411UDAC Manual — P/N 51073:E 9/20/2013

Modes of Operation

Program Mode

The Programmer cable should not be removed from the 411UDAC unless the unit is in Normal
Mode. If the Programmer cable is removed while the 411UDAC is in a Mode other than Normal
Mode, the communicator will automatically revert to Normal Mode following a 10 minute time-out
period. Note that if the Programmer is in Troubleshoot Mode when the cable is removed, the
411UDAC will revert to Normal Mode following a 20 minute time-out period.

3.4.1 DACT Programming

Primary Central Station Phone Number (00 - 19)

The first twenty add8resses (00 - 19) are factory set to 'F' (00_F to 19_F). Programming is done as
follows:

If your phone number is 484-7161, press 4.

The display will read 00_4.

Press [ENTER/STORE] to save the entry to memory and increment to the next address
01_F.

Enter the remaining numbers in their respective addresses as shown below:

Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the
numeric digits as dialed numbers and the hexadecimal digits representing the following functions:

A = * on a Touch-Tone phone keypad

B = # on a Touch-Tone phone keypad

C = look for secondary dial tone for up to two seconds (then dial anyway)

D = three second pause

E = five second pause

F = end of phone number (Note: F must remain in all unused phone number addresses)

If the first digit of the Primary Central Station Phone Number remains ‘F’ and the digital communi-
cator is enabled for transmission to a Central Station, a primary phone number fault will be gener-
ated. The phone number must begin with a digit other than ‘F.’

New FCC regulations allow extra digits to the CIC (Carrier ID Code), to identify the long distance
carrier. The expanded phone number field of 20 digits facilitates this function. Simply enter the
digits required by the telephone company if desired.

Primary Central Station Number Communication Format (20)

One location is needed to select the Communication Format to the primary phone number. Address
20 is used for this purpose. The factory default setting for this address is 'E', which is Contact ID
Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE].
Choose from the list of formats below:

0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK

4 8 4 7 1 6 1 F F F F F F F F F F F F F