Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 196

Command Response Name

Response

Description

Low

Byte

High
Byte

Profile Number

A/R

A/R

The number of the profile created or edited

Segments Remaining

A/R

A/R

The number of unused segments remaining

Command Successfully

0x4F

0x4B

The command requested was executed without error

Command Not Recognized

0xFF

0xFF

The command is not recognized

Profile Number Invalid

0xF0

0x00

The profile number specified is not available.

Profile Name Invalid

0xF0

0x01

The profile name/characters are not valid

Start Signal Invalid

0xF0

0x02

The start signal is not recognized

Start Time Invalid

0xF0

0x03

The specified time is not within range

Start Day Invalid

0xF0

0x04

The specified day is not recognized

Starting Setpoint Invalid

0xF0

0x05

The specified starting setpoint is not recognized

Profile Recovery Invalid

0xF0

0x06

The profile recovery is not recognized

Recovery Time Invalid

0xF0

0x07

The recovery time is not within limits

Abort Action Invalid

0xF0

0x08

The abort action is not recognized

Profile Cycles Invalid

0xF0

0x09

The number of profile cycles is not within limits

Segment Number Invalid

0xF0

0x0A

The segment number is not valid for this profile

Segment Type Invalid

0xF0

0x0B

The segment type is not recognized

Segment Info A Invalid

0xF0

0x0C

Segment information A not valid for the type defined

Segment Info B Invalid

0xF0

0x0D

Segment information B is not valid for the type defined

Loop 1 Auto Hold Type Invalid

0xF0

0x0E

The auto hold type is not recognized

Loop 1 Auto Hold Value Invalid

0xF0

0x16

The auto hold value is not within input span

Events Value Invalid

0xF0

0x10

The events are not within range

No Segments Remaining

0xF0

0x11

There are no more segments available

Write Length Invalid

0xF0

0x12

The number of parameters to be written are invalid for
the function requested

Segment Setpoint Clamped

0xF0

0x13

The setpoint value entered was out of bounds. It has
been clamped within the units setpoint limits.

Segment Not Written

0xF0

0x14

The segment has not been written

Profiler Running

0xF0

0x15

The profiler is currently running so cannot be edited

Loop 2 Auto Hold Value Invalid

0xF0

0x17

The auto hold type is not recognized

Invalid number of loops

0xF0

0x18

The number of loops is not recognised

Loop 2 Auto Hold Type Invalid

0xF0

0x19

The auto hold type is not recognized

Read a Profile Header Request & Response Sequence

Read A Profile Header - Request (to instrument)

Field Name

Data

Comments

Dec

Hex

Unit Address

A/R

A/R

The ID address of the instrument

Function Code

23

17

Requires the multi read/write function

Read Start Address High Byte

32

20

Read Start Address Low Byte

6

6