Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 118

Input 1 Scale Point 15

Multi-Point Scaling Point 15

Dec

1082

17466 34932

RW

Percentage of the scaled input where multi-point scaling value

15 is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

043A

443A

8874

Input 1 Display Point 15

Multi-Point Scaling Display Value For Point 15

Dec

1083

17467 34934

RW

Value to display at multi-point scaling point 15

Valid between the scaled input lower & upper limits

Hex

043B

443B

8876

User Calibration Type

Value

Calibration Type

Dec

1085

17469 34938

RW

0

None (input 1 base calibration used)

Hex

043D

443D

887A

1

Single Point Calibration

2

Two Point Calibration

User Calibration Point - Low Value

Two Point Calibration Low Point

Dec

1086

17470 34940

RW

The input value at which the Low Offset will be applied

Valid between input 1 scaled input lower & upper limits

Hex

043E

443E

887C

User Calibration Low Offset

Two Point Calibration Low Offset Value

Dec

1087

17471 34942

RW

The Low Offset value applied to the reading at the Low

Calibration Point

0.0 to 100.0%

Hex

043F

443F

887E

User Calibration Point - High Value

Two Point Calibration High Point

Dec

1088

17472 34944

RW

The input value at which the High Offset will be applied

Valid between input 1 scaled input lower & upper limits

Hex

0440

4440

8880

User Calibration High Offset

Two Point Calibration High Offset Value

Dec

1089

17473 34946

RW

The High Offset value applied to the reading at the High

Calibration Point

0.0 to 100.0%

Hex

0441

4441

8882

Universal Process Input 2 Parameters

Parameter Name & Register Address

Integer Int +1

Float

Access

Values

& Descriptions

Universal Input 2 Usage

Value

Process Input Type

Dec

1166

17550 35100

RW

0

Standard

Hex

048E

448E

891C

1

Feedback signal for Input 1

2

Redundant Sensor (backup for Input 1 Thermocouple
or RTD)

3

Not Used (or Indication only)

Universal Process Input 2 Type

Value

Process Input Type

Dec

1100

17484 34968

RW

0

B Type Thermocouple

Hex

044C

444C

8898

2

C Type Thermocouple

4

D Type Thermocouple

6

E Type Thermocouple

8

J Type Thermocouple

10

K Type Thermocouple

12

L Type Thermocouple

14

N Type Thermocouple

16

R Type Thermocouple

18

S Type Thermocouple

20

T Type Thermocouple

22

PtRh 20%: 40% Thermocouple

24

PT100 RTD