8 ul power-limited wiring requirements, Ul power-limited wiring requirements – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 29

Advertising
background image

411UDAC Manual — P/N 51073:E 9/20/2013

29

UL Power-limited Wiring Requirements

Installation

2.8 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” away from any nonpower-limited circuit
wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the
cabinet through different knockouts and/or conduits. A typical wiring diagram for the 411UDAC is
shown below.

CAUTION!

HIGH VOLTAGE

CAUTIO

N!

GND FAULT

Figure 2.11 Typical UL Power-limited Wiring Diagram

AC Power
Nonpower-limited

Nonpower-limited Circuits

Power-limited Circuits

41

1a

ul

pw

2.

w

m

f

Note: Relay connections may be power-limited or nonpower-
limited, provided that 0.25" spacing is maintained between
conductors of power-limited and nonpower-limited circuits.

Nonpower-limited Circuits