West Control Solutions Pro-EC44 User Manual

Page 72

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 65

P

rof

il

e Seg

ment

D

etai

ls

Profile Segments: Settings that apply to individual profile segments
Segment
Number

Shows the number of the profile segment being created. The maximum

number of profiles across all profiles is 255.

Segment Type

Set the segment type from: Ramp Time (time to reach target SP); Ramp

Rate (rate of change towards target SP

Single loop profiles only); Step

(jump to target SP), Dwell (keep current SP); Hold (hold profile until
released); Loop (back to previous segment); Join (to another profile); End
or Repeat Sequence Then End (repeat a sequence of joined profiles).

Note: Segment Ramp Rate is not available if the profile controls two
loops. A Join, End or Repeat Sequence Then End isthe last segment in
the profile. Repeat Sequence Then End is always the last profile in a
sequence.

Loop 1 Target
Setpoint.

The setpoint value to be reached control loop 1 by the end of this segment,

if the type is Ramp Time, Ramp Rate or Step.

Loop 2 Target
Setpoint.

If the profile is controlling 2 loops, this is the setpoint value to be reached

control loop 2 by the end of the segment, if the type is Ramp Time or Step.

Segment
Ramp Time

The time (hh:mm:ss) to reach the segment target setpoint if the segment

type is Ramp Time.

Segment
Ramp Rate

The rate of change towards the Segment Target Setpoint if segment type is

Ramp Rate. The rate can be from 0.001 to 9999.9 display units per hour.

Segment
Dwell Time

The time (hh:mm:ss) to maintain the current setpoint if the segment type is

Dwell.

Number of
Loops

If the segment type is Loop, enter the number of times to repeat the loop

back, before continuing forward to the next segment.

Back to
Segment
Number

If the segment type is Loop, enter the segment to loop back to.

Note: Two Loop-backs cannot be set to cross each other.

Loop 1 Auto-
Hold Type

The auto-hold type for this segment to ensure loop 1 tracks the setpoint.

From: None (no auto-hold); Above Setpoint (hold if too high only); Below
Setpoint (hold if too low only) or Band (hold if too high or low).

Loop 1 Auto-
Hold Band
Value

The distance loop 1 can be from setpoint. Beyond this the profile is held for

the selected Auto-Hold Type.

Note: For Two-Loop Profiles, either loop can cause the profile to hold.
The profile continues only when both loops are within their Auto-Hold
Bands.

Loop 2 Auto-
Hold Type

The auto-hold type for this segment to ensure loop 2 tracks the setpoint.

From: None (no auto-hold); Above Setpoint (hold if too high only); Below
Setpoint (hold if too low only) or Band (hold if too high or low).

Loop 2 Auto-
Hold Band
Value

The distance loop 2 can be from setpoint. Beyond this the profile is held for

the selected Auto-Hold Type.

Note: For Two-Loop Profiles, either loop can cause the profile to hold.
The profile continues only when both loops are within their Auto-Hold
Bands.

Segment Hold
Release Type

A hold segment can either be released by an Operator/Digital input or be

set to wait until a specified Time of Day - Recorder version only.

Hold Release
Time

The time of day (hh:mm:ss) when a Hold Segment will release if the

Release Type is Time Of Day. The profile is held by the hold segment and
only released at the next occurrence of the time of day set.

Times To
Repeat
Sequence

The number of times the entire sequence of profiles should run. – if the last

segment is Repeat Sequence Then End.

Segment End
Type

The action taken after the profile ends normally. From: Control Outputs Off;

Maintain Last Profile Setpoint or Use Controller Setpoint.

Select Profile
To Join

Choose a profile to join to from the list provided – if the final segment type is

Join. The selected profile will start immediately the current profile ends.

Advertising