Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 169

Alarm 5 Alternate Label

Alternate Language Name For Alarm 5 In Status Screen

Dec

6216

22600 45200

RW

8 ASCII characters replacing the title "Alarm 5" in alarm status

screens when the alternate language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1848

5848

B090

Alarm 5 Minimum Duration

Alarm 5 Minimum Duration

Dec

6217

22601 45202

RW

Minimum time alarm 5 must be passed its threshold before

activating (deactivation is not affected by this parameter).

From 0 to 9999 secs

Hex

1849

5849

B092

Alarm 6 Input Source

Value

Source

Dec

6223

22607 45214

RW

0

Input 1

Hex

184F

584F

B09E

1

Input 2

2

Aux A Input

3

Control Loop 1 Primary Power

4

Control Loop 1 Secondary Power

5

Control Loop 2 Primary Power

6

Control Loop 2 Secondary Power

7

Loop 1

8

Loop 2

Alarm 5 Type

Value

Alarm 5 Type

Dec

6224

22608 45216

RW

0

Unused

Hex

1850

5850

B0A0

1

Process High Alarm

2

Process Low Alarm

3

Deviation Alarm (SP-PV)

4

Band Alarm

5

Input Rate of Change

6

Input/Sensor Break Alarm

7

Loop Alarm

10

% memory used

11

High Power Alarm

12

Low Power Alarm

Alarm 6 Value

Value At Which Alarm 6 Activates

Dec

6225

22609 45218

RW

Limited by input scaling for alarm types 1 to 4.

Not used for alarms 5, 6 or 7.

0 to 100% for alarms 10 to 12.

Hex

1851

5851

B0A2

Alarm 6 Rate of Change Value

Process Variable Rate of Change Alarm Threshold

Dec

6230

22614 45228

RW

Value for Rate of Change Alarm. Alarm 6 activates when PV

change exceeds this level. From 0.0 to 99999

Hex

1856

5856

B0AC

Alarm 6 Hysteresis

Alarm 6 Hysteresis Value

Dec

6226

22610 45220

RW

Deadband value (on “safe” side of alarm), through which signal

must pass before Alarm 6 deactivates.

Limited by the input scaling span

Hex

1852

5852

B0A4

Alarm 6 Inhibit Enable/disable

Value

Alarm 6 Power-up/Setpoint Change Inhibit

Dec

6227

22611 45222

RW

0

Disabled

Hex

1853

5853

B0A6

1

Enabled

Alarm 6 Status

Value

Alarm 6 Status

Dec

6228

22612 45224

RO

0

Inactive

Hex

1854

5854

B0A8

1

Active