West Control Solutions Pro-EC44 User Manual

Page 188

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 181

9

Alarm/Events/Digital/Control inverted (Logical NOR of
selection)

Value 8 (Logical OR selection of Alarm/Events/Digital/Control) turns ON the LED if any of the selected
alarms, events, inputs or functions are active.
Value 9 (Logical NOR selection of Alarm/Events/Digital/Control) turns OFF the LED if any of the selected
alarms, events, inputs or functions are active.

Note: Pre-tune will flash the LED instead of turning it on, but flashing will be obscured if used in
conjunction with other functions when they are on.

LED 4 Alarm Indication

Bit

If bit =1, Alarm n status is selected

Dec

7714

24098

48196

RW

0

Alarm 1

Hex

1E22

5E22

BC44

1

Alarm 2

2

Alarm 3

3

Alarm 4

4

Alarm 5

5

Alarm 6

6

Alarm 7

LED 4 Event Indication

Bit

If bit =1, Event n status is selected

Dec

7716

24100

48200

RW

0

Event 1

Hex

1E24

5E24

BC48

1

Event 2

2

Event 3

3

Event 4

4

Event 5

5

Profile Running

6

Profile End

LED 4 Slot A & Soft Input Indication

Bit

If bit =1, Digital A / Soft Input n status is selected

Dec

7718

24102

48204

RW

0

Digital Input A

Hex

1E26

5E26

BC4C

1

Soft Digital 1

2

Soft Digital 2

3

Soft Digital 3

4

Soft Digital 4

LED 4 Option C Digital Indication

Bit

If bit =1, Digital Cn status is selected

Dec

7720

24104

48208

RW

0

Digital Input C1

Hex

1E28

5E28

BC50

1

Digital Input C2

2

Digital Input C3

3

Digital Input C4

4

Digital Input C5

5

Digital Input C6

6

Digital Input C7

LED 4 Control Indication

Bit

If bit =1, the function's status is selected

Dec

7650

24034

48068

RW

0

Loop 1 Auto Tune (self-tune=On, pre-tune=flashing)

Hex

1DE2

5DE2

BBC4

1

Loop 1 Manual Control

2

Loop 2 Auto Tune (self-tune=On, pre-tune=flashing)

3

Loop 2 Manual Control

Advertising
This manual is related to the following products: