411UDAC Manual — P/N 51073:E 9/20/2013

Installation

Optional Programmer

2.7 Optional Programmer

The Fire-Watch 411 Series DACT Programmer (Model PRO-411) is used to:

switch between the digital alarm communicator's five Modes of operation

set the digital alarm communicator's 24 hour internal clock in Real-Time Clock Mode

program the 411UDAC digital alarm communicator in Program Mode

test the status of input and output circuits (including telephone lines) in Troubleshoot Mode

return all digital alarm communicator programming to the factory default settings in Default
Mode

To use the PRO-411 Programmer:

1. Remove all power from the 411UDAC.
2. Unlock and open the 411UDAC door.
3. Connect the Programmer cable to connector J2 located in the lower right corner of the

411UDAC. Note that the key on the connector must align with the slot in the J2 connector.

4. Reapply power to the 411UDAC.
5. Operate the Programmer by pressing the MODE key. Enter the appropriate four digit code

and then press the [ENTER/STORE] key.

Note that it is not possible to switch from Normal Mode to any other mode if any of the four Chan-
nels is programmed for fire alarm or fire supervisory and is active, that is, in alarm (shorted).

CAUTION!

HIGH VOLTAGE

COMM. FAIL

BATT FAULT

SYSTEM

TROUBLE

SUPV.

AC PWR

ALARM

GND FAULT

Figure 2.10 Programmer Connection to 411UDAC

Cable attached
to Programmer

411UDAC

Programmer

J2 connector

41

1a-

pr

o2

.w

m

f

- +

NOTE: The Fire•Watch 411 Series DACT
Programmer must be removed when not in use.