Plug-in module slot a parameters – West Control Solutions Pro-EC44 User Manual

Page 142

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 135

Soft Digital 4 AND Digital Inputs

Bit

If Bit value = 1 Input n Is Included in AND Selection

Dec

10047

26431 52862

RW

0

Digital Input A

Hex

273F

673F

CE7E

1

Digital Input C1

2

Digital Input C2

3

Digital Input C3

4

Digital Input C4

5

Digital Input C5

6

Digital Input C6

7

Digital Input C7

8

Digital Input C8

Soft Digital 4 OR Alarms

Bit

If Bit value = 1 Alarm n Is Included in OR Selection

Dec

10056

26440 52880

RW

0

Alarm 1

Hex

2748

6748

CE90

1

Alarm 2

2

Alarm 3

3

Alarm 4

4

Alarm 5

5

Alarm 6

6

Alarm 7

Soft Digital 4 OR Events

Bit

If Bit value = 1 Event n Is Included in OR Selection

Dec

10057

26441 52882

RW

0

Event 1

Hex

2749

6749

CE92

1

Event 2

2

Event 3

3

Event 4

4

Event 5

5

Profile Running

6

Profile End

Plug-in Module Slot A Parameters

Parameter Name & Register Address

Integer Int +1

Float

Access

Values

& Descriptions

Digital Input A Status

Value

Digital Input A Status

Dec

2115

18499 36998

RO

0

Inactive

Hex

0843

4843

9086

1

Active

Option Slot A Module Type

Value

Module Fitted In Slot A

Dec

2116

18500 37000

RO

0

None Fitted

Hex

0844

4844

9088

1

RS485 Communications

3

Digital Input A

4

Auxiliary Input A

5

Ethernet Communications

255

Error (unrecognised module)

RS485 Address

Value

RS485 Communications Address

Dec

2117

18501 37002

RW

0

Modbus Master mode

Hex

0845

4845

908A

1 to 255 Modbus Slave Address

Advertising