West Control Solutions Pro-EC44 User Manual

Page 174

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 167

Alarm 4 Type

Value

Alarm 4 Type

Dec

6192

22576 45152

RW

0

Unused

Hex

1830

5830

B060

1

Process High Alarm

2

Process Low Alarm

3

Deviation Alarm (SP-PV)

4

Band Alarm

5

Input Rate of Change

6

Input/Sensor Break Alarm

7

Loop Alarm

10

% memory used

11

High Power Alarm

12

Low Power Alarm

Alarm 4 Value

Value At Which Alarm 4 Activates

Dec

6193

22577 45154

RW

Limited by input scaling for alarm types 1 to 4.

Not used for alarms 5, 6 or 7.

0 to 100% for alarms 10 to 12.

Hex

1831

5831

B062

Alarm 4 Rate of Change Value

Process Variable Rate of Change Alarm Threshold

Dec

6198

22582 45164

RW

Value for Rate of Change Alarm. Alarm 4 activates when PV

change exceeds this level. From 0.0 to 99999

Hex

1836

5836

B06C

Alarm 4 Hysteresis

Alarm 4 Hysteresis Value

Dec

6194

22578 45156

RW

Deadband value (on

“safe” side of alarm), through which signal

must pass before Alarm 4 deactivates.

Limited by the input scaling span

Hex

1832

5832

B064

Alarm 4 Inhibit Enable/disable

Value

Alarm 4 Power-up/Setpoint Change Inhibit

Dec

6195

22579 45158

RW

0

Disabled

Hex

1833

5833

B066

1

Enabled

Alarm 4 Status

Value

Alarm 4 Status

Dec

6196

22580 45160

RO

0

Inactive

Hex

1834

5834

B068

1

Active

Alarm 4 Inhibit Status

Value

Alarm 4 Inhibit Status

Dec

6197

22581 45162

RO

0

Not Inhibited

Hex

1835

5835

B06A

1

Inhibited

Alarm 4 Label

Main Language Name For Alarm 4 In Status Screen

Dec

6199

22583 45166

RW

8 ASCII characters replacing the title "Alarm 4" in alarm status

screens when main display language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1837

5837

B06E

Alarm 4 Alternate Label

Alternate Language Name For Alarm 4 In Status Screen

Dec

6200

22584 45168

RW

8 ASCII characters replacing the title "Alarm 4" in alarm status

screens when the alternate language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1838

5838

B070

Alarm 4 Minimum Duration

Alarm 4 Minimum Duration

Dec

6201

22585 45170

RW

Minimum time alarm 4 must be passed its threshold before

activating (deactivation is not affected by this parameter).

From 0 to 9999 secs

Hex

1839

5839

B072

Advertising
This manual is related to the following products: