Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 162

PID Set 4 - Overlap/Deadband

PID Set 4 - Overlap/Deadband For Loop 2

Dec

4461

20845 41690

RW

PID Set 4 overlap (+ve) or deadband (-ve) between primary &

secondary prop bands. In display units - limited to 20% of the

combined band width.

Hex

116D

516D

A2DA

PID Set 4 - On/Off Differential

PID Set 4 - On/Off Differential For Loop 2

Dec

4480

20864 41728

RW

The on-off control hysteresis (deadband) for PID Set 4.

1 to 300 display units, centred about the setpoint.

Hex

1180

5180

A300

PID Set 5 - Primary Prop Band

PID Set 5 Primary Proportional Band For Loop 2

Dec

4462

20846 41692

RW

Primary Proportional Band for Gain Set 5.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

116E

516E

A2DC

PID Set 5 - Secondary Prop Band

PID Set 5 Secondary Proportional Band For Loop 2

Dec

4463

20847 41694

RW

Secondary Proportional Band for Gain Set 5.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

116F

516F

A2DE

PID Set 5 - Integral Time

PID Set 5 - Integral Time For Loop 2

Dec

4464

20848 41696

RW

Gain Set 5 integral time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

1170

5170

A2E0

PID Set 5 - Derivative Time

PID Set 5 - Derivative Time For Loop 2

Dec

4465

20849 41698

RW

Gain Set 5 derivative time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

1171

5171

A2E2

PID Set 5 - Overlap/Deadband

PID Set 5 - Overlap/Deadband For Loop 2

Dec

4466

20850 41700

RW

PID Set 5 overlap (+ve) or deadband (-ve) between primary &

secondary prop bands. In display units - limited to 20% of the

combined band width.

Hex

1172

5172

A2E4

PID Set 5 - On/Off Differential

PID Set 5 - On/Off Differential For Loop 2

Dec

4481

20865 41730

RW

The on-off control hysteresis (deadband) for PID Set 5.

1 to 300 display units, centred about the setpoint.

Hex

1181

5181

A302

Loop 2 Gain Set 2 Breakpoint

Gain Scheduling PID Set 1 To 2 Switch Point

Dec

4469

20853 41706

RW

Value (SP or PV) gain scheduling switches from PID Set 1 to 2.

Value between Scaled Input 2 Lower & Upper Limits

Hex

1175

5175

A2EA

Loop 2 Gain Set 3 Breakpoint

Gain Scheduling PID Set 2 To 3 Switch Point

Dec

4470

20854 41708

RW

Value (SP or PV) gain scheduling switches from PID Set 2 to 3.

Value between Set 2 Breakpoint & Scaled Input 2 Upper Limit.

Hex

1176

5176

A2EC

Loop 2 Gain Set 4 Breakpoint

Gain Scheduling PID Set 3 To 4 Switch Point

Dec

4471

20855 41710

RW

Value (SP or PV) gain scheduling switches from PID Set 3 to 4.

Value between Set 3 Breakpoint & Scaled Input 2 Upper Limit.

Hex

1177

5177

A2EE

Loop 2 Gain Set 5 Breakpoint

Gain Scheduling PID Set 4 To 5 Switch Point

Dec

4472

20856 41712

RW

Value (SP or PV) gain scheduling switches from PID Set 4 to 5.

Value between Set 4 Breakpoint & Scaled Input 2 Upper Limit.

Hex

1178

5178

A2F0

Slave Setpoint Scale Minimum

0% Master Power Demand to Slave Setpoint Scaling

Dec

4485

20869 41738

RW

The effective cascade slave setpoint value equating to 0% power

demand from the master loop.

Hex

1185

5185

A30A

Slave Setpoint Scale Maximum

100% Master Power Demand to Slave Setpoint Scaling

Dec

4486

20870 41740

RW

The effective cascade slave setpoint value equating to 100%

power demand from the master loop.

Hex

1186

5186

A30C

Slave Setpoint

Slave Setpoint Value for Cascade Control

Dec

4492

20876 41752

RW

The slave setpoint valve when in Cascade Control Mode.

Only write to this parameter if the unit is cascade status is OPEN

(e.g. when tuning slave).

Hex 118C

518C

A318