411UDAC Manual — P/N 51073:E 9/20/2013

23

Input Channels

Installation

The channel/inputs may be programmed as shown below:

A maximum of five waterflow devices may be used on any circuit programmed as a waterflow zone
per NFPA 72.

It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull sta-
tions, etc.) on any zone. This is not recommended, however, since specific and detailed reports will
not be possible (particularly critical when using Contact ID format). For example, the report of
general fire alarm versus pull station fire alarm or smoke detector fire alarm could not be distin-
guished.

The factory default programming for each channel is as follows:

Channel 1 - fire alarm (4-wire smoke)

Channel 2 - pull station

Channel 3 - fire alarm (4-wire smoke)

Channel 4 - pull station

The following illustration shows Channel 1 connected to 4-wire smoke detectors, and UL-listed
power supervision relay; Channel 2 connected to manual pull stations; Channel 3 connected to
manual pull stations; and Channel 4 connected to waterflow devices. In this example, the factory
default programming for Channel 4 must be changed from pull station to waterflow device.

• 4-wire smoke detector (inputs 1 & 3 only)

• Supervisory

• Pull station

• Supervisory autoresettable

• Normally-open contact device

• Waterflow silenceable

• Host panel trouble

• Waterflow nonsilenceable

UL-listed
power
supervision
relay*

Manual Pull
Stations
(Class A)

Manual Pull
Stations
(Class B)

Waterflow
Devices
(Class B)

411UDAC Main Circuit Board

Zone 1/Channel 1

Zone 2/Channel 2

Zone 3/Channel 3

Zone 4/Channel 4

Figure 2.5 Wiring Initiating Device Circuits

411

ud

ai

n3

.w

m

f

4-Wire
Smoke
Detector

*Refer to the Device Compatibility
Document
for a list of compatible
relays.

Class B Initiating Device Circuits
(supervised and power-limited)
4.7 K

, ½ watt resistor P/N:71252