Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 41

Advertising
background image

411UDAC Manual — P/N 51073:E 9/20/2013

41

Program Mode

Modes of Operation

Enter the remaining numbers in their respective addresses as shown below:

Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the
numeric digits as dialed numbers and the hexadecimal digits representing the following functions:

A = * on a Touch-Tone phone keypad

B = # on a Touch-Tone phone keypad

C = look for secondary dial tone for up to two seconds (then dial anyway)

D = three second pause

E = five second pause

F = end of phone number (Note: F must remain in all unused phone number addresses)

If the first digit of the Secondary Central Station Phone Number remains ‘F’ and the digital com-
municator is enabled for transmission to a Central Station, a secondary phone number fault will be
generated. The phone number must begin with a digit other than ‘F.’

Secondary Central Station Number Communication Format (50)

One location is needed to select the Communication Format to the secondary phone number.
Address 50 is used for this purpose. The factory default setting for this address is 'E', which is Con-
tact ID Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE].
Choose from the list of formats below:

0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use

The Format selected in address 50 will cause the 411UDAC to automatically program addresses
229 - 312 with the factory default settings. Any of the Event Code settings may be altered. Consult
your Central Station prior to altering the event code settings. An entry of all zeros for any event
code will cause the communicator to NOT transmit the report. Transmission of reports to either or
both Central Station phone numbers may be disabled.

Refer to “Central Station Communications” on page 54 for information on Format reporting.

4 8 4 7 1 6 1 F F F F F F F F F F F F F