expanded 1900 Hz Carrier

1400 Hz ACK

Format Group 2

4+1 Ademco Express Standard, DTMF

1400/2300 Hz ACK

3+1 Expanded 1800 Hz Carrier

2300 Hz ACK

3+1 Expanded 1900 Hz Carrier

1400 Hz ACK

3+1 Standard 1800 Hz Carrier

2300 Hz ACK

3+1 Standard 1900 Hz Carrier

1400 Hz ACK

4+1 Standard 1800 Hz Carrier

2300 Hz ACK

4+1 Standard 1900 Hz Carrier

1400 Hz ACK

Note that although all Expanded Mode formats communicate two digits per event, only the first
digit is programmable. The second digit cannot be changed.

411UDAC Events

Format Group 1

Format Group 2

Ademco Contact ID

Input Circuit Functions

Active

Restore

Active

Restore

Active and

Restore

Sensor #

4-wire Smoke

1x

Ex

1

E

111

00x

Pull Station

1x

Ex

1

E

115

00x

Contact Closure

1x

Ex

1

E

110

00x

Host Control Panel Trouble

FF

Ex

F

E

373

00x

Latching Supervisory

8x

Ex

8

E

200

00x

Autoresettable Supervisory

8x

Ex

8

E

200

00x

Silenceable Waterflow

1x

Ex

1

E

113

00x

Nonsilenceable Waterflow

1x

Ex

1

E

113

00x

Other Events

Active

Restore

Active

Restore

Active and

Restore

Sensor #

Input Circuit Fault

Fx

Dx

F

D

380

00x

AC Fault

92

93

9

9

301

000

Earth Fault

61

A1

6

A

310

000

Low Battery Fault

62

A2

6

A

302

000

No Battery Fault

63

A3

6

A

311

000

Phone Line 1 Fault

64

A4

6

A

351

000

Phone Line 2 Fault

65

A5

6

A

352

000

NAC Fault

66

A6

6

A

321

000

Phone Number 1 Fault

6A

AA

6

A

354

001

Phone Number 2 Fault

6B

AB

6

A

354

002

System Off Normal Fault

6F

AF

6

A

308

000

Special Events

Active

Restore

Active

Restore

Active and

Restore

Sensor #

System Test Message

99

-

9

-

602

000

System Abnormal Test Message

91

-

F

-

608

000

Upload/Download Request

71

-

7

-

411

000

Upload Successful

72

-

7

-

416

000

Download Successful

73

-

7

-

412

000

Upload/Download Failed

74

-

7

-

412

000

Advertising