West Control Solutions Pro-EC44 User Manual

Page 145

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 138

5

Loop 2 Primary Output Power

6

Loop 2 Secondary Output Power

7

Loop 2 VMD Open

8

Loop 2 VMD Close

9

OR Alarm Event Direct

10

OR Alarm Event Reverse

11

AND Alarm Event Direct

12

AND Alarm Event Reverse

Output 1 OR Alarm Selection

Bit

If Bit = 1, Alarm n Is Included in OR Selection

Dec

10107

26491 52982

RW

2

Alarm 1

Hex

277B

677B

CEF6

3

Alarm 2

4

Alarm 3

5

Alarm 4

6

Alarm 5

7

Alarm 6

8

Alarm 7

Output 1 OR Event Selection

Bit

If Bit = 1, Event n Is Included in OR Selection

Dec

10108

26492 52984

RW

2

Event 1

Hex

277C

677C

CEF8

3

Event 2

4

Event 3

5

Event 4

6

Event 5

7

Profile Running

8

Profile End

Output 1 AND Alarm Selection

Bit

If Bit = 1, Alarm n Is Included in AND Selection

Dec

10109

26493 52986

RW

2

Alarm 1

Hex

277D

677D

CEFA

3

Alarm 2

4

Alarm 3

5

Alarm 4

6

Alarm 5

7

Alarm 6

8

Alarm 7

Output 1 AND Event Selection

Bit

If Bit = 1, Event n Is Included in AND Selection

Dec

10110

26494 52988

RW

2

Event 1

Hex

277E

677E

CEFC

3

Event 2

4

Event 3

5

Event 4

6

Event 5

7

Profile Running

8

Profile End

Output 1 Retransmit Input 1 Minimum

Value For Loop 1 Retransmit Minimum

Dec

2152

18536 37072

RW

Displayed value at which the retransmission output reaches its

minimum level (e.g. 4mA if type is 4-20mA).

Adjustable from -9999 to 9999.9

Hex

0868

4868

90D0

Output 1 Retransmit Input 1 Maximum

Value For Loop 1 Retransmit Maximum

Dec

2153

18537 37074

RW

Displayed value at which the retransmission output reaches its

maximum level (e.g. 2mA if type is 4-20mA).

Adjustable from -9999 to 9999.9

Hex

0869

4869

90D2