Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 105

5. Follow the instructions in the diagram below. At each stage, allow sufficient settling time

before moving on to the next stage. P.Pb is the Primary Proportional Band, Int.T is the
Integral Time Constant.

This method can also be used to tune PID loops. Set Derivative to approx. Ta / 4

Figure 61.

Manually Tuning

– PI Control

The controller is now tuned.

Fine-tuning may be required

to optimise the controllers’

response

Apply power to

the load

Does the

PV continuously

oscillate?

END

Note the time

interval T

a

START

Multiply

P.Pb

setting by 1.5

& Set

Int.T

= T

a

Are the

Oscillations

decaying to

zero?

Multiply

P.Pb

setting by 1.5

Note the period

of the decaying

oscillations (T

b

)

Multiply

P.Pb

setting by 1.5 &

Set

Int.T

Time

P

ro

c

es

s

V

a

riabl

e

T

b

Time

P

ro

c

es

s

V

a

riabl

e

T

a

Y

es

Y

es

No

No