Loop-back segments, Profile running / holding vs. hold segments – West Control Solutions Pro-EC44 User Manual

Page 97

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 90

Loop-back Segments

A Loop-back segment goes back to a specified segment in the current profile. This action is
repeated for the required number of times (1 to 9999) before the profile continues onwards.
More than one Loop Segment can be used in a profile, but they cannot cross.

Loop-back target segment

End

Loop Segment

Figure 50.

Loop-back Segments

Profile Running / Holding vs. Hold Segments

Hold Start

Run

Continue
Triggers

End

Hold Stop

Hold Segments

Figure 51.

Run/Hold & Hold Segments

A Hold condition during a segment maintains the current profile setpoint value(s). Once the
hold condition is stopped the Ramp or Dwell continues. The user can request that the profile
holds, or it can be instigated automatically.

Note: A running segment will hold if the operator or a digital input instructs it to. It
can also hold due to

“auto-hold”, if one of the profile control loops is disabled, if a

cascade is set to “open” or if manual control is selected.

A Hold Segment is a pre-planned hold programmed into the profile. It maintains the value of
the previous segment and the profile does not continue until a Continue Trigger occurs.
This can be via a key-press, serial communications, a digital input signal or after waiting until
a pre-set time of day (time of day is available with the recorder option only).

x 500

Example:
Runs segments 1 to 5, then
repeats segments 3 to 5
again 500 times, before
continuing on to segments 7
to 9,

Advertising