Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 42

Advertising
background image

42

411UDAC Manual — P/N 51073:E 9/20/2013

Modes of Operation

Program Mode

Upon accessing the first event code address which is 229 (Table 3.5, “4+2 Standard and 4+2
Express Formats - Secondary,” on page 43), th
e following may be displayed on the Programmer’s
7-Segment Display, if the corresponding Format was selected in address 50.

The first three locations on the left of the Programmer’s display represent the memory address 229.
The last location 1 (farthest right) represents the contents of memory address 229 which is the first
digit of the event code.

The following Tables list the data which is automatically programmed for each Format that can be
selected in address 50. The addresses shown in each Table contain the event code Setting data
which is automatically programmed by the 411UDAC. To change the value, key in the new digits
and then press the [ENTER/STORE] key to save the new value. Use the Up and Down Arrow
keys to increment to the next address or decrement to the previous address.

Ademco Contact ID Format Secondary Central Station Event Codes

If ‘E’ is entered for address 50, the following data is automatically programmed for the Secondary
Central Station phone number event codes. Enter '000' for the Setting to disable the report to the
Central Station.

2291

(address) (data)

Address

Description

Setting

Channel/Input #

233 - 235

Secondary # Input Channel 1 Active Event Code

111

001

236 - 238

Secondary # Input Channel 2 Active Event Code

115

002

239 - 241

Secondary # Input Channel 3 Active Event Code

111

003

242 - 244

Secondary # Input Channel 4 Active Event Code

115

004

245 - 247

Secondary # Input Channel 1 Fault Event Code

380

001

248 - 250

Secondary # Input Channel 2 Fault Event Code

380

002

251 - 253

Secondary # Input Channel 3 Fault Event Code

380

003

254 - 256

Secondary # Input Channel 4 Fault Event Code

380

004

257 - 259

Secondary # AC Voltage Fault Event Code

301

000

260 - 262

Secondary # Earth Fault Event Code

310

000

263 - 265

Secondary # Low Battery Fault Event Code

302

000

266 - 268

Secondary # No Battery Fault Event Code

311

000

269 - 271

Secondary # Phone Line 1 Voltage Fault Event Code

351

000

272 - 274

Secondary # Phone Line 2 Voltage Fault Event Code

352

000

275 - 277

Secondary # NAC Fault Event Code

321

000

278 - 280

Secondary # Charger Fault Event Code

300

000

281 - 283

Secondary # Phone Number 1 Communication Fault Event Code

354

001

284 - 286

Secondary # Phone Number 2 Communication Fault Event Code

354

002

287 - 289

Secondary # System Off Normal Fault Event Code

308

000

290 - 292

Secondary # System Test Message

602

000

293 - 295

Secondary # System Abnormal Test Message

608

000

296 - 298

Secondary # Upload/Download Request Code

411

000

299 - 301

Secondary # Upload Successful Code

416

000

302 - 304

Secondary # Download Successful Code

412

000

305 - 307

Secondary # Upload/Download Failed Code

413

000

Table 3.4 Ademco Contact ID Format - Secondary