Event codes - setting entries – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 37

Advertising
background image

411UDAC Manual — P/N 51073:E 9/20/2013

37

Program Mode

Modes of Operation

9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use

Consult the Central Station for proper Format selection. For any Format chosen, all event codes
are automatically programmed by the 411UDAC. Refer to Table 3.1, “Ademco Contact ID Format
- Primary,” on page 37, T
able 3.2, “4+2 Standard and 4+2 Express Formats - Primary,” on
page 38 and T
able 3.3, “All 3+1, 4+1 and 4+2 Expanded Formats - Primary,” on page 39.

Event Codes - Setting Entries

The Format selected in address 20 will cause the 411UDAC to automatically program addresses
145 - 228 with the factory default settings. Any of the Event Code settings may be altered. Consult
your Central Station prior to altering the event code settings. An entry of all zeros for any event
code will cause the communicator to NOT transmit the report. Transmission of reports to either or
both Central Station phone numbers may be disabled.

Upon accessing the first event code address (address 145) shown in Table 3.2, the following may be
displayed on the Programmer 7-Segment Display, if the corresponding Format was selected in
address 20.

The first three locations on the left of the Programmer display represent the memory address 145 of
the Format previously selected in address 20. The last location 1 (farthest right) represents the con-
tents of memory address 145 (which is the first digit of the event code).

The following Tables list the data which is automatically programmed for each Format that can be
selected in address 20. The addresses shown in each Table contain the Setting data which is auto-
matically programmed by the 411UDAC. To change the value, key in the new digit and then press
the [ENTER/STORE] key to save the new value. Use the Up and Down Arrow keys to increment
to the next address or decrement to the previous address.

Ademco Contact ID Format Primary Central Station Event Codes

If 'E' is entered for address 20, the following data is automatically programmed for the Primary
Central Station phone number event codes. Enter '000' for the Setting to disable the report to the
Central Station. The Channel # is not programmable.

1451

(address) (data)

Address

Description

Setting

Channel/Input #

145 - 147

Primary # Input Channel 1 Active Event Code

111

001

148 - 150

Primary # Input Channel 2 Active Event Code

115

002

151 - 153

Primary # Input Channel 3 Active Event Code

111

003

154 - 156

Primary # Input Channel 4 Active Event Code

115

004

157 - 159

Primary # Input Channel 1 Fault Event Code

380

001

160 - 162

Primary # Input Channel 2 Fault Event Code

380

002

163 - 165

Primary # Input Channel 3 Fault Event Code

380

003

166 - 168

Primary # Input Channel 4 Fault Event Code

380

004

169 - 171

Primary # AC Voltage Fault Event Code

301

000

172 - 174

Primary # Earth Fault Event Code

310

000

Table 3.1 Ademco Contact ID Format - Primary

Advertising