Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 153

Loop 1 Primary Power Upper limit

Loop 1 Primary Power Upper limit

Dec

4321

20705 41410

RW

10 to 100%

but must be at least 10% above the primary power lower limit.

Hex

10E1

50E1

A1C2

Loop 1 Primary Power Lower Limit

Loop 1 Primary Power Lower Limit

Dec

4322

20706 41412

RW

0 to 90%

but must be at least 10% below the primary power upper limit.

Hex

10E2

50E2

A1C4

Loop 1 Secondary Upper Power limit

Loop 1 Secondary Upper Power limit

Dec

4323

20707 41414

RW

10 to 100%

but must be at least 10% above the secondary power lower limit.

Hex

10E3

50E3

A1C6

Loop 1 Secondary Power Lower limit

Loop 1 Secondary Power Lower limit

Dec

4324

20708 41416

RW

0 to 90%

but must be at least 10% below the primary power upper limit.

Hex

10E4

50E4

A1C8

Loop 1 Pre-Tune Method

Value

Pre-tune type

Dec

4396

20780 41560

RW

0

Standard

Hex

112C

512C

A258

1

Pretune at Value

Loop 1 Pretune at Value

Value To Pre-tune Loop 1

Dec

4399

20783 41566

RW

Valid between the scaled input lower & upper limits

(applies if Pre-Tune Type = Pre-tune at Value)

Hex

112F

512F

A25E

Loop 1 Pretune Set

Value

PID Set Pre-tune Will Optimize

Dec

4397

20781 41562

RW

0

PID Set 1

Hex

112D

512D

A25A

1

PID Set 2

2

PID Set 3

3

PID Set 4

4

PID Set 5

Loop 1 Pretune Cascade Loop

Value

Cascade Loop To Be Pre-Tuned

Dec

4398

20782 41564

RW

0

Slave (opens cascade - close when finished)

Hex

112E

512E

A25C

1

Master (tunes master/slave combination)

Loop 1 Pre-Tune Engage/disengage

Value

Pre-Tune Engage/Disengage For Loop 1

Dec

4325

20709 41418

RW

0

Pre-Tune OFF

Hex

10E5

50E5

A1CA

1

Run Pre-Tune

Loop 1 Self-Tune Engage/disengage

Value

Self-Tune Engage/Disengage For Loop 1

Dec

4326

20710 41420

RW

0

Self-Tune OFF

Hex

10E6

50E6

A1CC

1

Self-Tune ON

Loop 1 Loop Alarm Type

Value

Loop Alarm Type For Loop 1

Dec

4327

20711 41422

RW

1

User Defined Time

Hex

10E7

50E7

A1CE

2

Automatic (2x Integral Time)

Loop Alarm Time

Loop Alarm Activation Time

Dec

4328

20712 41424

RW

1 to 5999 Seconds after output loop 1 power reaches saturation

Hex

10E8

50E8

A1D0

Loop 1 Primary Power

Loop 1 Primary Power Level

Dec

4329

20713 41426

RO

The current loop 1 primary power level (0 to 100%)

Hex

10E9

50E9

A1D2

Loop 1 Secondary Power

Loop 1 Secondary Power Level

Dec

4330

20714 41428

RO

The current loop 1 secondary power level (0 to 100%)

Hex

10EA

50EA

A1D4