Section 6: battery calculations – Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 64

Advertising
background image

64

411UDAC Manual — P/N 51073:E 9/20/2013

Section 6: Battery Calculations

Use the Total Standby and Alarm Load Currents calculated in Tables 6.2, and 6.3, for the following
battery calculations.

1. Select a battery with an Amp Hour rating greater than that calculated in Table 6.1.

NFPA 72 for Central Station and Proprietary Protected Premises systems require 24 hours of
standby

2. Two 12 VDC, 7 Amp Hour batteries, wired in parallel, can be located in the backbox to

provide 14 Amp Hours of backup (refer to Figure 2.4 on page 22 for battery cable connections)

Standby Load

Current in amps

(from Table 6.2 )

[ ]

X

Required Standby Time in Hours

(24 or 60 Hours)

[ ]

=

__________

Alarm Load

Current in amps

(from Table 6.3 )

[ ]

X

Required Alarm Time in Hours

(i.e. 5 min. = 0.084 Hours)

[ ]

=

__________

Add Standby and Alarm Load for Required Ampere Hour Battery

__________

Multiplying by derating factor of 1.2

X1.2

Total Ampere Hour Battery

1

=

__________

Table 6.1 Battery Calculations