Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 161

PID Set 2 - Integral Time

PID Set 2 - Integral Time For Loop 2

Dec

4449

20833 41666

RW

Gain Set 2 integral time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

1161

5161

A2C2

PID Set 2 - Derivative Time

PID Set 2 - Derivative Time For Loop 2

Dec

4450

20834 41668

RW

Gain Set 2 derivative time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

1162

5162

A2C4

PID Set 2 - Overlap/Deadband

PID Set 2 - Overlap/Deadband For Loop 2

Dec

4451

20835 41670

RW

PID Set 2 overlap (+ve) or deadband (-ve) between primary &

secondary prop bands. In display units - limited to 20% of the

combined band width.

Hex

1163

5163

A2C6

PID Set 2 - On/Off Differential

PID Set 2 - On/Off Differential For Loop 2

Dec

4478

20862 41724

RW

The on-off control hysteresis (deadband) for PID Set 2.

1 to 300 display units, centred about the setpoint.

Hex

117E

517E

A2FC

PID Set 3 - Primary Prop Band

PID Set 3 Primary Proportional Band For Loop 2

Dec

4452

20836 41672

RW

Primary Proportional Band for Gain Set 3.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

1164

5164

A2C8

PID Set 3 - Secondary Prop Band

PID Set 3 Secondary Proportional Band For Loop 2

Dec

4453

20837 41674

RW

Secondary Proportional Band for Gain Set 3.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

1165

5165

A2CA

PID Set 3 - Integral Time

PID Set 3 - Integral Time For Loop 2

Dec

4454

20838 41676

RW

Gain Set 3 integral time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

1166

5166

A2CC

PID Set 3 - Derivative Time

PID Set 3 - Derivative Time For Loop 2

Dec

4455

20839 41678

RW

Gain Set 3 derivative time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

1167

5167

A2CE

PID Set 3 - Overlap/Deadband

PID Set 3 - Overlap/Deadband For Loop 2

Dec

4456

20840 41680

RW

PID Set 3 overlap (+ve) or deadband (-ve) between primary &

secondary prop bands. In display units - limited to 20% of the

combined band width.

Hex

1168

5168

A2D0

PID Set 3 - On/Off Differential

PID Set 3 - On/Off Differential For Loop 2

Dec

4479

20863 41726

RW

The on-off control hysteresis (deadband) for PID Set 3.

1 to 300 display units, centred about the setpoint.

Hex

117F

517F

A2FE

PID Set 4 - Primary Prop Band

PID Set 4 Primary Proportional Band For Loop 2

Dec

4457

20841 41682

RW

Primary Proportional Band for Gain Set 4.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

1169

5169

A2D2

PID Set 4 - Secondary Prop Band

PID Set 4 Secondary Proportional Band For Loop 2

Dec

4458

20842 41684

RW

Secondary Proportional Band for Gain Set 4.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

116A

516A

A2D4

PID Set 4 - Integral Time

PID Set 4 - Integral Time For Loop 2

Dec

4459

20843 41686

RW

Gain Set 4 integral time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

116B

516B

A2D6

PID Set 4 - Derivative Time

PID Set 4 - Derivative Time For Loop 2

Dec

4460

20844 41688

RW

Gain Set 4 derivative time constant for Loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

116C

516C

A2D8