Connection from pc to bottom configuration socket – West Control Solutions Pro-EC44 User Manual

Page 244

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 237

A communications settings screen is shown whenever the user attempts to connect to the
instrument from the software. If the settings are not in-line with the information below, the
software may not be able to communicate with the instrument.

Connection from PC to Bottom Configuration Socket

When using the built-in configuration socket, set the communications parameters as shown
here and in the following table.

Device connector = Configuration Socket

PC connector = the PC Serial Com port number you are connected to

Start and Stop bits = 1

Data bits = 8.

Parity, Bit Rate & Address = must match settings in the table below

Con

nec

tion

fro

m

PC

to Rear RS485 Communications Option

When using the optional RS485 communications, set the parameters as shown here.

Device connector = Bus

PC connector = the PC Serial Com port number you are connected to

Start and Stop bits = 1

Data bits = 8

Parity, Bit Rate & Address = must match the settings in the instruments own

Communication Configuration menu.

Note: When uploading or downloading via the bottom mounted configuration
port, the required software communication settings depend on the module fitted
in slot A. See the table below.

Slot A Module Bit Rate

Parity

Address

Slot A Empty

19200

None

1

Digital Input

19200

None

1

Ethernet
Comms

9600

None

1

Auxiliary Input

4800

None

1

RS485
Comms

Must match the Communication
Configuration menu settings.