411UDAC Manual — P/N 51073:E 9/20/2013

19

Mounting

Installation

7. Mount the backbox to the keyhole mounting bolts, install and tighten the remaining fastener.

Main Circuit Board Mounting
1. When the location is clean and free of construction dust or other contaminants, install the main

PC board by installing the four supplied standoffs on the four main circuit board mounting
studs located in the backbox. Refer to Figure 2.1 for locations.

2. Position the main circuit board’s four corner mounting holes over the four standoffs just

installed. Be certain to observe the proper ESD (Electro Static Discharge) precautions to
prevent damage to the static sensitive circuits. This includes, but is not limited to, use of a
wrist strap.

3. Secure the main circuit board to the standoffs with the four supplied screws and attached

washers.

4. Plug the transformer connector into the main circuit board connector J4. The connector is

keyed and can only be plugged-in one way. Refer to Figure 2.3 on page 21 and Figure 2.11 on
page 29
for transformer connector location and AC power connections.

Figure 2.1 Cabinet Dimensions and Knockout Locations

41

1u

d

ac

ca

b.

wmf

Ground Stud

Top

Right side

Mounting Keyholes

10.0” (25.4cm)

Main Circuit Board

Mounting Studs

Transformer

Mounting Studs

Left side

Mounting Holes

Bottom