Secondary central station phone number (30 - 49) – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 40

Advertising
background image

40

411UDAC Manual — P/N 51073:E 9/20/2013

Modes of Operation

Program Mode

Primary Central Station Number Account Code (21 - 24)

The four locations at addresses 21 - 24 default to all '0's. Valid entries are 0 - 9 and A - F. The num-
ber of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 20,
enter three digits (one digit each in locations 21, 22 and 23 - location 24 is ignored). If program-
ming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 20, enter four digits (one each in locations 21, 22,
23 and 24).

Primary Central Station Number 24 Hour Test Time (25 - 28)

Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1
takes up four locations, from addresses 25 - 28. The default is 00:00 (12:00 midnight). The limits
for each location are as follows (do not use values of A - F as entries).

25: enter 0, 1 or 2
26: enter 0 - 9
27: enter 0 - 5
28: enter 0 - 9

Primary Central Station Number 24/12/8/6 Hour Test Time Interval (29)

The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times
are needed, enter 1 = 12 hour, 2 = 8 hour or 3 = 6 hour.

Secondary Central Station Phone Number (30 - 49)

Addresses 30 - 49 are factory set to 'F' (30_F to 49_F). Programming is typically done as follows:

If your phone number is 484-7161, press 4.

The display will read 30_4.

Press [ENTER/STORE] to save the entry to memory and increment to the next address
31_F.

171

Primary # Input Channel 4 Fault Restore Code

D

172

Primary # AC Voltage Fault Restore Code

9

173

Primary # Earth Fault Restore Code

A

174

Primary # Low Battery Fault Restore Code

A

175

Primary # No Battery Fault Restore Code

A

176

Primary # Phone Line 1 Voltage Fault Restore Code

A

177

Primary # Phone Line 2 Voltage Fault Restore Code

A

178

Primary # NAC Fault Restore Code

A

179

Primary # Charger Fault Restore Code

180

Primary # Phone Number 1 Communication Fault Restore Code

A

181

Primary # Phone Number 2 Communication Fault Restore Code

A

182

Primary # System Off Normal Restore Code

A

183

Primary # System Test Message

9

184

Primary # System Abnormal Test Message

F

*

185

Primary # Upload/Download Request Code

7

186

Primary # Upload Successful Code

7

187

Primary # Download Successful Code

7

188

Primary # Upload/Download Failed Code

7

* For Formats ‘B’ and ‘D’, this address is defaulted to ‘9’ instead of ‘F.’

Address

Description

Setting

Table 3.3 All 3+1, 4+1 and 4+2 Expanded Formats - Primary